DATASHEET - M22-K10
Contact element, Screw terminals, Front fixing, 1 N/O, 24 V 3 A, 220 V 230
V 240 V 6 A
Part no. M22-K10
Catalog No. 216376
Alternate Catalog
No.
M22-K10Q
EL-Nummer
(Norway)
4355363
Delivery program
Product range Accessories
Basic function accessories Contact elements
Accessories Auxiliary contact
Accessories Standard auxiliary contact, trip-indicating auxiliary switch
Standard/Approval UL/CSA, IEC
Construction size NZM1/2/3/4
Connection technique Screw terminals
Fixing Front fixing
Degree of Protection IP20
Connection to SmartWire-DT no
For use with NZM1(-4), 2(-4), 3(-4), 4(-4)
PN1(-4), 2(-4), 3(-4)
N(S)1(-4), 2(-4), 3(-4), 4(-4)
Approval
Contacts
N/O = Normally open 1 N/O
Contact sequence
Contact travel diagram, stroke in connection with front
element
Contact diagram
12/29/2020 Eaton 216376 ED2020 V75.0 EN 1 / 6
Configuration
Connection type Single contact
Description of HIA trip-indicating auxiliary contact General trip indication '+', when tripped by shunt release, overload release, short-
circuit release or by the residual-current release due to residual-current.
Can be used with NZM1, 2, 3 circuit-breaker: a trip-indicating auxiliary contact can
be clipped into the circuit-breaker.
Can be used with NZM4 circuit-breaker: up to two standard auxiliary contacts can
be clipped into the circuit-breaker.
Any combinations of the auxiliary contact types are possible.
Not in combination with switch-disconnector PN…
Marking on switch: HIA
Labeling in FI-Block: HIAFI.
If the trip-indicating auxiliary switch in the fault current block is used, the NC
contacts operates as a N/O contact and the NC contact operates as an N/O
contact.
Description standard auxiliary contact HIN Switching with the main contacts Used for indicating and interlocking tasks.
Can be used with NZM1 circuit-breaker: a standard auxiliary contact can be
clipped into the circuit-breaker.
Can be used with NZM2 size circuit-breaker: a standard auxiliary contact can be
clipped into the circuit-breaker.
Can be used with NZM3, 4 circuit-breaker: up to three standard auxiliary contacts
can be clipped into the circuit-breaker.
Any combinations of the auxiliary contact types are possible.
Marking on switch: HIN.
On combination with remote operator NZM-XR... the right mounting location of
standard auxiliary contact HIN can be fitted only with individual contacts.
Connection technique Screw terminals
Notes
For Std. pack:
M22‐(C)K… : Std. pack = 20 off
Notes
The following can be clipped into the switches:
NZM1: a standard auxiliary contact
NZM2: up to two M22-(C)K… standard auxiliary contacts
NZM3: up to three M22-(C)K… standard auxiliary contacts
NZM4: up to three M22-(C)K… standard auxiliary contacts
Any combinations of the auxiliary contact types are possible.
Marking on switch: HIN
In combination with remote operator NZM‐XR… only single contacts can be fitted to some installation locations of the standard auxiliary contact.
NZM2: Only single contact can be fitted in left installation location of standard auxiliary contact.
NZM3: Only single contact can be fitted in installation locations of standard auxiliary contact.
NZM4: Only single contact can be fitted in right installation location of standard auxiliary contact.
Technical data
General
Standards IEC 60947-5-1
Lifespan, mechanical Operations x 106> 5
Operating frequency Operations/h ≦ 3600
Actuating force n ≦ 5
Operating torque (screw terminals) Nm ≦ 0.8
Degree of Protection IP20
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Open °C -25 - +70
Mechanical shock resistance to IEC 60068-2-27 Shock duration 11 ms, half-
sinusoidal
g > 30
Terminal capacities mm2
Solid mm20.75 - 2.5
Stranded mm20.5 - 2.5
Flexible with ferrule mm20.5 - 1.5
Contacts
Rated impulse withstand voltage Uimp V AC 6000
12/29/2020 Eaton 216376 ED2020 V75.0 EN 2 / 6
Rated insulation voltage UiV 500
Overvoltage category/pollution degree III/3
Control circuit reliability
at 24 V DC/5 mA HFFault
probability
< 10-7 (i.e. 1 failure to 107 operations)
at 5 V DC/1 mA HFFault
probability
< 5 x 10-6 (i.e. 1 failure in 5 x 106 operations)
Max. short-circuit protective device
Fuseless Type PKZM0-10/FAZ-B6/1
Fuse gG/gL A 10
Switching capacity
Rated operational current IeA
AC-15
115 V IeA 6
220 V 230 V 240 V IeA 6
380 V 400 V 415 V IeA 4
500 V IeA 2
DC-13
24 V IeA 3
42 V IeA 1.7
60 V IeA 1.2
110 V IeA 0.6
220 V IeA 0.3
Lifespan, electrical
AC-15
230 V/0.5 A Operations x 1061.6
230 V/1.0 A Operations x 1061
230 V/3.0 A Operations x 1060.7
DV-13
12 V/2.8 A Operations x 1061.2
Auxiliary contacts
Rated operational voltage UeV
Rated operational voltage Ue V AC 500
Rated operational voltage, max. Ue V DC 220
Conventional thermal current Ith = IeCSA 4
Rated operational current IeA
Different rated operational currents when used as auxiliary contact for NZM
circuit-breaker
M22-
(C)K10(01)
M22-
CK11(02)
(20)
XHIV
bei
AC =
50/60
Hz
Bemessungsbetriebsstrom
AC-15115
V
Ie A 4 4 4
230
V
Ie A 4 4 4
400
V
Ie A 2 - 2
500
V
Ie A 1 - 1
DC-1324 V Ie A 3 3 3
42 V Ie A 1.7 1 1.5
60 V Ie A 1.2 0.8 0.8
110
V
Ie A 0.6 0.5 0.5
220
V
Ie A 0.3 0.2 0.2
Short-circuit protection
max. fuse A gG/gL 10
Max. miniature circuit-breaker A FAZ-B6/B1
Operating times
12/29/2020 Eaton 216376 ED2020 V75.0 EN 3 / 6
Early-make time of the HIV compared to the main contacts during with make and
break switching.
(switch times with manual operation):
NZM1, PN1, N(S)1: ca. 20 ms
NZM2, PN2, N(S)2: ca. 20 ms
NZM3, PN3, N(S)3: ca. 20 ms
NZM4, N(S)4: approx. 90 ms, the HIV switch early Offswitching not forward.
Terminal capacities mm2
Solid or flexible conductor, with ferrule mm21 x (0,75 - 2,5)
2 x (0,75 - 2,5)
UL/CSA
Rated operational current IeA 5 A – 600 V AC
1 A - 250 V DC
Other technical data (sheet catalogue) Maximum equipment and position of the internal accessories
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation InA 6
Heat dissipation per pole, current-dependent Pvid W 0.11
Equipment heat dissipation, current-dependent Pvid W 0
Static heat dissipation, non-current-dependent Pvs W 0
Heat dissipation capacity Pdiss W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 70
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat
and fire due to internal electric effects
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation Meets the product standard's requirements.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Technical data ETIM 7.0
Low-voltage industrial components (EG000017) / Auxiliary contact block (EC000041)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Component for low-voltage switching technology / Auxiliary switch block
(ecl@ss10.0.1-27-37-13-02 [AKN342013])
12/29/2020 Eaton 216376 ED2020 V75.0 EN 4 / 6
Number of contacts as change-over contact 0
Number of contacts as normally open contact 1
Number of contacts as normally closed contact 0
Number of fault-signal switches 0
Rated operation current Ie at AC-15, 230 V A 6
Type of electric connection Screw connection
Model Top mounting and integrable
Mounting method Front fastening
Lamp holder None
Approvals
Product Standards IEC/EN 60947-5; UL 508; CSA-C22.2 No. 14-05; CSA-C22.2 No. 94-91; CE marking
UL File No. E29184
UL Category Control No. NKCR
CSA File No. 012528
CSA Class No. 3211-03
North America Certification UL listed, CSA certified
Degree of Protection UL/CSA Type: -
Dimensions
A = 37.2
Pushbutton with M22-(C)K…
Pushbutton with M22-(C) LED… + M22-XLED…
12/29/2020 Eaton 216376 ED2020 V75.0 EN 5 / 6
Additional product information (links)
IL04716002Z (AWA1160-1745) RMQ-Titan System
IL04716002Z (AWA1160-1745) RMQ-Titan
System
https://es-assets.eaton.com/DOCUMENTATION/AWA_INSTRUCTIONS/IL04716002Z2020_09.pdf
DGUV Test Mark Customer Information http://www.dguv.de/medien/dguv-test-medien/_pdf_zip_doc_ppt/agb-und-pzo/dguv_test_zeichen_infoblatt_kunden.pdf
Maximum equipment and position of the
internal accessories
http://ecat.moeller.net/flip-cat/?edition=HPLEN&amp;startpage=17.178
12/29/2020 Eaton Industries GmbH
http://www.eaton.eu
© 12/2020 by Eaton Industries GmbH
Eaton 216376 ED2020 V75.0 EN
6 / 6