Thermal Overcurrent Circuit Breaker 3130
www.e-t-a.com05/06(290405)
87
1
Description
Typical applications
Technical data
Single, two and three pole rocker switch/thermal trip free circuit
breakers (S-type TO CBE to EN 60934) of compact design for snap-in
panel mounting. Available either with protection on one/both/all poles
or, in the case of the double pole version, protection on one pole only.
Illumination is optional and there is a choice of rocker colours.
Approved to CBE standard EN 60934 (IEC 60934).
Motors, transformers, solenoids, household and office machines,
electrical tools, mobile homes, boating, construction vehicles, medical
equipment to EN 60601.
3130
1 pole 3 pole
For further details please see chapter: Technical Information
Voltage rating AC 240 V; 3 AC 415 V; DC 50 V
(UL: AC 250 V; 3 AC 250 V; DC 50 V)
Current ratings 0.1...20 A 1 pole
0.1...16 A 2 and 3 pole
Typical life 1 pole
AC 240 V: 0.1...20 A 30,000 operations at 1 x IN, inductive
DC 50 V: 0.1...4 A 30,000 operations at 1 x IN, inductive
4.5...16 A 30,000 operations at 1 x IN, resistive
DC 28 V: 4.5...20 A 30,000 operations at 1 x IN, inductive
2 pole
AC 240 V: 0.1...16 A 50,000 operations at 1 x IN, inductive
DC 50 V: 0.1...16 A 50,000 operations at 1 x IN, inductive
3 pole
3 AC 415 V: 0.1...16 A 30,000 operations at 1 x IN, inductive
Ambient temperature -30...+60 °C (-22...+140 °F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664 A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 3,000 V
current path/current path AC 1,500 V
Insulation resistance >100 M(DC 500 V)
Interrupting capacity Icn 0.1...2 A 10 x IN
2.5...20 A 150 A 1 pole
2.5...16 A 250 A 2 pole
2.5...12 A 150 A 3 pole
14 + 16 A 130 A 3 pole
Interrupting capacity IN0.1...12 A 14...16 A
(UL 1077) 1 + 2 pole AC 250V/3500A AC 250V/3500A
3 pole 3AC 250V/5000A
1 + 2 pole DC 50V/2000A DC 50V/2000A
Degree of protection operating area IP40
(IEC 60529/DIN 40050) terminal area IP00
Vibration 5 g (57-500 Hz), ±0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock 1 pole: 25 g (11 ms) 2 + 3 pole: 20 g (11 ms)
to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH,
to IEC 60068-2-3, test Ca
Mass approx. 45 g (three pole)
approx. 31 g (double pole)
approx. 17 g (single pole)
Approvals
Standard current ratings and typical internal resistance values
Current Internal resistance Current Internal resistance
rating (A) per pole () rating (A) per pole ()
0.1 94 4 0.0435
0.2 24 5 0.0325
0.3 12 6 0.0215
0.4 5.30 7 0.0165
0.5 4.20 8 0.0165
0.8 1.50 10 < 0.02
1 0.9 12 < 0.02
1.2 0.80 14 < 0.02
1.5 0.45 15 < 0.02
2 0.27 16 < 0.02
2.5 0.0785 18 < 0.02
3 0.0595 20 < 0.02
3.5 0.0565
Authority Voltage rating Current rating
VDE (EN 60934) AC 240/415 V 0.1...20 A single pole
0.1...16 A multi pole
DC 50 V 0.1...8 A single pole
0.1...16 A multi pole
DC 28 V 0.1...20 A single pole
UL, CSA AC 250 V, DC 50 V 0.1...16 A 1 and 2 pole
3 AC 250 V 0.1...12 A 3 pole
Illumination voltage/power consumption
operating voltage power consumption
filament/neon (B) LED (G, R, Y)
6 V 60 mA 9 mA
12 V 20 mA 9 mA
24 V 20 mA 9 mA
48 V 20 mA 1.5 mA
115 V < 1.5 mA < 1 mA*
230 V < 1.5 mA < 1 mA*
415 V < 1 mA not available
* single pole version only
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications
without notice is reserved.Product markings may not be exactly as the ordering codes.
Errors and omissions excepted.
www.e-t-a.com 05/06(290405)
88
Thermal Overcurrent Circuit Breaker 3130
1
Ordering information - multipole
Type No.
3130 rocker switch/circuit breaker multipole
Mounting
Fsnap in frame
Frame
1standard
Number of poles
22 pole, thermally protected
33 pole, thermally protected
52 pole, thermally protected on one pole only
63 pole, thermally protected on two poles only
B2 pole, unprotected**
C3 pole, unprotected**
Frame mounting
0panel thickness 1-2.5 mm (.039-.099 in) (only 3130-F1..-...)
Terminal design
P7 blade terminals DIN 46244-C-Ms-S (QC 2x.110)
H7 for terminals 1.1, 2.1 3.1 terminal screws M 3.5;
for terminals 1.2, 2.2, 3.1 blade terminals
(QC 2x.110)
N7 blade terminals DIN 46244-C-Ms-S (QC 2x.110),
with shunt terminal
Characteristic curve
T1 thermal, 1.05-1.4 IN
Q1 switch, only with terminal design -N7
Switch style
Wrocker
Umomentary switch function
Switch colour designation
opaque translucent
01 black 12 white
02 white 14 red
04 red 19 green
09 green
Rocker markings
Q"I" and "O" moulded in
Rocker illumination (optional)
Bfilament (≤ AC/DC 48 V),
neon (≥ AC 115 V)
Ggreen LED, DC
Rred LED, DC
Yyellow LED, DC
Illumination voltage range*
(optional)
14 - 7 V (B,G,R,Y)
210 - 14 V (B,G,R,Y)
320 - 28 V (B,G,R,Y
442 - 54 V (B,R,Y
690 - 140 V (B)
7185 - 275 V (B)
8320 - 450 V (B)
Current ratings
0.1...16 A
3130 - F 1 3 0 - P7 T1 - W 12 Q B 7 - 5 A ordering example
* N/A for non-illuminated version
** unprotected poles have to ordered with terminal design N7
Ordering information - 1 pole
Type No.
3130 rocker switch/circuit breaker
Mounting
Fsnap in frame
Frame
1standard
3special single pole version
Number of poles
1single pole, thermally protected
A1 pole, unprotected**
Frame mounting
0panel thickness 1-2.5 mm (.039-.099 in) (only 3130-F1..-...)
1panel thickness 1.5-3.2 mm (.059-.126 in)(only 3130-F3.1-...)
Terminal design
P7 blade terminals DIN 46244-C-Ms-S (QC 2x.110)
H7 for terminals 1.1, 2.1 3.1 terminal screws M 3.5
for terminals 1.2, 2.2, 3.1 blade terminals (QC 2x.110)
N7 blade terminals (QC 2x.110), with shunt terminal
Characteristic curve
T1 thermal, 1.05-1.4 IN
Q1 switch, only with terminal design -N7
Switch style
Wrocker
Umomentary switch function
Switch colour designation
opaque translucent
01 black 12 white
02 white 14 red
04 red 19 green
09 green 29 black, rocker with green dot
Rocker markings
Adot (ON position)
Q"I" and "O" moulded in
Rocker illumination (optional)
.12QYwhite rocker, yellow LED, AC/DC
. 14 Q R red rocker, red LED, AC/DC
. 19 Q Y green rocker, yellow LED, AC/DC
. 29 A G black rocker with dot, green LED
Illumination voltage range*
(optional)
14 - 7 V (G,R,Y)
210 - 14 V (G,R,Y)
320 - 28 V (G,R,Y)
442 - 54 V (R,Y)
690 - 140 V (R,Y)
7185 - 275 V (R,Y)
XLED, DC 8 - 10 mA ***
Current ratings
0.1...20 A
3130 - F 1 1 0 - P7 T1 - W 12 Q Y 7 - 5 A ordering example
* N/A for non-illuminated version
** unprotected poles have to ordered with terminal design N7
*** without series resistor and diode, to be selected by customer.
Recommendation:
4-7 V Rv 0.43 kΩ
10-14 V Rv 1.1 kΩ
20-28 V RV 2.7 kΩ
diode 1N4007
Thermal Overcurrent Circuit Breaker 3130
www.e-t-a.com05/06(290405)
89
1
Dimensions
18
36
R3
terminal for
illumination
conductor size
0.14 mm2 (AWG26),
length 180 mm
(7.09 in.)
+0.3
+.012
26.1 +0.2
29.5
36
R3
optional illumination
26
21
2I
+0.3
+.012
blade terminals DIN 46244-C-Ms-S
(QC 2x.110 P7 or N7)
9.5
OFF ON
5.85
2
33
34
10
20
2
14.5
34+0.2
14.6 +0.2
min. 1.5
< R0.5
±0.1
panel thickness
1-2.5 mm
(.039-.098 in.)
Panel cut-out
I.2
LINE
I.I
Side view
LINE
I.I
flat head screw M3.5x5 -MS ISO 1580 (H7)
tightening torque max. 0.8 Nm
I.3
-0.4
-0.2
switch only
illuminated dot (-.29AG.-)
.230
.079
.374
.571
±.004
< .020
-.016
-.008
min .059
.709
1.42 1.34+.008
.575 +.008
.394 1.30
.079
.787
1.34
3130-F110-…
blade terminals DIN 46244-C-Ms-S
(QC 2x.110 P7 or N7)
OFF ON
5.85
2
33
34
10
20
2
34+0.2
min. 1.5
< R0.5
±0.1
panel thickness
1-2.5 mm
(.039-.098 in.)
Panel cut-out
I.2
LINE
I.I
Side view
LINE
I.I
flat head screw M3.5x5 -MS ISO 1580 (H7)
tightening torque max. 0.8 Nm
I.3
Edges of working parts: DIN 6784
.230
.079
.827
1.02
±.004
< .020
min .059
1.16
1.42
1.34+.008
1.03 +.008
.394 1.30
.079
.787
1.34
3130-F120-…
unit
.118
.118
-0.4
-0.2
19.5
39.5
R1.5
17.8
+0.3
+.012
41
2unit
I
3
+0.3
+.012
blade terminals DIN 46244-C-Ms-S
(QC 2x.110 P7 or N7)
terminal for
illumination
conductor size
0.14 mm2 (AWG26),
length 180 mm
(7.09 in.)
9.5
OFF ON
5.85
2
33
34
10
20
2
B
18+0.2
min. 1.5
< R0.5
±0.1
A
Panel cut-out
I.2
LINE
I.I
Side view
LINE
I.I
flat head screw M3.5x5 -MS ISO 1580 (H7)
tightening torque max. 0.8 Nm
I.3
Edges of working parts: DIN 6784
optional illumination
.230
.079
.374
.701
±.004
< .020
-.016
-.008
min .059
.768
1.56
.709 +.008
.394 1.30
.079
.787
1.34
.059
37.6 +0.2
36
R3
optional illumination
37.5
32.5
blade terminals DIN 46244-C-Ms-S
(QC 2x.110 P7 or N7)
OFF ON
5.85
2
33
34
10
20
2
34+0.2
min. 1.5
< R0.5
±0.1
panel thickness
1-2.5 mm
(.039-.098 in.)
Panel cut-out
I.2
LINE
I.I
Side view
LINE
I.I
flat head screw M3.5x5 -MS ISO 1580 (H7)
tightening torque max. 0.8 Nm
I.3
Edges of working parts: DIN 6784
.230
.079
1.28
1.48
±.004
< .020
min .059
1.61
1.42
1.34+.008
1.48 +.008
.394 1.30
.079
.787
1.34
.118
3130-F130-…
3130-F311-…
-0.4
-0.2
mm
1.50
2.35
3.20
mm
35
36
37
+0.15
+0.15
+0.15
AB
inch
.059
.093
.126
inch
1.38
1.42
1.46
+.006
+.006
+.006
-.016
-.008
This is a metric design and millimeter dimensions take precedence ( mm )
inch
Trip time in seconds
+23 °C
+73.4 °F
+60 °C
+140 °F
-30 °C
-22 °F
… times rated current
Trip time in seconds
+23 °C
+73.4 °F
+60 °C
+140 °F
-30 °C
-22 °F
12468102040
10000
1000
100
10
1
0.1
0.1 … 2 A
2.5 … 20 A 1 pole
2.5 … 16 A 2 and 3 pole
Multipole types: all poles symmetrically loaded.
With single pole overload, thermal tripping will be at approx. 1.54 x IN
with 2 pole devices and at approx. 1.68 x IN with 3 pole devices.
12468102040
10000
1000
100
10
1
0.1
… times rated current
www.e-t-a.com 05/06(290405)
90
Thermal Overcurrent Circuit Breaker 3130
1
This is a metric design and millimeter dimensions take precedence ( mm )
inch
Installation drawing 3130-F1...
mounting area
When installing the circuit breaker apply pressure on bezel only.
I.2
LINE
I.II.3
10
32
7
25
20
5
87
operating area
.984
1.26
.276.276.315
.787
.197
.394
Accessories 3130-F130-...
Internal connection diagrams
Typical time/current characteristics
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the circuit
breaker current ratings by the derating factor shown below. See also section 9
– Technical information.
Ambient temperature °F -22 -4 +14 +32 +73.4 +104 +122 +140
°C -30 -20 -10 0 +23 +40 +50 +60
Derating factor 0.8 0.76 0.84 0.92 1 1.08 1.16 1.24
line I.I
I.3 lamp
1 pole momentary switch
load
I.2
line I.I
1 pole
lamp
3.I
3.2
2.I
2.2
I.2
line I.I
3 pole
line I.I
I.3
1 pole switch
lamp
2.I
2.3
I.3
line I.I
2 pole momentary switch
load load
load
load
load
load load
2 pole
2.I
2.2
I.2
line I.I
load load
ø4.4
.173
36.5
1.44
41.5
1.63
1.97
.197
.472
.315
1.97
.433
2.17
12
5
50
55
50
ø11
ø8
Splash cover, transparent, for 3 pole version
X 221 258 01 (IP54), comprising bezel Y 306 109 01
and transparent cover Y 306 108 01
Thermal Overcurrent Circuit Breaker 3130
www.e-t-a.com05/06(290405)
91
1
Description
Typical applications
Technical data
Single pole rocker switch/thermal trip free circuit breakers (S-type TO
CBE to EN 60934) of compact design for snap-in panel mounting.
Available either with protection on one/both/all poles or, in the case of
the double pole version, protection on one pole only. Illumination is
optional and there is a choice of rocker colours.
Approved to CBE standard EN 60934 (IEC 60934).
Motors, transformers, solenoids, household and office machines,
electrical tools, mobile homes, boating, construction vehicles, medical
equipment to EN 60601.
3130
water splash protected (IP 66)
For further details please see chapter: Technical Information
Voltage rating AC 240 V; DC 50 V
(UL: AC 250 V; DC 50 V)
Current ratings 0.1...20 A
Typical life
AC 240 V: 0.1...20 A 30,000 operations at 1 x IN, inductive
DC 50 V: 0.1...4 A 30,000 operations at 1 x IN, inductive
4.5...16 A 30,000 operations at 1 x IN, resistive
DC 28 V: 4.5...20 A 30,000 operations at 1 x IN, inductive
Ambient temperature -30...+60 °C (-22...+140 °F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664 A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 3,000 V
current path/current path AC 1,500 V
Insulation resistance >100 M(DC 500 V)
Interrupting capacity Icn 0.1...2 A 10 x IN
2.5...20 A 150 A
Interrupting capacity 0.1...12 A 14...16 A
(UL 1077) AC 250V/3500A AC 250V/3500A
DC 50V/2000A DC 50V/2000A
Degree of protection operating area IP66
(IEC 60529/DIN 40050) terminal area IP00
Vibration 5 g (57-500 Hz), ±0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock 25 g (11 ms)
to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH,
to IEC 60068-2-3, test Ca
Mass approx. 17 g
Approvals
Standard current ratings and typical internal resistance values
Current Internal resistance Current Internal resistance
rating (A) per pole () rating (A) per pole ()
0.1 94 4 0.0435
0.2 24 5 0.0325
0.3 12 6 0.0215
0.4 5.30 7 0.0165
0.5 4.20 8 0.0165
0.8 1.50 10 < 0.02
1 0.9 12 < 0.02
1.2 0.80 14 < 0.02
1.5 0.45 15 < 0.02
2 0.27 16 < 0.02
2.5 0.0785 18 < 0.02
3 0.0595 20 < 0.02
3.5 0.0565
Authority Voltage rating Current rating
VDE (EN 60934) AC 240/415 V 0.1...20 A
DC 50 V 0.1...8 A
DC 28 V 0.1...20 A
UL, CSA AC 250 V, DC 50 V 0.1...16 A
Illumination voltage/power consumption
operating voltage power consumption
filament/neon (B) LED (G, R, Y)
6 V 60 mA 9 mA
12 V 20 mA 9 mA
24 V 20 mA 9 mA
48 V 20 mA 1.5 mA
115 V < 1.5 mA < 1 mA
230 V < 1.5 mA < 1 mA
415 V < 1 mA not available
www.e-t-a.com 05/06(290405)
92
Thermal Overcurrent Circuit Breaker 3130
1
Installation drawing 3130-F212-...
I.3 I.2
LINE
I.I
mounting area
operating area
10
32
7
25
20
5
87
.984
.315 .197
.787
.276 .276
.394
1.26
Dimensions 3130-F212-...
.079
R1
illuminated trip indication (optional)
panel thickness
2 - 3.5 mm
(.079-.138 in.)
16.6
+0.2
38
terminal for
illumination
flying lead
conductor size
0.14 mm2,
length 180 mm
(7.09 in.)
blade terminals DIN 46244-C-Ms-S
(QC 2x.110 P7 or N7)
min. 1.5
< R0.5
±0.1
Panel cut-out
Side view
flat head screw M3.5x5 -MS ISO 1580 (H7)
tightening torque max. 0.8 Nm
Edges of working parts: DIN 6784
-0.4
-0.2 sharp edged
14.3
1.7
28
2
LINE
I.I
OFF ON
10
44
I.3 I.2
LINE
I.I
GERMANY
+0.2
22.5
.563
.067
1.10
1.73
.886
-.016
-.008
±.004
< .020
min .059
+.008
1.50
.039
.654+.008
34
20
.787
.394
1.34
This is a metric design and millimeter dimensions take precedence ( mm )
inch
Ordering information - IP 66
Type No.
3130 rocker switch/circuit breaker
Mounting
Fsnap in frame
Frame
2splash water protected
Number of poles
1single pole, thermally protected
A1 pole, unprotected **
Frame mounting
2panel thickness 2-3.5 mm
Terminal design
P7 blade terminals DIN 46244-C-Ms-S (QC 2x.110)
H7 for terminals 1.1 terminal screws M 3.5
for terminals 1.2 2 x .110 blade terminals
N7 blade terminals DIN 46244-C-Ms-S (QC 2x.110),
with shunt terminal or for switch only
Characteristic curve
T1 thermal, 1.05-1.4 IN
Q1 switch, only with terminal design -N7
Switch style
S 00 without actuator rocker X 222 420 ..
must be ordered separately.
Available symbols see following pages.
Srocker
Pmomentary switch
Switch colour designation (not S00)
opaque translucent
01 black 12 white
02 white 14 red
04 red 19 green
09 green
Switch markings
0without actuator
Q"I" and "O" moulded in
Switch illumination
.12QYwhite rocker, yellow LED, AC/DC
. 14 Q R red rocker, red LED, AC/DC
. 19 Q Y green rocker, yellow LED, AC/DC
S000 Ywithout rocker, LED yellow, AC/DC
Illumination voltage range*
14 - 7 V (R,Y)
210 - 14 V (R,Y)
320 - 28 V (R,Y)
442 - 54 V (R,Y)
690 - 140 V (R,Y)
7185 - 275 V (R,Y)
XLED, DC 8-10 mA ***
Current ratings
0.1...20 A
3130 F 2 1 2 - P7 T1 - S 12 Q Y 7 - 5 A ordering example
* N/A for non-illuminated version
** unprotected poles have to ordered with terminal design N7
*** without series resistor and diode, to be selected by customer.
Recommendation:
4-7 V Rv 0,43 kΩ
10-14 V Rv 1,1 kΩ
20-28 V RV 2,7 kΩ
diode 1N4007
Thermal Overcurrent Circuit Breaker 3130
www.e-t-a.com05/06(290405)
93
1
Internal connection diagrams
line I.I
I.3 lamp
1 pole momentary switch
load
I.2
line I.I
1 pole
lamp
load
line I.I
I.3
1 pole switch
lamp
load
Typical time/current characteristics
+60 °C
+140 °F
+60 °C
+140 °F
+23 °C
+73.4 °F
-30 °C
-22 °F
+23 °C
+73.4 °F
-30 °C
-22 °F
12468102040
… times rated current
Trip time in seconds
10000
1000
100
10
1
0.1
12468102040
… times rated current
Trip time in seconds
10000
1000
100
10
1
0.1
0.1 … 2 A
2.5 … 20 A
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, please multiply the circuit
breaker current ratings by the derating factor shown below. See also
section 9 – Technical information.
Ambient temperature °F -22 -4 +14 +32 +73.4 +104 +122 +140
°C -30 -20 -10 0 +23 +40 +50 +60
Derating factor 0.8 0.76 0.84 0.92 1 1.08 1.16 1.24
This is a metric design and millimeter dimensions take precedence ( mm )
inch
www.e-t-a.com 05/06(290405)
94
Thermal Overcurrent Circuit Breaker 3130
1
Accessories
Symbols/legends available
Interior light
Anchor light
Cockpit light
Navigation light
VHF radio
Refrigerator
Anchor
Windshield wiper
Bilge pump
Potable water
Horn
Ventilation fan
Panel light
Navigation instruments
Music
Heating
Shower pump
Icebox
Water for windshield wiper
Weigh anchor
Drop anchor
Rocker
X 222 420 ..
Caution!
Use care not to
damage the seal.
I.3 I.2
LINE
I.I
GERMANY
How to exchange rockers
symbol
X 222 420 12
Further symbols upon request.
S00 switch style:
white translucent rocker coated with black lacquer
with laser marked symbols that appear in white translucent.
Ice
NAV
UP
DOWN
X 222 420 01
X 222 420 02
X 222 420 03
X 222 420 04
X 222 420 05
X 222 420 06
X 222 420 07
X 222 420 08
X 222 420 09
X 222 420 10
X 222 420 11
X 222 420 12
X 222 420 13
X 222 420 14
X 222 420 15
X 222 420 16
X 222 420 17
X 222 420 18
X 222 420 19
X 222 420 20
X 222 420 21
X 222 420 22
22.5
ON
14.3
panel thickness
2 - 3.5 mm
(.079-.138 in.)
16.6
+0.2
38
min. 1.5
< R0.5
±0.1
Edges of working parts: DIN 6784
-0.4
-0.2 sharp edged
+0.2
-.016
-.008
±.004
< .020
min .059
+.008
1.50
.654+.008
28
I.3 I.2
LINE
I.I
GERMANY
34 Panel cut-out
1.7
OFF
44
.563
.067
1.10
1.73
.886
1.34
Blanking piece (black)
3130-387012
This is a metric design and millimeter dimensions take precedence ( mm )
inch
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications
without notice is reserved.Product markings may not be exactly as the ordering codes.
Errors and omissions excepted.