Millenium 3 logic controllers
Type Part number Power supply Inputs Outputs
With display
CD12 88970041 24 V c8 digital (of which 4 are analogue) 4 x 8 A relays
88970042 24 V c8 digital (of which 4 are analogue)
4 solid state 0.5 A (of which 1 is PWM)
88970043 100
V
240 V a8 digital 4 x 8 A relays
88970044 24 V a8 digital 4 x 8 A relays
88970045 12 V c8 digital (of which 4 are analogue) 4 x 8 A relays
CD20 88970051 24 V c12 digital (of which 6 are analogue) 8 x 8 A relays
88970052 24 V c12 digital (of which 6 are analogue)
8 solid state 0.5 A (of which 4 are PWM)
88970053 100
V
240 V a12 digital 8 x 8 A relays
88970054 24 V a12 digital 8 x 8 A relays
88970055 12 V c12 digital (of which 6 are analogue) 8 x 8 A relays
Without display
CB12 88970021 24 V c8 digital (of which 4 are analogue) 4 x 8 A relays
88970023 100
V
240 V a8 digital 4 x 8 A relays
88970024 24 V a8 digital 4 x 8 A relays
88970840 NEW 12 V c8 digital (of which 4 are analogue)
4 solid state 0.5 A (of which 1 is PWM)
CB20 88970031 24 V c12 digital (of which 6 are analogue) 8 x 8 A relays
88970033 100
V
240 V a12 digital 8 x 8 A relays
88970034 24 V a12 digital 8 x 8 A relays
M3 SOFT
Multilingual programming software
(CD-ROM) including a library of
specifi c functions.
Part no.: 88970111
M3 ALARM
Alarm management software (CD-ROM)
Part no.: 88970116
This software is used alongside the
M3MOD communication interface
(part no.: 88970117).
Optimum memory capacity
Ergonomic display
Millenium 3 logic controllers operate with the following software:
For all details of hardware adaptation, see pages 64-65.
26 www.millenium3.crouzet.com
Modem
communication solutions
Modular power supplies (1) Starter kits
and demo
case
M3MOD STN GSM 12 V DC - 24 W 24 V DC - 7.5 W 24 V DC - 15 W 24 V DC - 30 W 24 V DC - 60 W
88970117 88970118 88970119 88950306 88950303 88950304 88950307 88950302 Standard
bvv bbbb 88970080
bvv bbbb 88970106 (case)
bvv 88970081
bvv
bvvb
bvv bbbb 88970082
bvv bbbb
bvv 88970083
bvv
bvvb
bvv bbbb
bvv
bvv
bvvb
bvv bbbb
bvv
bvv
Millenium 3 Standard
NEW NEW NEW NEW
“Compact” range selection guide
The 4 starter kits each contain:
1 CD12 or CD20 logic controller + 1 USB link cable +
1 M3 SOFT programming software application (CD-ROM)
including a library of specifi c functions.
Part no.: 88970080 / 88970081 / 88970082 / 88970083
The demonstration case contains:
1 CD12 logic controller + 1 USB link cable +
1 M3 SOFT programming software application (CD-ROM)
including the library of specifi c functions + 1 voltage adaptor +
1 I/O simulation card.
Part no.: 88970106
bCompatible
v Mounted with the M3MOD:
- STN modem,
- or GSM modem
(1) Find the whole “Power Supplies” offer on pages 58-59.
27
www.millenium3.crouzet.com
28 www.millenium3.crouzet.com
"Compact" range with display
Budget solution with display
Memory: 120 lines in LADDER language and up to 350
"typical" blocks in FBD language
LCD with 4 lines of 18 characters and configurable
backlighting
Selective parameter setting: You can choose the
parameters that can be adjusted on the front panel
Analogue inputs 0-10 V or 0-20 mA/Pt 100 with
converters (see page 50)
Type Input Output Supply Code
CD12 8 digital (including 4 analogue) 4 relays 8 A 24 V 88970041
8 digital (including 4 analogue) 4 solid state 0.5 A (including 1 PWM) 24 V 88970042
8 digital 4 relays 8 A 100 240 V 88970043
8 digital 4 relays 8 A 24 V 88970044
8 digital (including 4 analogue) 4 relays 8 A 12 V 88970045
CD20 12 digital (including 6 analogue) 8 relays 8 A 24 V 88970051
12 digital (including 6 analogue) 8 solid state 0.5 A (including 4 PWM) 24 V 88970052
12 digital 8 relays 8 A 100 240 V 88970053
12 digital 8 relays 8 A 24 V 88970054
12 digital (including 6 analogue) 8 relays 8 A 12 V 88970055
Type Description Code
M3 SOFT Multilingual programming software containing specific library functions (CD-ROM) 88970111
PA EEPROM memory cartridge 88970108
3 m serial link cable: PC Millenium 3 88970102
3 m USB link cable: PC Millenium 3 88970109
Millenium 3 Bluetooth interface (class A 10 m) 88970104
Type Input Output Supply Code
Kit 12 8 digital (including 4 analogue) 4 relays 24 V 88970080
8 digital 4 relays 100 240 V 88970081
Kit 20 12 digital (including 6 analogue) 8 relays 24 V 88970082
12 digital 8 relays 100 240 V 88970083
CD12 CD20
See Page 40-43 for details or to find instruction sheets visit: www.millenium3.crouzet.com in "Download"
Millenium 3 Standard
CD12 CD20
Part numbers
Accessories
Starter kits (see page 27 for details)
Dimensions (mm)
35 27,5 27,5
1 2 1 2 1 2 1 2
100
59,9
71,2
58
68
90
107,6
A B OK ESC
+
35 27,5 27,5
58
68
90
107,6
100
113,3
124,6
A B OK ESC
+
Input / Output Connections
For adapted products, see page page 64-65
29
www.millenium3.crouzet.com
Millenium 3 Standard
"Compact" range without display
Simply a control system solution inside a modular
casing
Memory: 120 lines in LADDER language and up to 350
"typical" blocks in FBD language
No display or parameter-setting buttons to avoid
tampering by unauthorised users
Analogue inputs 0-10 V or 0-20 mA/Pt 100 with
converters (see page 50)
Type Input Output Supply Code
CB12 8 digital (including 4 analogue) 4 relays 8 A 24 V 88970021
8 digital 4 relays 8 A 100 240 V 88970023
8 digital 4 relays 8 A 24 V 88970024
8 digital (including 4 analogue) 4 solid state 0.5 A (including 1 PWM) 12 V 88970840
CB20 12 digital (including 6 analogue) 8 relays 8 A 24 V 88970031
12 digital 8 relays 8 A 100 240 V 88970033
12 digital 8 relays 8 A 24 V 88970034
Type Description Code
M3 SOFT Multilingual programming software containing specific library functions (CD-ROM) 88970111
PA EEPROM memory cartridge 88970108
3 m serial link cable: PC Millenium 3 88970102
3 m USB link cable: PC Millenium 3 88970109
Millenium 3 Bluetooth interface (class A 10 m) 88970104
CB12 CB20
See Page 40-43 for details or to find instruction sheets visit: www.millenium3.crouzet.com in "Download"
CB12 CB20
Part numbers
Accessories
Dimensions (mm)
35 27,5 27,5
1 2 1 2 1 2 1 2
100
59,9
71,2
57,5
67,5
90
107,6
35 27,5 27,5
57,5
67,5
90
107,6
100
113,3
124,6
Input / Output Connections
For adapted products, see page page 64-65
Extensions "Sandwich"
Type Part number Power supply Inputs Outputs
TOR
XE10 88970321 Via the 24 V ccontroller 6 digital
4 x 5 A relays, 1 of which is a changeover relay
88970323 100
V
240 V a6 digital
4 x 5 A relays, 1 of which is a changeover relay
88970324 24 V a6 digital
4 x 5 A relays, 1 of which is a changeover relay
Type Part number Power supply Mains Characteristics of exchanges (words)
Communication
XN05 88970270 Via the 24 V ccontroller Modbus TCP Ethernet protocol Read: 8 - Read/Write: 8
Clock: 4 - Status: 1
XN03 88970250 Via the 24 V ccontroller Modbus RS-485
(slave)
Read: 8 - Read/Write: 8
Clock: 4 - Status: 1
XN06 88972250 Via the 24 V ccontroller Modbus RS-485
(slave)
Read: 8 - Read/Write: 8
Clock: 4 - Status: 1
Millenium 3 logic controllers
Type Part number Power supply Inputs Outputs
With XD10/
XD26 display
Without display
XB10/XB26
88970141 88970131 24 V c
6 digital (of which 4 are analogue)
4 x 8 A relays
88970142 88970132 24 V c
6 digital (of which 4 are analogue)
4 solid state 0.5 A (of which 1 is PWM)
88970143 88970133 100
V
240 V a6 digital 4 x 8 A relays
88970144 88970134 24 V a6 digital 4 x 8 A relays
88970161 88970151 24 V c
16 digital (of which 6 are analogue)
10 relays, of which 8 are 8 A and 2 are 5 A
88970162 88970152 24 V c
16 digital (of which 6 are analogue)
10 solid state 0.5 A (of which 4 are PWM)
88970163 88970153 100
V
240 V a16 digital
10 relays, of which 8 are 8 A and 2 are 5 A
88970164 88970154 24 V a16 digital
10 relays, of which 8 are 8 A and 2 are 5 A
88970165 88970155 12 V c
16 digital (of which 6 are analogue)
10 relays, of which 8 are 8 A and 2 are 5 A
88970814 - 12 V c
16 digital (of which 6 are analogue)
10 solid state 0.5 A (of which 4 are PWM)
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
NEW
Millenium 3 logic controllers operate with the following software:
M3 SOFT
Multilingual programming software (CD-ROM) including
the library of specifi c functions.
Part no.: 88970111
M3 ALARM
Alarm management software (CD-ROM)
Part no.: 88970116
This software is used alongside the M3MOD communication
interface (part no.: 88970117).
For all details of hardware adaptation, see pages 64-65.
30 www.millenium3.crouzet.com
Modem
communication solutions
Modular power supplies (1) Starter
kits
M3MOD STN GSM 12 V DC - 24 W 24 V DC - 7.5 W 24 V DC - 15 W 24 V DC - 30 W 24 V DC - 60 W
88970117 88970118 88970119 88950306 88950303 88950304 88950307 88950302 Expandable
bvv bbbb
bvv bbbb
bvv
bvv
bvv bbbb 88970084
bvv bbbb
bvv 88970085
bvv
bvvb
bvvb
Termination extensions
Type Part number Power supply Inputs Outputs
Digital
XR06 88970211
Via the
24 V ccontroller 4 digital 2 x 8 A relays
88970213
Via the 100
V
240 V a
controller 4 digital 2 x 8 A relays
88970214 Via the 24 V acontroller 4 digital 2 x 8 A relays
88970215 Via the 12 V ccontroller 4 digital 2 x 8 A relays
XR10 88970221 Via the 24 V ccontroller 6 digital 4 x 8 A relays
88970223
Via the 100
V
240 V a
controller 6 digital 4 x 8 A relays
88970224 Via the 24 V acontroller 6 digital 4 x 8 A relays
88970225 Via the 12 V ccontroller 6 digital 4 x 8 A relays
XR14 88970231 Via the 24 V ccontroller 8 digital 6 relays, of which 4 are 8 A and 2 are 5 A
88970233
Via the 100
V
240 V a
controller 8 digital 6 relays, of which 4 are 8 A and 2 are 5 A
88970234 Via the 24 V acontroller 8 digital 6 relays, of which 4 are 8 A and 2 are 5 A
88970235 Via the 12 V ccontroller 8 digital 6 relays, of which 4 are 8 A and 2 are 5 A
Analogue
XA04 88970241 Via the 24 V ccontroller 1 analogue (0-10 V/0-20 mA),
1 analogue (0-10 V/0-20 mA/Pt100)
2 analogue (0-10 V)/PWM
Millenium 3 Standard
NEW NEW NEW NEW
b Compatible
v Mounted with the M3MOD:
- STN modem,
- or GSM modem
(1) Find the whole “Power Supplies” offer on pages 58-59.
The 2 starter kits each contain:
1 XD26 logic controller + 1 USB link cable +
1 M3 SOFT programming software application (CD-ROM) including
a library of specifi c functions.
Part no.: 88970084 / 88970085
“Expandable” range selection guide
31
www.millenium3.crouzet.com
32 www.millenium3.crouzet.com
"Expandable" range with display
"High-performance" expandable solution with display
Extended memory: 120 lines in LADDER language and
up to 700 "typical" blocks in FBD language
LCD with 4 lines of 18 characters and configurable
backlighting
Selective parameter setting: You can choose the
parameters that can be adjusted on the front panel
Analogue inputs 0-10 V or 0-20 mA/Pt 100 with
converters (see page 50)
Open to XN network communication extensions and
digital I/O or analogue extensions
Type Input Output Supply Code
XD10 6 digital (including 4 analogue) 4 relays 8 A 24 V 88970141
6 digital (including 4 analogue) 4 solid state 0.5 A (including 1 PWM) 24 V 88970142
6 digital 4 relays 8 A 100 240 V 88970143
6 digital 4 relays 8 A 24 V 88970144
XD26 16 digital (including 6 analogue) 10 relays (8 x 8 A relay and 2 x 5 A relay) 24 V 88970161
16 digital (including 6 analogue) 10 solid state 0.5 A (including 4 PWM) 24 V 88970162
16 digital 10 relays (8 x 8 A relay and 2 x 5 A relay) 100 240 V 88970163
16 digital 10 relays (8 x 8 A relay and 2 x 5 A relay) 24 V 88970164
16 digital (including 6 analogue) 10 relays (8 x 8 A relay and 2 x 5 A relay) 12 V 88970165
16 digital (including 6 analogue) 10 solid state 0.5 A (including 4 PWM) 12 V 88970814
Type Description Code
M3 SOFT Multilingual programming software containing specific library functions (CD-ROM) 88970111
PA EEPROM memory cartridge 88970108
3 m serial link cable: PC Millenium 3 88970102
3 m USB link cable: PC Millenium 3 88970109
Millenium 3 Bluetooth interface (class A 10 m) 88970104
Type Input Output Supply Code
Kit 26 16 digital (including 6 analogue) 10 relays (8 x 8 A relay and 2 x 5 A relay) 24 V 88970084
16 digital 10 relays (8 x 8 A relay and 2 x 5 A relay) 100 240 V 88970085
XD10 XD26
See Page 40-43 for details or to find instruction sheets visit: www.millenium3.crouzet.com in "Download"
Millenium 3 Standard
XD10 XD26
Part numbers
Accessories
Starter kits (see page 31 for details)
Dimensions (mm)
35 27,5 27,5
1 2 1 2 1 2 1 2
100
59,9
71,2
58
68
90
107,6
A B OK ESC
+
35 27,5 27,5
58
68
90
107,6
100
113,3
124,6
A B OK ESC
+
Input / Output Connections
For adapted products, see page page 64-65
33
www.millenium3.crouzet.com
Millenium 3 Standard
"Expandable" range without display
"High-performance" expandable solution without
display
Extended memory: 120 lines in LADDER language and
up to 700 "typical" blocks in FBD language
No display or parameter-setting buttons to avoid
tampering by unauthorised users
Analogue inputs 0-10 V or 0-20 mA/Pt 100 with
converters (see page 50)
Open to XN network communication extensions and
digital I/O or analogue extensions
Type Input Output Supply Code
XB10 6 digital (including 4 analogue) 4 relays 8 A 24 V 88970131*
6 digital (including 4 analogue) 4 solid state 0.5 A (including 1 PWM) 24 V 88970132
6 digital 4 relays 8 A 100 240 V 88970133*
6 digital 4 relays 8 A 24 V 88970134
XB26 16 digital (including 6 analogue) 10 relays (8 x 8 A relay and 2 x 5 A relay) 24 V 88970151
16 digital (including 6 analogue) 10 solid state 0.5 A (including 4 PWM) 24 V 88970152
16 digital 10 relays (8 x 8 A relay and 2 x 5 A relay) 100 240 V 88970153
16 digital 10 relays (8 x 8 A relay and 2 x 5 A relay) 24 V 88970154
16 digital (including 6 analogue) 10 relays (8 x 8 A relay and 2 x 5 A relay) 12 V 88970155
*Available 2nd quarter of 2008
See page 22, except:
Certifications UL, CSA
Type Description Code
M3 SOFT Multilingual programming software containing specific library functions (CD-ROM) 88970111
PA EEPROM memory cartridge 88970108
PA 3 m serial link cable: PC Millenium 3 88970102
PA 3 m USB link cable: PC Millenium 3 88970109
PA Millenium 3 Bluetooth interface (class A 10 m) 88970104
XB10 XB26
See Page 40-43 for details or to find instruction sheets visit: www.millenium3.crouzet.com in "Download"
Millenium 3 Standard
XB10 XB26
Part numbers
General characteristics
Accessories
Dimensions (mm)
35 27,5 27,5
1 2 1 2 1 2 1 2
100
59,9
71,2
57,5
67,5
90
107,6
Input / Output Connections
For adapted products, see page 64-65
35 27,5 27,5
57,5
67,5
90
107,6
100
113,3
124,6
34 www.millenium3.crouzet.com
Sandwich communication extensions for XD10/XB10 & XD26/XB26
Exchange of input/output state or of internal values via
communication networks
Power supply via the controller
Type Description Supply Code
XN03 Modbus RS-485 slave communication extension 4 words Via the 24 V controller 88970250
XN06 Modbus RS-485 slave communication extension 8 words Via the 24 V controller 88972250
XN05 Ethernet protocol TCP Modbus extension Via the 24 V controller 88970270
General characteristics 88970250 & 88972250 88970270
See page 22, except:
Certifications UL, CSA, GL (UL, CSA: 88972250) UL, CSA
GL pending
Earthing Yes, refer to the quick reference guide supplied with
the product
Yes, refer to the quick reference guide supplied
with the product
Operating temperature -20 +55°C (+40°C in a non-ventilated
enclosure) in accordance with IEC/EN 60068-
2-1 and IEC/EN 60068-2-2
0 +55°C (+40°C in a non-ventilated
enclosure) in accordance with IEC 60068-2-1
and IEC 60068-2-2
Cable length Maximum length of the network: 1000 m
(9600 Baud max, AWG26)
Maximum length between 2 controllers: 100 m
Communication parameters 88970250 & 88972250 88970270
Type of link 2 or 4-wire; RTU or ASCII -
Transmission rate (Bauds) 1200, 2400, 4800, 9600, 19200, 28800, 38400,
57600
-
Parity None; even; odd -
Addressing 1 247 Static or dynamic
Characteristics of exchanges 88970250 88972250 88970270
Programming with Ladder language
Image of smart relay I/O 4 4 -
Status 1 1 -
Programming with FBD language
Read 4 8 8
Read/Write 4 8 8
Clock words 412 4
Status words 1 1 1
XN03 - XN05 - XN06
Millenium 3 Standard
XN03 XN06 XN05
Part numbers
Characteristics of communication extensions
Dimensions (mm)
10
57
52,5
70
44
15
25
90
35 27,527,5
108
35
100
For adapted products, see page 64-65
35
www.millenium3.crouzet.com
Millenium 3 Standard
Digital sandwich extension for XD10/XB10 and XD26/XB26
Can be used to reach up to 50 inputs/outputs in
conjunction with XR14 termination extensions
Relay outputs one of which is a changeover relay
Type Input Output Supply Code
XE10 6 digital 4 relays 5 A (1 of which is a changeover relay) Via the 24 V controller 88970321
6 digital 4 relays 5 A (1 of which is a changeover relay) 100 240 V 88970323
6 digital 4 relays 5 A (1 of which is a changeover relay) 24 V 88970324
XE10
See Page 40-43 for details or to find instruction sheets visit: www.millenium3.crouzet.com in "Download"
XE10
Part numbers
Dimensions (mm)
35 27,527,5
57,4
70
90
107,6
60
72
100
Input / Output Connections
For adapted products, see page page 64-65
36 www.millenium3.crouzet.com
Digital extension for XD10/XB10 and XD26/XB26
Analogue extension for XD10/XB10 and XD26/XB26
Power supply via the controller at the same voltage as
the inputs
Number of inputs/outputs can be configured in
accordance with your requirements
Type Input Output Supply Code
XR06 4 digital 2 relays 8 A Via the 24 V controller 88970211
4 digital 2 relays 8 A Via the 100 240 V controller 88970213
4 digital 2 relays 8 A Via the 24 V controller 88970214
4 digital 2 relays 8 A Via the 12 V controller 88970215
XR10 6 digital 4 relays 8 A Via the 24 V controller 88970221
6 digital 4 relays 8 A Via the 100 240 V controller 88970223
6 digital 4 relays 8 A Via the 24 V controller 88970224
6 digital 4 relays 8 A Via the 12 V controller 88970225
XR14 8 digital 6 relays (4 x 8 A relay and 2 x 5 A relay) Via the 24 V controller 88970231
8 digital 6 relays (4 x 8 A relay and 2 x 5 A relay) Via the 100 240 V controller 88970233
8 digital 6 relays (4 x 8 A relay and 2 x 5 A relay) Via the 24 V controller 88970234
8 digital 6 relays (4 x 8 A relay and 2 x 5 A relay) Via the 12 V controller 88970235
XR06 XR10 - XR14
See Page 40-43 for details or to find instruction sheets visit: www.millenium3.crouzet.com in "Download"
Direct connection of analogue 0-10 V or 0-20 mA or
Pt 100 inputs (10 bits) can be configured using the M3
SOFT
2 analogue 0-10 V or PWM outputs (10 bits) can be
configured using the M3 SOFT software
Ramp can be parameterised for outputs used as 0-10 V
outputs
Power supply via the controller
Type Input Output Supply Code
XA04 1 analogue (0-10 V / 0-20 mA),
1 analogue (0-10 V / 0-20 mA / Pt100)
2 analogue (0-10 V) / PWM Via the 24 V controller 88970241
Millenium 3 Standard
XR06 XR10 XR14
Part numbers
Dimensions (mm)
35 27,527,5
57,4
70
90
107,6
25
35,5
100
35 27,527,5
57,4
70
90
107,6
60
72
100
Input / Output Connections
XA04
Part numbers
For adapted products, see page page 64-65
37
www.millenium3.crouzet.com
Millenium 3 Standard
General characteristics of analogue extension 88970241
See page 22, except:
Certifications UL, CSA
GL (pending)
Earthing Yes, refer to the quick reference guide supplied with the product
Analogue inputs
Inputs used as analogue inputs 0-10 V 0-20 mA Pt 100
Input IP and IQ IP and IQ IQ
Input range 0 10 V 0 20 mA -25 125°C
Input impedance 18 kΩ246 Ω-
Maximum non destructive current/voltage 30 V 30 mA -
Value of LSB 9.8 mV 20 μA 0.15°C
Input type Common mode Common mode Pt 100 probe - IEC 751 - 3-wire
Resolution 10 bits 10 bits 10 bits
Conversion time Module cycle time Module cycle time Module cycle time
Accuracy at 25°C ± 1% ± 1% ±1.5°C
Accuracy at 55°C ± 1% ± 1% ±1.5°C
Isolation between analogue channel and power
supply
None None None
Longueur câble 10 m maximum, with shielded
cable (sensor not isolated)
10 m maximum, with shielded
cable (sensor not isolated)
10 m maximum, with shielded
cable (sensor not isolated)
Protection against polarity inversions Command ignored Command ignored Command ignored
Analogue outputs
Range output 0 10 V
Input type Resistive
Max. load 10 mA
Value of LSB 10 mV
Resolution 10 bits
Conversion time Controller cycle time
Accuracy at 25°C ±1% of full scale
Accuracy at 55°C ±1% of full scale
Repeat accuracy at 55 °C ± 1%
Isolation between analogue channel and power
supply
None
Cable length 10 metres maximum, with shielded cable (sensor not isolated)
Protection against polarity inversions Yes
PWM
Range output V power supply
Max. load 1.2 kΩ (I 20 mA)
PWM cyclic ratio 1024 steps
Frequency 78 Hz, 312.5 Hz, 666.6 Hz, 1000 Hz, 1250 Hz, 1428 Hz, 1666 Hz, 2000 Hz
Accuracy 1% across the entire temperature range for PWM ratios from 5% to 95%
Built-in protections Against overvoltages: Yes
XA04
See Page 40-43 for details or to find instruction sheets visit: www.millenium3.crouzet.com in "Download"
Characteristics of analogue extension 88970241
Dimensions (mm)
35 27,527,5
57,4
70
90
107,6
25
35,5
100
Input / Output Connections
For adapted products, see page page 64-65
38 www.millenium3.crouzet.com
Modem communication plug and play solutions
For remote control of your application
Automatic notification of alarms via SMS (GSM
Modem) / email or on a PC with M3 ALARM software.
Millenium 3 program can be downloaded, modified
and sent
Input and output states, as well as all program values,
can be polled and controlled remotely
2 types of pre-configured ready-to-use modem:
- STN modem for wired transmission networks
- GSM modem for wireless communication
Type Description Supply Code
M3MOD Modem communication interface 12-24 V 88970117
STN STN modem 12-24 V 88970118
GSM GSM modem
850/900/1800/1900 MHz 12-24 V 88970119
Type Description Code
PA 1.80 m serial link cable: DB9/DB9 88970123
M3 ALARM Alarm management software (CD-ROM) 88970116
General characteristics of the modem communication 88970117 88970118 88970119
See page 22, except:
Certifications UL, CSA UL, CSA UL, CSA, CE, FCC, IC,
PTCRB, R&TTE
Power supply 88970117 88970118 88970119
Nominal voltage (V) 12 24 V 12 24 V 12 24 V
Operating limits -13% / + 20%
or 10 28.8 V
-13% / + 5%
or 10 30 V
-54% / + 33%
or 5.5 32 V
Ripple 5% max. - -
Nominal current under 12 V DC 30 mA 140 mA 165 mA
Nominal current under 24 V DC 30 mA 70 mA 87 mA
Peak current on energisation 550 mA 9600 mA 2100 mA at 5.5 V
Max. absorbed power 1.1 W -2.1 W
Immunity from micro power cuts 1 ms, repetition 20 times No -
Protection against polarity inversions Yes -No
Fuse protection 1 A fuse -With fuse 2.5 A
Characteristics of the "COM-M3" link with the controller
Type of connector Specific Millenium
Type of link Specific Millenium communication protocol
Compatibility Only with Millenium controllers version V2.1
Isolation of "Com-M3" connector from the "Com-M" connector Via optocoupler 1780 V
Isolation of "Com-M3" connector from the ± supply terminals Via optocoupler 1780 V
Characteristics of the "COM-M3" link with the modem
Type of connector Specific Millenium
Type of link with Modem connector cable RS 232 serial (supplied with the communication interface)
Compatibility Only with Millenium controllers version V2.1
Analogue RTC modem compatibility AT commands
GSM modem compatibility AT commands
Isolation of "Com-M" connector from the Modem Via link cable to Modem (supplied)
Isolation of "Com-M" connector from the ± supply terminals Via link cable to Modem (supplied)
Millenium 3 Standard
Part numbers
Accessories
Characteristics of the communication Modem system
M3MOD STN GSM