AC axial fan
A2D170-AA04-02
Charts: Air flow 60 Hz
Druck p f s[Pa]für Rho=1,2kg/m^3
qv[m^3/h]
550500450400350300250200150100500
qv[cfm]
300250200150100500
p f s[Pa]
260
250
240
230
220
210
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
20
10
0
pfs _E[IN H2O]
1
0,95
0,9
0,85
0,8
0,75
0,7
0,65
0,6
0,55
0,5
0,45
0,4
0,35
0,3
0,25
0,2
0,15
0,1
0,05
0
p f s[Pa]
1
2
3
4
Measurement: LU-25209
Air performance measured as per ISO 5801
Installation category A. For detailed
information on the measuring set-up, please
contact ebm-papst. Suction-side noise
levels: LwA measured as per ISO 13347 /
LpA measured with 1m distance to fan axis.
The values given are valid under the
measuring conditions mentioned above and
may vary according to the actual installation
situation. With any deviation from the
standard set-up, the specific values have to
be checked and reviewed with the unit
installed.
Measured values
1
2
3
4
U
V
400
400
400
400
f
Hz
60
60
60
60
n
min-1
3100
3065
3015
3000
Pe
W
39
41
43
44
I
A
0.09
0.09
0.09
0.09
qv
m3/h
535
495
450
370
pfs
Pa
0
30
60
80
U = Supply voltage · f = Frequency · n = Speed · Pe= Power input · I = Current draw · qv = Air flow · pfs = Pressure increase
Item no. 11074-5-9980 · Revision 72138 · Release 2010-09-27 · Page 5 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com