Early-make time of the HIV compared to the main contacts during with make and
break switching.
(switch times with manual operation):
NZM1, PN1, N(S)1: ca. 20 ms
NZM2, PN2, N(S)2: ca. 20 ms
NZM3, PN3, N(S)3: ca. 20 ms
NZM4, N(S)4: approx. 90 ms, the HIV switch early Offswitching not forward.
Terminal capacities mm2
Solid or flexible conductor, with ferrule mm21 x (0,75 - 2,5)
2 x (0,75 - 2,5)
UL/CSA
Rated operational current IeA 5 A – 600 V AC
1 A - 250 V DC
Other technical data (sheet catalogue) Maximum equipment and position of the internal accessories
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation InA 6
Heat dissipation per pole, current-dependent Pvid W 0.11
Equipment heat dissipation, current-dependent Pvid W 0
Static heat dissipation, non-current-dependent Pvs W 0
Heat dissipation capacity Pdiss W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 70
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Technical data ETIM 7.0
Low-voltage industrial components (EG000017) / Auxiliary contact block (EC000041)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Component for low-voltage switching technology / Auxiliary switch block
(ecl@ss10.0.1-27-37-13-02 [AKN342013])
12/29/2020 Eaton 216376 ED2020 V75.0 EN 4 / 6