ENVIRONMENTAL CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Storage Temperature Range -40 85
°C
Operating Temperature Range Refer to power derating curve vs. operating temperature -40 85
Start up -40
Operating Humidity Non-condensing 10 95 %
Operating Altitude For class I IT equipment deployment -200 5000 m
Other -200 2000
MTBF Telcordia SR-332 M1C3 50°C, 110W 1M Hours
Shock
Operating, IEC60068-2-27, half-sine 5G, 6ms, 3 times
per face, 6 faces Complies
Non-operating, IEC60068-2-27, half-sine, 30G, 18ms, 3
times per face, 6 faces Complies
Vibration
Operating, IEC60068-2-6, 1.0G, 10-150Hz, 10minutes
per axis, on all 3 axes Complies
Non-operating, IEC60068-2-6, 2.0G, 10-150Hz, 10min-
utes per axis, on all 3 axes Complies
Safety
IEC60950-1:2005 2nd Ed.; Am1:2009
EN60950-1:2006; A11:2009; A1:2010; A12:2011
UL60950-1, 2nd Ed., 2011-12-19 & CSA C22.2 No. 60950-1-07, 2nd Ed., 2011-12
IEC60601-1:2005 3rd Ed. + CORR.1(2006) + CORR.2(2007)
ANSI/AAMI ES60601-1 (2005+C1:09 + A2:10), CSA-C22.2 No. 60601-1(2008), MOPP
CE Marking per LVD
Warranty 2 years6
Outside Dimensions 2.0" x 4.0" x 1.5" (50.8mm x 101.6mm x 38.1mm)
Weight 0.42lbs (190g) typical
PROTECTION CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Overvoltage Protection V1; Latching (50% load) 110 140
%
V2; Latching (50% load) 110 170
Overcurrent Protection V1; Hiccup mode; Auto Recovery 110 170
V2; Hiccup mode; Auto Recovery 0.11 0.4 A
Overtemperature Protection Auto recovery Complies
ISOLATION CHARACTERISTICS
Parameter Conditions Min. Typ. Max. Units
Isolation
Primary to Earth Ground (1x MOPP) 1500 Vac
Primary to Secondary (2x MOPP)74000
Secondary to Earth Ground 500 Vdc
Leakage Current (under normal conditions) 264Vac, 60Hz, 25°C 350 A
240Vac, 60Hz, 25°C 300 A
Touch Current 264Vac, 60Hz, 25°C 100 A
EMISSIONS AND IMMUNITY
Characteristic Standard Compliance
Input Current Harmonics IEC/EN 61000-3-2 Class D, Class C
Voltage Fluctuation and Flicker IEC/EN 61000-3-3 Complies
Conducted Emissions EN 55022 Class B, (Class A as Class II equipment deployment)
FCC Part 15 Class B, (Class A as Class II equipment deployment)
ESD Immunity IEC/EN 61000-4-2 Level 4, Criterion A
Radiated Field Immunity IEC/EN 61000-4-3 Level 2, Criterion A
Electrical Fast Transient Immunity IEC/EN 61000-4-4 Level 3, Criterion A
Surge Immunity IEC/EN 61000-4-5 Level 4, Criterion A
RF Conducted Immunity IEC/EN 61000-4-6 Level 2, Criterion A
Magnetic Field Immunity IEC/EN 61000-4-8 Level 2, Criterion A
Voltage dips, interruptions IEC/EN 61000-4-11 Level 3, Criterion B
6 At Ta<50°C.
7 Class I equipment deployment.