Thermal Overcurrent Circuit Breaker 3130
www.e-t-a.com05/06(290405)
87
1
Description
Typical applications
Technical data
Single, two and three pole rocker switch/thermal trip free circuit
breakers (S-type TO CBE to EN 60934) of compact design for snap-in
panel mounting. Available either with protection on one/both/all poles
or, in the case of the double pole version, protection on one pole only.
Illumination is optional and there is a choice of rocker colours.
Approved to CBE standard EN 60934 (IEC 60934).
Motors, transformers, solenoids, household and office machines,
electrical tools, mobile homes, boating, construction vehicles, medical
equipment to EN 60601.
3130
1 pole 3 pole
For further details please see chapter: Technical Information
Voltage rating AC 240 V; 3 AC 415 V; DC 50 V
(UL: AC 250 V; 3 AC 250 V; DC 50 V)
Current ratings 0.1...20 A 1 pole
0.1...16 A 2 and 3 pole
Typical life 1 pole
AC 240 V: 0.1...20 A 30,000 operations at 1 x IN, inductive
DC 50 V: 0.1...4 A 30,000 operations at 1 x IN, inductive
4.5...16 A 30,000 operations at 1 x IN, resistive
DC 28 V: 4.5...20 A 30,000 operations at 1 x IN, inductive
2 pole
AC 240 V: 0.1...16 A 50,000 operations at 1 x IN, inductive
DC 50 V: 0.1...16 A 50,000 operations at 1 x IN, inductive
3 pole
3 AC 415 V: 0.1...16 A 30,000 operations at 1 x IN, inductive
Ambient temperature -30...+60 °C (-22...+140 °F)
Insulation co-ordination rated impulse pollution
(IEC 60664 and 60664 A) withstand voltage degree
2.5 kV 2
reinforced insulation in operating area
Dielectric strength
(IEC 60664 and 60664A) test voltage
operating area AC 3,000 V
current path/current path AC 1,500 V
Insulation resistance >100 MΩ(DC 500 V)
Interrupting capacity Icn 0.1...2 A 10 x IN
2.5...20 A 150 A 1 pole
2.5...16 A 250 A 2 pole
2.5...12 A 150 A 3 pole
14 + 16 A 130 A 3 pole
Interrupting capacity IN0.1...12 A 14...16 A
(UL 1077) 1 + 2 pole AC 250V/3500A AC 250V/3500A
3 pole 3AC 250V/5000A
1 + 2 pole DC 50V/2000A DC 50V/2000A
Degree of protection operating area IP40
(IEC 60529/DIN 40050) terminal area IP00
Vibration 5 g (57-500 Hz), ±0.38 mm (10-57 Hz)
to IEC 60068-2-6, test Fc
10 frequency cycles/axis
Shock 1 pole: 25 g (11 ms) 2 + 3 pole: 20 g (11 ms)
to IEC 60068-2-27, test Ea
Corrosion 96 hours at 5 % salt mist,
to IEC 60068-2-11, test Ka
Humidity 240 hours at 95 % RH,
to IEC 60068-2-3, test Ca
Mass approx. 45 g (three pole)
approx. 31 g (double pole)
approx. 17 g (single pole)
Approvals
Standard current ratings and typical internal resistance values
Current Internal resistance Current Internal resistance
rating (A) per pole (Ω) rating (A) per pole (Ω)
0.1 94 4 0.0435
0.2 24 5 0.0325
0.3 12 6 0.0215
0.4 5.30 7 0.0165
0.5 4.20 8 0.0165
0.8 1.50 10 < 0.02
1 0.9 12 < 0.02
1.2 0.80 14 < 0.02
1.5 0.45 15 < 0.02
2 0.27 16 < 0.02
2.5 0.0785 18 < 0.02
3 0.0595 20 < 0.02
3.5 0.0565
Authority Voltage rating Current rating
VDE (EN 60934) AC 240/415 V 0.1...20 A single pole
0.1...16 A multi pole
DC 50 V 0.1...8 A single pole
0.1...16 A multi pole
DC 28 V 0.1...20 A single pole
UL, CSA AC 250 V, DC 50 V 0.1...16 A 1 and 2 pole
3 AC 250 V 0.1...12 A 3 pole
Illumination voltage/power consumption
operating voltage power consumption
filament/neon (B) LED (G, R, Y)
6 V 60 mA 9 mA
12 V 20 mA 9 mA
24 V 20 mA 9 mA
48 V 20 mA 1.5 mA
115 V < 1.5 mA < 1 mA*
230 V < 1.5 mA < 1 mA*
415 V < 1 mA not available
* single pole version only
All dimensions without tolerances are for reference only. In the interest of improved design,
performance and cost effectiveness the right to make changes in these specifications
without notice is reserved.Product markings may not be exactly as the ordering codes.