Hall Effect Current Sensor S27S300D15Y
Tamura reserve the right to modify its products in order to improve them without prior notice
S27S300D15YrevA, November 2011
E243511
T
A
=25ºC, V
CC
=±15V
Electrical Characteristics
Specifications
Features:
• Closed Loop type
• Current or voltage output
• Conversion ratio K = 1:2000
• Panel mounting with Molex Minifit connector
• Large aperture
• Insulated plastic case according to UL94V0
Parameters
Symbol S27S300D15Y
Rated Current I
f
300AT
Maximum Current
1 I
fmax
± 500A (@ R
M
≤ 5Ω)
If = ± A
DC
Measuring resistance @ 85°C
±12V 300A : 0Ω ~ 39Ω
500A : 0Ω ~ 12Ω
±15V 300A : 0Ω ~ 58Ω
500A : 0Ω ~ 22Ω
±20V 300A : 15Ω ~ 93Ω
500A : 15Ω ~ 45Ω
Conversion Ratio K 1 : 2000
Output Current I
OUT
± 150mA
Offset Current I
OE
± 0.2mA @ I
f
= 0A
Output Current Accuracy X I
OUT
± 0.4%
Output Linearity
ε
L
± 0.1% @ I
f
Supply Voltage
2
V
CC
± 12V ~ ± 20V
Consumption Current I
CC
± 20mA (Output Current is not included)
Response Time
3
t
r
< 1.0µs @ di/dt = 100A / µs
Output Temperature Characteristic TCI
OUT
± 0.01 % / ºC @ I
f
Offset Temperature Characteristic
4
TCI
OE
< ± 0.5mA max. @ I
f
= 0A (-40ºC ~ +85ºC)
Hysteresis allowance I
OH
≤ 0.08mA (0A ⇔ 3 x I
f
)
Insulation Withstanding V
d
AC 4000V, for 1minute (sensing current 0.5mA), inside of aperture ⇔ terminals
Insulation Resistance R
IS
> 500MΩ (@ DC 500V) inside of aperture ⇔ terminals
Frequency Bandwidth f DC .. 100 kHz
Secondary Coil Resistance R
S
25Ω @ T
A
= 70ºC
28Ω @ T
A
= 85ºC
Operating Temperature T
A
– 40ºC ~ +85ºC
Storage Temperature T
S
– 40ºC ~ +90ºC
R
M
1
@ V
CC
=±15V for 10 Seconds —
2
Rated Current is restricted by V
CC
—
3
Time between 10% input current full scale and 90% of sensor output full scale
—
4
< ± 0.3mA max. @ I
f
= 0A (-10ºC ~ +70ºC)
Advantages:
• Excellent accuracy and linearity
• Low temperature drift
• Wide frequency bandwidth
• No insertion loss
• High Immunity to external interferences
• Optimised response time
• Current overload capability