DUB71
Mode of Operation
DUB71 monitor both AC and
DC over or under voltage.
Example 1
(no connection between ter-
minals Z1, Y1 - latch func-
tion disabled)
The relay operates when the
measured value exceeds (or
drops below) the set level for
more than the set delay
time.
It releases when the voltage
drops below (or exceeds)
the set level (see hysteresis
setting), or when power sup-
ply is interrupted.
Example 2
(connection between termi-
nals Z1, Y1 - latch function
enabled)
The relay operates and
latches in operating position
when the measured value
exceeds (or drops below)
the set level for more than
the set delay time.
Provided that the voltage
has dropped below (or has
exceeded) the set point (see
hysteresis setting) the relay
releases when the intercon-
nection between terminals
Z1, Y1 is interrupted, or
power supply is interrupted
as well.
The yellow LED flashes until
the delay time has expired
or the measured value has
dropped below the set point
(see hysteresis setting).
Note
When the inhibit contact is
opened, if the input signal is
already in alarm position, the
delay time needs to elapse
before relay activation.
Power ON delay 1s± 0.5 s or 6 s ± 0.5 s
Reaction time (input signal variation from
-20% to +20% or from
+20% to -20% of set value)
Alarm ON delay < 100 ms
Alarm OFF delay < 100 ms
Accuracy (15 min warm-up time)
Temperature drift ± 1000 ppm/°C
Delay ON alarm ± 10% on set value ± 50 ms
Repeatability ± 0.5% on full-scale
Indication for
Power supply ON LED, green
Alarm ON LED, red (flashing 2 Hz
during delay time)
Output relay ON LED, yellow
General Specifications
Adjust the input range set-
ting the DIP switches 1 and
2 as shown below.
Select the desired function
setting the DIP switches 3 to
6 as shown below.
To access the DIP switches
open the grey plastic cover
as shown below.
Selection of level and time
delay:
Upper knob:
Setting of hysteresis on rela-
tive scale: 0 to 30% on set
value.
Centre knob:
Voltage level setting on rela-
tive scale: 10 to 110% on
full scale.
Lower knob:
Setting of delay on alarm
time on absolute scale (0.1
to 30 s).
Function/Range/Level and Time Delay Setting
Relay working mode
ON: Normally De-Energized
OFF: Normally Energized
Measuring range
Model 500 V 10 V
ON OFF 20 V 1 V
OFF OFF 50 V 2 V
ON ON 200 V 5 V
OFF ON 500 V 10 V
Power ON delay
ON: 6 s ± 0.5 s
OFF: 1 s ± 0.5 s
Contact input
ON: Latch function enable
OFF: Inhibit function enable
Monitoring function
ON: Over voltage
OFF: Under voltage
Environment
Degree of protection IP 20
Pollution degree 3
Operating temperature -20 to 60°C, R.H. < 95%
Storage temperature -30 to 80°C, R.H. < 95%
Housing
Dimensions 35.5 x 81 x 67.2 mm
Material PA 66
Weight Approx. 150 g
Screw terminals
Tightening torque Max. 0.5 Nm
acc. to IEC 60947
Approvals UL, CSA
CE Marking Yes
EMC
Electromagnetic Compatibillity
Immunity According to EN 61000-6-2
Emission According to EN 61000-6-3