https://www.phoenixcontact.com/us/products/2688080 I/O module - AXL AO 8 - 2688080 Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's documentation. Our General Terms of Use for Downloads are valid (http://phoenixcontact.com/download) Axioline analog output module, 8 outputs: 0 - 10 V, 10 V, 0 - 5 V, 5 V, 0 - 20 mA, 4 - 20 mA, 20 mA, 2-wire connection method (including bus base module and connectors) Product description The module is designed for use within an Axioline F station. It is used to output analog voltage and current signals. Product Features 8 analog, bipolar output channels for the connection of either voltage or current signals Connection of actuators in 2-wire technology Voltage ranges: 0 V ... 10 V, 10 V, 0 V ... 5 V, 5 V Current ranges: 0 mA ... 20 mA, 4 mA ... 20 mA, 20 mA Short-circuit-proof outputs Device rating plate stored Diagnostic and status indicators Key commercial data Packing unit 1 pc Weight per Piece (excluding packing) 260.0 GRM Custom tariff number 85389091 Country of origin Germany Technical data Dimensions Width 53.6 mm Height 126.1 mm Depth 54 mm Note on dimensions The depth is valid when a TH 35-7.5 DIN rail is used (according to EN 60715). 09/03/2014 Page 1 / 6 https://www.phoenixcontact.com/us/products/2688080 I/O module - AXL AO 8 - 2688080 Technical data Ambient conditions Ambient temperature (operation) -25 C ... 60 C Ambient temperature (storage/transport) -40 C ... 85 C Permissible humidity (operation) 5 % ... 95 % (according to DIN EN 61131-2) Permissible humidity (storage/transport) 5 % ... 95 % (according to DIN EN 61131-2) Air pressure (operation) 70 kPa ... 106 kPa (up to 3000 m above sea level) Air pressure (storage/transport) 70 kPa ... 106 kPa (up to 3000 m above sea level) Degree of protection IP20 Connection data Designation Axioline F connector Connection method Push-in technology Conductor cross section solid min. 0.2 mm Conductor cross section solid max. 1.5 mm Conductor cross section stranded min. 0.2 mm Conductor cross section stranded max. 1.5 mm Conductor cross section AWG/kcmil min. 24 Conductor cross section AWG/kcmil max 16 Stripping length 8 mm General Weight 260 g Note on weight specifications with connectors and bus base module Mounting type DIN rail Protection class III, IEC 61140, EN 61140, VDE 0140-1 Test section 5 V communications power (logic), 24 V supply (I/O) 500 V AC 50 Hz 1 min 5 V supply (logic)/analog outputs 500 V AC 50 Hz 1 min 5 V supply (logic)/functional earth ground 500 V AC 50 Hz 1 min 24 V supply (I/O)/analog outputs 500 V AC 50 Hz 1 min 24 V supply (I/O) / functional earth ground 500 V AC 50 Hz 1 min Analog outputs/functional earth ground 500 V AC 50 Hz 1 min Conformance with EMC directives Noise immunity test in accordance with EN 61000-6-2 Electrostatic discharge (ESD) EN 6100042/IEC 6100042 Criterion B; 6 kV contact discharge, 8 kV air discharge Noise immunity test in accordance with EN 61000-6-2 Electromagnetic fields EN 6100043/IEC 6100043 Criterion A; Field intensity: 10 V/m Noise immunity test in accordance with EN 61000-6-2 Fast transients (burst) EN 6100044/IEC 6100044 Criterion B, 2 kV Noise immunity test in accordance with EN 61000-6-2 Transient surge voltage (surge) EN 6100045/IEC 6100045 Criterion B; supply lines DC: 0.5 kV/0.5 kV (symmetrical/asymmetrical); 1 kV to shielded I/O cables 09/03/2014 Page 2 / 6 https://www.phoenixcontact.com/us/products/2688080 I/O module - AXL AO 8 - 2688080 Technical data General Noise immunity test in accordance with EN 61000-6-2 Conducted interference EN 6100046/IEC 6100046 Criterion A; Test voltage 10 V Noise emission test according to EN 61000-6-3 Radio interference properties EN 55022 Class B Mechanical tests Vibration resistance in acc. with EN 60068-2-6/IEC 60068-2-6 5g Shock in acc. with EN 60068-2-27/IEC 60068-2-27 25g, 11 ms period, halfsine shock pulse Continuous shock according to EN 60068-2-27/IEC 60068-2-27 10g Interfaces Designation Axioline F local bus Connection method Bus base module Transmission speed 100 MBit/s Axioline potentials Communications power UBus 5 V DC (via bus base module) Current consumption from UBus typ. 105 mA max. 130 mA Supply of analog modules UA 24 V DC Current consumption from UA typ. 50 mA (induced current consumption; no load, 0 V output) typ. 110 mA (8 voltage channels, 10 V output) max. 235 mA (8 current channels, 20 mA output) Analog outputs Number of outputs 8 Connection method Push-in technology 2-wire (shielded, twisted pair) Output name Analog outputs D/A conversion time 5 s D/A resolution 16 bit Type of protection Short-circuit and overload protection Transient protection Protective circuit/component Electronic Suppressor diode Data formats IB IL, S7-compatible Representation of output values 16 bits (15 bits + sign) Process data update 300 s Current output signal 0 mA ... 20 mA 4 mA ... 20 mA -20 mA ... 20 mA 09/03/2014 Page 3 / 6 https://www.phoenixcontact.com/us/products/2688080 I/O module - AXL AO 8 - 2688080 Technical data Analog outputs Load/output load current output to 500 Voltage output signal 0 V ... 5 V -5 V ... 5 V 0 V ... 10 V -10 V ... 10 V Load/output load voltage output > 2 k Precision typ. 0.1 % (of output range final value) typ. 0.1 % (of output range final value) Permissible cable length max. 250 m Classifications eCl@ss eCl@ss 4.0 27240405 eCl@ss 4.1 27240405 eCl@ss 5.0 27242201 eCl@ss 5.1 27242601 eCl@ss 6.0 27242601 eCl@ss 7.0 27242601 eCl@ss 8.0 27242601 ETIM ETIM 3.0 EC001599 ETIM 4.0 EC001599 ETIM 5.0 EC001596 UNSPSC UNSPSC 6.01 43172015 UNSPSC 7.0901 43201404 UNSPSC 11 39121311 UNSPSC 12.01 39121311 UNSPSC 13.2 39121311 Approvals Approvals 09/03/2014 Page 4 / 6 https://www.phoenixcontact.com/us/products/2688080 I/O module - AXL AO 8 - 2688080 Approvals Approvals UL Listed / cUL Listed / BSH / RINA / DNV / cULus Listed Ex Approvals Approvals submitted Approval details UL Listed cUL Listed BSH RINA DNV cULus Listed Drawings 09/03/2014 Page 5 / 6 https://www.phoenixcontact.com/us/products/2688080 I/O module - AXL AO 8 - 2688080 Dimensioned drawing 53,6 Connection diagram 54 U1 U2 I1 I2 U GND GND I 126,1 122,4 GND GND Connection for voltage and current output Block diagram Supervisor UBus 4x mC Axio bus FE # U D UA E1 E2 U/I REF # U/I U REF GND UANA 24 V AO 1...8 Internal wiring of the terminal points Phoenix Contact 2014 (c) - all rights reserved http://www.phoenixcontact.com 09/03/2014 Page 6 / 6