1
New Product
Digital Timer
H5CX-@-N
Ultra-compact Timer Provides Advanced
Functions and Security Settings.
Basic Features
Short body with depth of only 59 mm (for 24-VAC / 12 to 24-VDC Models with
Screw Terminals). *1
Character height of 12 mm for better readability (on models with 4 digits).
The present value display characters can be switched between red, green,
and orange. *2
Safety and Reliability
Power supply circuit and input circuits are isolated for safety and reliability. *3
New set value limit and output counter functions have been added.
Other Features
Front Panel can be changed to white or light gray. *4
Models with instantaneous contact output added to the series.
*1. For 100 to 240 VAC Models with Screw Terminals 78 mm, Models with Sockets: 63.7 mm
(case dimension).
*2. The H5CX-A11, H5CX-L8 and H5CX-B Timers have only red characters.
*3. Specifications: 100 to 240 VAC
*4. Replacement Front Panels sold separately.
Features
Basic Features
Ultra Short Body
The body depth has been greatly reduced. Helps in making thinner
control panels. (Models with Screw Terminals)
Easier to Read
For better readability, the character height for the present value display
is 12 mm (on models with 4 digits), the largest class in the industry. The
wide viewing angle and brightness provide excellent visibility.
The number of display segments has also been increased to make
settings easier to understand, and the present value display can be
switched between red, green and orange so that output status can be
seen from a distance.
Note: The H5CX-A11 and H5CX-L8 Timers have only red characters.
The Easiest Operation
Operation is simplified by the
Up/Down Keys for each digit
on 4-digit models and Up Keys
for each digit on 6-digit
models.
Safety and Reliability
Isolated Power Supply and Input Circuits *1
Power supply circuit and input circuits are isolated for safety and
reliability.
Previous non-isolated timers had wiring restrictions and could be damaged if
wired incorrectly. The New H5CX removes these worries.
*1. New Models (H5CX-@-N) with 100 to 240-VAC specifications.
Set Value Limit
You can set an upper limit for the set value to prevent unexpected
operation of output devices caused by setting mistakes.
Output Counter
The output counter counts the number of times the output turns ON
(alarm display, count monitoring, count in increments of 1,000). This
counter is useful in managing the service life of the Timer or the load.
Refer to “Safety Precautions” on page 41.
New models Previous
models
24-VAC / 12 to 24-VDC Models with Screw Terminals: 59 mm
100 to 240-VAC / VDC Models with Screw Terminals: 78 mm *
Models with Sockets: 63.7 mm (case dimension)
*The shortest body for a timer with isolated power supply and input circuits and a maximum
ambient temperature of 55°C (according to OMRON investigation in June 2009).
Model with 4 Digits Model with 6 Digits
(Display example)
12 mm
(actual size)
10 mm
(actual size)
Previous
models
New
models
Easy to read from the top, bottom, and sides!
Model with 4 Digits Model with 6 Digits
V+V
Output terminal on PLC
or other device
AC power
supply *2
H5CX
Previous
Input terminal
0-V terminal
COM terminal
Forget These
Worries with the
New H5CX
Stabilized DC
power supply
*2. The AC power supply ground is on the commercial power supply side.
Worry-free operation
is achieved with the
New H5CX by
restricting the time
that can be set.
H5CX-@-N
2
Other Features
Change the Front Panel Color
The Front Panel can be replaced with an optional Front Panel (order
separately) with a different color to match the installation site. Select
from black, white, and light gray.
Models with Instantaneous Contact Output
Models with instantaneous contact outputs have been added to the
lineup for use with self-holding circuits and as auxiliary relays. These
models are also convenient when replacing analog timers.
Universal NPN/PNP Input
DC 2-wire sensors can be connected for a wide range of input
devices.
Waterproof, Dust-proof Structure (UL508 Type
4X and IP66)
Worry-free application is possible in locations subject to water.
Note: When the Y92S-29 Waterproof Packing is used.
Key Protection
Select from any of seven protection patterns. Use the best one for the
application.
New Modes
Modes, such as a stopwatch mode (Mode S), have been added.
Select any of 15 modes.
Model Number Structure
Model Configuration
Black
(standard)
White Light gray
You can replace
the Front Panel.
H5CX Series
Type
Standard Type
H5CX-A Series
Economy Type
H5CX-L Series
Six-digit Type
H5CX-B Series
Model H5CX-A@-N H5CX-A11@-N H5CX-L8@-N H5CX-L8E@-N H5CX-B@-N
Function
Timer Yes Yes No
Twin timer Yes Yes No
Two-stage settings/
forecast output
No No Yes
Operating modes Timer Mode: 11 modes
Twin Timer Mode: 4 modes
Timer Mode
: 4 modes
Twin Timer Mode
: 2 modes
Timer Mode: 2 modes
Input NPN/PNP input NPN input None NPN/PNP input
External connections Screw terminal
block 11-pin socket 8-pin socket Screw terminal block
Present value display
character color
Red, green, or
orange Red
Number of display digits 46
Instantaneous contacts None Provided None
Gate input Supported Not supported Supported
DIP switch settings Provided None Provided
Power supply voltage 100 to 240 VAC or 24 VAC/12 to 24 VDC 12 to 24 VDC
H5CX-@-N
3
Model Number Legend (Not all possible combinations of functions are available.)
H5CX- @@@@@-N
–––––
12345
Ordering Information
List of Models
Note: 1. The functions that are provided depend on the model. Check detailed specifications before ordering.
2. Refer to page 33 and later for information on H5CX-B Timers (6-digit display).
Type Time specifications Operating modes External
connections Inputs Outputs Supply voltage Models
H5CX-A
0.001 to 9.999 s
0.01 to 99.99 s
0.1 to 999.9 s
1 to 9999 s
1 s to 99 min 59 s
0.1 to 999.9 min
1 to 9999 min
1 min to 99 h 59 min
0.1 to 999.9 h
1 to 9999 h
Timer Mode
A: Signal ON Delay I
A-1: Signal ON Delay II
A-2: Power ON Delay I
A-3: Power ON Delay II
b: Repeat cycle 1
b-1: Repeat cycle 2
d: Signal OFF Delay
E: Interval
F: Cumulative
Z:
ON/OFF-duty-adjustable flicker
S: Stopwatch
Twin Timer Mode
toff: Flicker OFF Start 1
ton: Flicker ON Start 1
toff-1: Flicker OFF Start 2
ton-1: Flicker ON Start 2
Screw terminals
Signal, Reset,
Gate (NPN/
PNP inputs)
Contact output
(time-limit
SPDT)
100 to 240 VAC H5CX-A-N
12 to 24 VDC/
24 VAC H5CX-AD-N
Transistor
output (SPST)
100 to 240 VAC H5CX-AS-N
12 to 24 VDC/
24 VAC H5CX-ASD-N
11-pin socket
Contact output
(time-limit
SPDT)
100 to 240 VAC H5CX-A11-N
12 to 24 VDC/
24 VAC H5CX-A11D-N
Transistor
output (SPST)
100 to 240 VAC H5CX-A11S-N
12 to 24 VDC/
24 VAC H5CX-A11SD-N
H5CX-L 8-pin socket
Signal, Reset
(NPN inputs)
Contact output
(time-limit
SPDT)
100 to 240 VAC H5CX-L8-N
12 to 24 VDC/
24 VAC H5CX-L8D-N
Transistor
output (SPST)
100 to 240 VAC H5CX-L8S-N
12 to 24 VDC/
24 VAC H5CX-L8SD-N
Timer Mode
A-2: Power ON Delay I
b: Repeat cycle 1
E: Interval
Z:
ON/OFF-duty-adjustable flicker
Twin Timer Mode
toff: Flicker OFF Start 1
ton: Flicker ON Start 1
None
Contact output
(time-limit SPDT
+ instantaneous
SPDT)
Models with
instantaneous
contact outputs
100 to 240 VAC H5CX-L8E-N
12 to 24 VDC/
24 VAC H5CX-L8ED-N
H5CX-B
0.01 to 9999.99 s
1 s to 99 h 59 min 59 s
0.1 to 99999.9 min
0.1 to 99999.9 h
A: Signal ON Delay I
F-1: Cumulative Screw terminals
Signal, Reset,
Gate (NPN/
PNP inputs)
Transistor
output (DPST) 12 to 24 VDC H5CX-BWSD-N
4. Output type
*Can be used as a time-limit DPDT output.
5. Supply voltage
*The H5CX-BWSD-N is available only for 12 to 24 VDC.
Symbol Meaning
None Contact output (time-limit SPDT)
EContact output (time-limit
SPDT + instantaneous SPDT) *
S Transistor output
Symbol Meaning
None 100 to 240 VAC 50/60 Hz
D 12 to 24 VDC/24 VAC 50/60 Hz *
1. Type Classifier 2. External Connections 3. Settings
Symbol Meaning
A Standard type
B6-digit type
L Economy type
Symbol Meaning
None Screw terminals
8 8-pin socket
11 11-pin socket
Symbol Meaning
None One stage
WTwo stages
H5CX-@-N
4
Accessories (Order Separately)
Front Panels (Replacement Parts)
Note: 1. You can change the color of the front panel when mounting the Timer. The Timer is shipped with a black (N1.5) Front Panel.
2. "TIMER" is printed on the front of Replacement Front Panels.
Soft Cover
Hard Cover
Flush Mounting Adapter
Waterproof Packing
Connection Sockets
Terminal Covers for P3G-08 and P3GA-11 Back-connecting Sockets
Models Color Applicable Timers Page
Y92P-CXT4G Light gray (5Y7/1)
Four-digit models 12Y92P-CXT4S White (5Y9.2 / 0.5)
Y92P-CXT4B Black (N1.5)
Models Remarks Page
Y92A-48F1 --- 12
Models Remarks Page
Y92A-48 --- 12
Models Remarks Page
Y92F-30 Included with models with terminal blocks.
12
Y92F-45
Use this Adapter to install the Timer in a cutout
previously made for a DIN 72 x 72 mm device
(panel cutout: 68 x 68 mm).
Models Remarks Page
Y92S-29 Included with models with terminal blocks. 12
Models Type Connectable Timers Remarks Page
P2CF-08 Front Connecting
Socket
H5CX-L8@
13
P2CF-08-E
Front Connecting
Socket
(Finger-safe Type)
Round crimp terminals cannot be used on Finger-safe
Sockets. Use forked crimp terminals.
P2CF-11 Front Connecting
Socket
H5CX-A11@
P2CF-11-E
Front Connecting
Socket
(Finger-safe Type)
Round crimp terminals cannot be used on Finger-safe
Sockets. Use forked crimp terminals.
P3G-08
Back Connecting Socket
H5CX-L8@A Y92A-48G Terminal Cover can be used with the
Socket to create a finger-safe construction.
P3GA-11 H5CX-A11@
Models Remarks Page
Y92A-48G --- 14
H5CX-A@-N/-L@-N
5
Switch the display color* between red, green, and orange
to see the output status from a distance.
Up/Down Keys for each digit enable easy operation.
Cyclic control is easy with the Twin Timer and Variable
ON/OFF Duty modes.
*Not supported by the H5CX-A11@ or H5CX-L8@.
Specifications
Ratings
*1. Do not use the output from an inverter as the power supply. The ripple must be 20% maximum for DC power.
*2. Inrush current will flow for a short time when the power supply is turned ON.
Inrush Current (Reference Values)
*3. The display is lit only when the power is ON. Nothing is displayed when power is OFF.
H5CX-A@-N/-L@-N Digital Timers
Item Models H5CX-A@-N H5CX-A11@-N H5CX-L8@-N
Classification Standard Type Economy Type
Ratings
Power supply
voltage *1
100 to 240 VAC 50/60 Hz
12 to 24 VDC/24 VAC 50/60 Hz
Operating voltage
fluctuation range 85% to 110% of rated supply voltage (90% to 110% at 12 to 24 VDC)
Power consumption Approx. 6.2 VA at 100 to 240 VAC, Approx. 5.1 VA/2.4 W at 24 VAC/12 to 24 VDC *2
Mounting method Flush mounting Flush mounting, surface mounting, DIN track mounting
External connections Screw terminals 11-pin socket 8-pin socket
Degree of protection IEC IP66, UL508 Type 4X (indoors) for panel surface only and when Y92S-29 Waterproof Packing is used
4 digits
Digits
Time ranges 0.001 s to 9.999 s, 0.01 s to 99.99 s, 0.1 s to 999.9 s, 1 s to 9999 s, 1 s ti 99 min 59 s
0.1 m to 999.9 min, 1 min to 9999 min, 1 min to 99 h 59 min, 0.1 h to 999.9 h, 1 h to 9999 h
Timer mode Elapsed time (Up), remaining time (Down) (selectable)
Inputs
Input signals Signal, Reset, Gate
Signal, Reset
(no inputs on models with instantaneous
contact outputs)
Input method
No-voltage Input ON impedance: 1 kΩ max. (Leakage current: 12 mA when 0 Ω)
ON residual voltage: 3 V max.
OFF impedance: 100 kΩ min.
Voltage Input High (logic) level: 4.5 to 30 VDC
Low (logic) level: 0 to 2 VDC (Input resistance: approx. 4.7 kΩ)
No-voltage input/voltage input (switchable)
No-voltage Input
ON impedance: 1 kΩ max.
(Leakage current: 12 mA when 0 Ω)
ON residual voltage: 3 V max.
OFF impedance: 100 kΩ min.
Signal, reset, gate Minimum input signal width: 1 or 20 ms (selectable, same for all input)
Reset system Power reset (depending on output mode), external reset, manual reset, automatic reset (depending on output mode)
Power reset Minimum power-opening time: 0.5 s (except for A-3, b-1, F, ton-1, and toff-1 mode)
Reset voltage 10% max. of rated supply voltage
Sensor waiting time 250 ms max. (Control output is turned OFF and no input is accepted during sensor waiting time.)
Output
Output modes
A: Signal ON Delay I, A-1: Signal ON Delay II, A-2: Power ON Delay I, A-3: Power ON
Delay II, b: Repeat Cycle 1, b-1: Repeat Cycle 2, d: Signal OFF Delay, E: Interval, F:
Cumulative, Z: ON/OFF-duty-adjustable flicker, S: Stopwatch, toff: Flicker OFF Start 1,
ton: Flicker ON Start 1, toff-1: Flicker OFF Start 2, ton-1: Flicker ON Start 2
Models with Instantaneous Contact
Outputs
A-2: Power ON Delay I, b: Repeat Cycle 1,
E: Interval, Z: ON/OFF-duty-adjustable
flicker, toff: Flicker OFF Start 1, ton:
Flicker ON Start 1
One-shot output
time 0.01 to 99.99 s
Control output
Models with Contact Outputs
5 A at 250 VAC/30 VDC, resistive load (cos =1)
Minimum applied load: 10 mA at 5 VDC (failure level: P, reference value)
Transistor output: NPN open collector,
100 mA at 30 VDC max., residual voltage: 1.5 VDC max. (Approx. 1 V), Leakage current: 0.1 mA max.
Display method *3
7-segment, negative transmissive LCD;
Present value: 12-mm-high characters,
(switchable between red,
green, and orange)
Set value: 6-mm-high characters,
green
7-segment, negative transmissive LCD;
Present value: 12-mm-high characters, red
Set value: 6-mm-high characters, green
Memory backup EEPROM (overwrites: 100,000 times min.) that can store data for 10 years min.
Operating temperature range -10 to 55°C (-10 to 50°C if counters are mounted side by side) (with no icing or condensation)
Storage temperature range -25 to 70°C (with no icing or condensation)
Operating humidity range 25% to 85%
Case color Black (N1.5) (Optional Front Panels are available to change the Front Panel color to light gray or white.)
Attachments Waterproof packing, flush mounting
adapter, label for DIP switch settings Label for DIP switch settings ---
Voltage Applied voltage Inrush current (peak value) Time
100 to 240 VAC 264 VAC 5.3 A 0.4 ms
12 to 24 VDC/24 VAC 26.4 VAC 6.4 A 1.4 ms
26.4 VDC 4.4 A 1.7 ms
H5CX-A@-N/-L@-N
6
Characteristics
*Refer to Life-test Curve.
Accuracy of operating time
and setting error (including
temperature and voltage
influences)
Power-ON start: ±0.01% ±50 ms max. (See note 1.)
Signal start: ±0.005%±0.03 ms max. (See note 1.)
Signal start for transistor output model: ±0.005%±3 ms max. (See note
1 and 2.)
If the set value is within the sensor waiting time at startup the control
output of the H5CX will not turn ON until the sensor waiting time passes.
Note: 1. The values are based on the set value.
2. The value is applied for a minimum pulse width of 1 ms.
Insulation resistance
100 MΩ min. (at 500 VDC) between current-carrying terminal and
exposed non-current-carrying metal parts, and between non-continuous
contacts
Dielectric strength
2,000 VAC, 50/60 Hz for 1 min between current-carrying metal parts and
non-current-carrying metal parts
2,000 VAC, 50/60 Hz for 1 min between power supply and input circuits
for H5CX-A11-N/-A11S-N
1,000 VAC, 50/60 Hz for 1 min between control output, power supply,
and input circuits for H5CX-@SD-N
2,000 VAC, 50/60 Hz for 1 min between control output, power supply,
and input circuits for other models
1,000 VAC, 50/60 Hz for 1 min between non-continuous contacts
Impulse withstand voltage
3 kV (between power terminals) for 100 to 240 VAC, 1 kV for 24 VAC/12
to 24 VDC
4.5 kV (between current-carrying terminal and exposed non-current-
carrying metal parts) for 100 to 240 VAC 1.5 kV for 24 VAC/12 to 24 VDC
Noise immunity
±1.5 kV (between power terminals) and ±600 V (between input
terminals), square-wave noise by noise simulator (pulse width: 100 ns/
1 µs, 1-ns rise)
Static immunity Malfunction: 8 kV
Destruction: 15 kV
Vibration
resistance
Destruction 10 to 55 Hz with 0.75-mm single amplitude each in three directions for
2 h each
Malfunction 10 to 55 Hz with 0.35-mm single amplitude each in three directions for
10 min each
Shock
resistance
Destruction 300 m/s2 in three directions, three cycles
Malfunction 100 m/s2 in three directions, three cycles
Life
expectancy
Mechanical 10,000,000 operations min. (under no load at 18,000 operations/h and
ambient temperature of 23°C)
Electrical 100,000 operations min. (5 A at 250 VAC, resistive load at 1,800
operations/h and ambient temperature of 23°C) *
Weight Approx. 115 g (Timer only)
Life-test Curve (Reference
Values)
A maximum current of 0.15 A can be switched at
125 VDC (cosφ =1) and a maximum current of 0.1
A can be switched if L/R is 7 ms. In both cases, a
life of 100,000 operations can be expected.
DC30V L/R=7ms
AC250V/DC30V
cos
φ
=1
AC250V cos
φ
=0.4
0 1 2 3 4 5
1,000
500
100
50
10
Switching operations (× 10
4
)
Load current (A)
H5CX-A@-N/-L@-N
7
Applicable Standards
*1. The following safety standards apply to models with sockets (H5CX-A11@ or H5CX-L8@).
cUL (Listing): Applicable when an OMRON P2CF (-E) Socket is used.
cUR (Recognition): Applicable when any other socket is used.
*2. Excluding the H5CX-ASD-N/-A11SD-N/-L8SD-N.
I/O Functions
For details, refer to the timing charts on page 20 and page 29.
*1. The H5CX-L8E@ does not have an input.
*2. The H5CX-L@ does not have a gate input.
Response Delay Time When Resetting (Transistor Output)
The following table shows the delay from when the reset signal is input until the output is turned OFF.
(Reference value)
Approved safety standards
UL508/Listing, UL50 Type 4X for indoor use (enclosure rating), CSA C22.2 No. 14 *1,
conforms to EN61812-1 (Pollution degree 2/overvoltage category III)
B300 PILOT DUTY
1/4 HP 120 VAC, 1/3 HP, 240 VAC, 5 A resistive load
VDE0106/P100
CCC: Pollution degree 2, Overvoltage category II *2
EMC
(EMI) EN61812-1
Emission Enclosure: EN55011 Group 1 class A
Emission AC mains: EN55011 Group 1 class A
(EMS) EN61812-1
Immunity ESD: EN61000-4-2: 6 kV contact discharge (level 2)
8 kV air discharge (level 3)
Immunity RF-interference: EN61000-4-3: 10 V/m (Amplitude-modulated, 80 MHz to 1 GHz) (level 3);
10 V/m (Pulse-modulated, 900 MHz 5 MHz) (level 3)
Immunity Conducted Disturbance: EN61000-4-6: 10 V (0.15 to 80 MHz) (level 3)
Immunity Burst: EN61000-4-4: 2 kV power-line (level 3);
1 kV I/O signal-line (level 4)
Immunity Surge: EN61000-4-5: 1 kV line to lines (power and output lines) (level 3);
2 kV line to ground (power and output lines) (level 3)
Immunity Voltage Dip/Interruption: EN61000-4-11: 0.5 cycle, 100% (rated voltage)
Inputs *1
Start signal Normally functions to start timing.
In modes A-2 and A-3, disable timing. In mode S, starts and stops timing.
Reset
Resets present value. (In elapsed time mode, the present value returns to 0; in remaining time mode,
the present value returns to the set value.)
Count inputs are not accepted and control output turns OFF while reset input is ON.
Reset indicator is lit while reset input is ON.
Gate *2 Disables timing. (If a reset occurs while the gate input is ON, a reset will be performed.)
Outputs Control output (OUT) Outputs take place according to designated operating mode when timer reaches corresponding set value.
Minimum reset signal width Output delay time
1 ms 0.8 to 1.2 ms
20 ms 15 to 25 ms
H5CX-A@-N/-L@-N
8
Connections
Block Diagram
Note: Basic insulation is provided between the power supply circuit and the input circuits. However, basic insulation is not provided in the
H5CX-@D-N.
Terminal Arrangement
Confirm that the power supply meets specifications before use.
H5CX-A-N/-AD-N H5CX-AS-N/-ASD-N
H5CX-A11-N/-A11D-N H5CX-A11S-N/-A11SD-N
H5CX-L8-N/-L8D-N H5CX-L8S-N/-L8SD-N
H5CX-L8E-N/-L8ED-N
Note: Do not connect unused terminals as relay terminals.
Output circuit
(See note.)
Internal control
circuit
Display circuit
Key switch circuit
Input circuits
Power supply
circuit
(Basic insulation)
(Basic insulation)
6789
0V
12345
(-) (+)
Contact output
Reset
Signal
Gate
Terminals 1 and 6 of the H5CX-AD-N
are connected internally.
6789
0V
12345
(-) (+)
Transistor output
Reset
Signal
Gate
Terminals 1 and 6 of the H5CX-ASD-N
are connected internally.
67
8
9
10
11
1
2
3
4
5
0V
Reset
Signal
Gate Internal circuit
Unused
Unused
Contact
output
(-) (+)
Terminals 2 and 3 of the
H5CX-A11D-N are
connected internally.
67
8
9
10
11
1
2
3
4
5
0V
Reset
Signal
Gate Internal circuit
Unused
Unused
Transistor
output
(-) (+)
Terminals 2 and 3 of the
H5CX-A11SD-N are
connected internally.
4
3
2
1 8
7
6
5
0V
Signal
Reset
Internal circuit
Contact
output
(-) (+)
Terminals 1 and 2 of the H5CX-L8D-N
are connected internally.
4
3
2
1 8
7
6
5
0V
Signal
Reset
Internal circuit
Unused
Transistor
output
(-) (+)
Terminals 1 and 2 of the H5CX-L8SD-N
are connected internally.
Transistor Output
The transistor output of
the H5CX is insulated
from the internal circuitry
by a photocoupler, so the
transistor output can be
used as both NPN and
PNP output.
The diode connected to
the collector of the output
transistor is used to
absorb inverted voltage
that is generated when an
inductive load is
connected to the H5CX.
Power for load
+
Load
Power for load
+
Load
NPN Output PNP Output
Power for load
+
Timer
Inductive
load
4
3
2
18
7
6
5
(–) (+)
Internal circuit Internal circuit
Instantaneous
contact output
OUT1
Time-limit
contact output
OUT2
H5CX-A@-N/-L@-N
9
Input Circuits
Signal, Reset, and Gate Input
Input Connections
The inputs are no-voltage (closed or open) inputs or voltage inputs except for the H5CX-L8@. (The inputs of the H5CX-L8@ are no-voltage inputs
only. The H5CX-L8E@ does not have an input.)
No-voltage Inputs (NPN Inputs)
Voltage Inputs (PNP Inputs) The inputs of the H5CX-L8@ are no-voltage inputs only.
Voltage Input Signal Levels
Note: 1. The DC voltage must be 30 VDC max.
2. Input resistance: Approx. 4.7 kΩ
Open Collector Voltage Output Contact Input DC Two-wire Sensor
No-contact Input (NPN Transistor) No-contact Input (PNP Transistor) Contact Input
High level (Input ON): 4.5 to 30 VDC
Low level (Input OFF): 0 to 2 VDC
Internal
circuit
IN
+14 V
1 kΩ
Internal
circuit
IN
Approx. 4.7 kΩ
No-voltage Inputs (NPN Inputs) Voltage Inputs (PNP Inputs)
H5CX-A@
-
H5CX-A11@
H5CX-L8@
6789
3765
134
PLC or
sensor
Note: Operate with transistor ON
0 V for inputs
Reset input
Signal input
Gate input
H5CX-A@
H5CX-A11@
H5CX-L8@-
6789
3765
134
Sensor
Note: Operate with transistor ON
0 V for inputs
Reset input
Signal input
Gate input
H5CX-A@
-
H5CX-A11@
H5CX-L8@
6789
3765
134
Note: Operate with relay ON
0 V for inputs
Reset input
Signal input
Gate input
H5CX-A@
-
H5CX-A11@
H5CX-L8@
6789
3765
134
Note: Operate with transistor ON
0 V for inputs
Reset input
Signal input
Gate input
Applicable Two-wire Sensor
Leakage current: 1.5 mA max.
Switching capacity: 5 mA min.
Residual voltage: 3.0 VDC max.
Operating voltage: 10 VDC
No-voltage Input Signal Levels
Note: The DC voltage must be 30 VDC max.
No-contact
input
Short-circuit level Transistor ON
Residual voltage: 3 V max.
Impedance when ON: 1 kΩ max.
(The leakage current is approx. 12 mA when the
impedance is 0 Ω.)
Open level Transistor OFF
Impedance when OFF: 100 kΩ min.
Contact input Use contacts which can adequately switch 5 mA at 10 V
H5CX-A@
H5CX-A11@
6789
376
5
Sensor
Note: Operate with transistor OFF
0 V for inputs
Reset input
Signal input
Gate input
H5CX-A@
H5CX-A11@
6789
3765
Sensor
Note: Operate with transistor ON
0 V for inputs
Reset input
Signal input
Gate input
H5CX-A@
H5CX-A11@
6789
3765
Note: Operate with relay ON
0 V for inputs
Reset input
Signal input
Gate input
H5CX-A@-N/-L@-N
10
Nomenclature
Dimensions (unit: mm)
Digital Timers
Digital Timers
OFF
ON
12mm 6mm
1
3
2
8
9
5
4
6
7
10
11
12 13
Display Section
1. Key Protect Indicator
(orange)
2. Control Output Indicator
(orange)
Front View
Note: There is no DIP switch on the
H5CX-L8@.
Character Size
for Present
Value Display
Character Size
for Set Value
Display
3. Reset Indicator
(orange)
Operation Key
Switches
8. Mode Key
(Changes modes and setting items)
9. Reset Key
(Resets present value and output)
10. Up Keys 1 to 4
11. Down Keys 1 to 4
12. Key-protect Switch
13. DIP Switch
6. Set Value Display
(Sub-display)
(Character height: 6 mm, green)
7. Set Value 1, 2 Indicator
(green)
4. Present Value Display
(Main display)
(Character height: 12 mm, red
*
)
* Characters on models with screw terminals
(H5CX-A@) can be switched between red,
green, and orange.
5. Time Unit Indicators
(Color is same as present value display.)
(If the time range is 0 min, 0 h, 0.0 h, or 0 h
0 min, these indicators flash to indicate
timing operation.)
12345678
OFF
(Disabled)
ON
(Enabled)
(Default setting)
78
6
44.8×44.8
48×48
H5CX-A-N/-AS-N (Flush Mounting Models)
Note: M3.5 terminal screw (effective length: 6 mm)
59
6
44.8×44.8
48×48
H5CX-AD-N/-ASD-N (Flush Mounting Models)
Note: M3.5 terminal screw (effective length: 6 mm)
63.7 14.4
6
44.8×44.8
48×48
H5CX-A11@-N
(Flush Mounting/Surface Mounting Models)
H5CX-L8@-N (Flush Mounting/Surface Mounting Models)
63.7 14.2
6
44.8×44.8
48×48
H5CX-A@-N/-L@-N
11
Dimensions with Flush Mounting Adapter
58
48 76.57.5
(51)
Y92S-29 (provided)
Waterproof
Packing
Y92F-30 (provided)
Flush Mounting Adapter
Panel
H5CX-A-N/-AS-N (Provided with Adapter and Waterproof Packing) Panel Cutouts
Panel cutouts areas shown below. (according
to DIN43700).
Note: 1. The mounting panel thickness
should be 1 to 5 mm.
2. To allow easier operation, it is
recommended that Adapters
be mounted so that the gap
between sides with hooks is at
least 15 mm (i.e., with the
panel cutouts separated by at
least 60 mm).
3. It is possible to mount Timers
side by side, but only in the
direction without the hooks.
(However, if Timers are
mounted side by side, water
resistance will be lost.)
Dimensions with Front
Connecting Socket
*These dimensions vary with the type of DIN track
(reference value).
60 min.
60 min.
45
+0.6
0
45
+0.6
0
15 min.
A
A=(48n-2.5)
With Y92A-48F1 attached.
A={48n-2.5+(n-1)×4}
With Y92A-48 attached.
A = (51n - 5.5)
n Units mounted side-by-side
+1
–0
+1
–0
+1
–0
103.2 100.9
H5CX
-A11@-N
P2CF-11(-E) (order separately)
Front Connecting Socket
*
H5CX
-L8@-N
P2CF-08(-E) (order separately)
Front Connecting Socket
92.3 90
*
58
48 57.57.5
(51)
Y92S-29 (provided)
Waterproof
Packing
Y92F-30 (provided)
Flush Mounting Adapter
Panel
H5CX-AD-N/-ASD-N (Provided with Adapter and Waterproof Packing)
58
4889.97.5
(51)
Y92S-29 (order separately)
Waterproof Packing
Y92F-30 (order separately)
Flush Mounting Adapter P3GA-11 (order
separately)
Back-connecting
Socket
Panel
H5CX-A11@-N (Adapter and Waterproof Packing Ordered Separately)
H5CX-L8@-N (Adapter and Waterproof Packing Ordered Separately)
58
4884.87.5
(51)
Y92F-30 (order separately)
Flush Mounting Adapter P3G-08 (order
separately)
Back-connecting
Socket
PanelY92S-29 (order separately)
Waterproof Packing
H5CX-A@-N/-L@-N
12
Accessories (Order Separately)
Front Panel (Replacement Part)
You can change the color of the front panel when mounting the Timer.
The Timer is shipped with a black (N1.5) Front Panel. Protecting the Timer in Environments Subject to Oil
The Waterproof Packing will deteriorate, harden, and shrink
depending on the application environment. To ensure maintaining the
IP@6, UL Type 4X waterproof level, periodically replace the
Waterproof Packing. The periodic replacement period will depend on
the application environment. You must confirm the proper
replacement period. Use 1 year or less as a guideline. If the
Waterproof Packing is not replaced periodically, the waterproof level
will not be maintained.
It is not necessary to mount the Waterproof Packing if waterproof
construction is not required.
Note:
Depending on the operating environment, the condition of
resin products may deteriorate, and may shrink or become
harder. Therefore, it is recommended that resin products are
replaced regularly.
Y92P-CXT4S
Cover for Timer with 4 Digits
White (5Y9.2/0.5)
Y92P-CXT4G
Cover for Timer with 4 Digits
Light gray (5Y7/1)
Y92P-CXT4B
Cover for Timer with 4 Digits
Black (N1.5)
Replacement Method
The Front Panel is attached to
the Terminal with tabs in four
locations. To remove the Front
Panel, open the tabs and pull the
Front Panel forward.
To attach the Front Panel, press
it onto the Timer so that all four
tabs lodge into the groves on the
body of the Timer.
Ta bs
Grooves
The H5CX's panel surface is water-resistive (IP@6, UL Type 4X)
and so even if drops of water penetrate the gaps between the keys,
there will be no adverse effect on internal circuits. If, however, there
is a possibility of oil being present on the operator's hands, use the
Soft Cover. The Soft Cover ensures protection equivalent to IP54
against oil. Do not, however, use the H5CX in locations where it
would come in direct contact with oil.
Soft Cover
Y92A-48F1
Hard Cover
Y92A-48
Y92F-45
Use this Adapter
to install the
Timer in a cutout
previously made
for a DIN 72 x 72
mm device
(panel cutout:
68 x 68 mm).
Flush Mounting Adapter
Y92F-30
Order the Flush
Mounting Adapter
separately if it is
lost or damaged.
Note: A Flush
Mounting
Adapter is
included with
models with
screw
terminals.
Waterproo
f
Pack
i
ng
Y92S-29
Note: The
Waterproof
Packing is
included with
models with
screw
terminals.
Order the Waterproof Packing
separately if it is lost or damaged.
The Waterproof Packing can be used
to achieve IP66 protection.
H5CX-A@-N/-L@-N
13
Connection Sockets
Front-connecting Sockets
Note: Round crimp terminals cannot be used on Finger-safe Sockets. Use forked crimp terminals.
Back-connecting Sockets
Note: A Y92A-48G Terminal Cover can be used with the Socket to create a finger-safe construction.
Model Dimensions Terminal arrangement
and internal connections
Mounting hole
dimensions
P2CF-08
(Top View)
Note: The Socket can
also be mounted
to DIN track.
P2CF-08-E
(Finger Safe Terminal)
P2CF-11
(Top View)
Note: The Socket can
also be mounted
to DIN track.
P2CF-11-E
(Finger Safe Terminal
Type)
Model Dimensions Terminal arrangement
and internal connections
P3G-08
(Bottom View)
P3GA-11
(Bottom View)
4
70 max.
Two, 4.5-dia. holes
Eight, M3.5 x 7.5 sems screws 7.8
20.3 max.
4.5
3
50 max.
35.4
6 5 4 3
7 8 1 2
40±0.2
Two, M4 or 4.5-dia. holes
1278
4365
P2CF-08-E
10A250VAC
RESISTIVE
4
70 max.
Two, 4.5-dia. holes
Eight, M3.5 x 7.5 set screws 7.8
21.5 max.
20.3
19
4.5
35.4
1.3
3
5
50 max.
40±0.2
4
70 max.
50 max.
Two, 4.5-dia. holes
Eleven, M3.5 x 7.5 sems screws 7.8
31.2 max.
4.5
3
35.4
8 7 6 5
10 11 1 2
9 3
4
40±0.2
Two, M4 or 4.5-dia. holes
10 11
12
7865
3
4
9
P2CF-11-E
10A250VAC
RESISTIVE
4
70 max.
50 max.
40
±0.2
Two, 4.5-dia. holes
Eleven, M3.5 x 7.5 set screws 7.8
31.2 max.
30
4.5
35.4
1.2
3
5
27 dia
4.9 17
45
45
6543
7812
27 dia
4.5 16.3 6.2
25.6
45
45
876
4
39
5
101112
H5CX-A@-N/-L@-N
14
Terminal Covers for P3G-08 and P3GA-11 Back-connecting Sockets
Note: The Terminal Cover can be used with a Back-mounting Socket (P3G-08 or P3GA-11) to create a finger-safe construction.
Optional Products for Track Mounting
Note: Order Spacers in increments of 10.
Model Dimensions
Y92A-48G
Y92A-48G UP
P C
34
Twelve, 6.4 dia
47.7×47.7 48×48
27.6
24.6
16.5
47.4
1
35
±0.3
7.3
±0.15
27
±0.15
4.5
15 25 2510 15 (5) *
1025 25
1,000 (500) ** The values shown in parentheses are for the PFP-50N.
Mounting Track
PFP-100N
PFP-50N
15 25 25 1,000
4.5
25 25 1510 1
242735±0.3
16
1.5
29.2
10
Mounting Track
PFP-100N2
4.8
1.3
35.5 35.3
1.8
1
1.8
10
6.2
M4 spring washer
50
11.5
M4 x 8 pan
head screw
10
End Plate
PFP-M
5
16
12
44.3 34.8
16.5
Spacer
PFP-S
H5CX-A@-N/-L@-N
15
Timer
Operating Procedures
Setting Procedure Guide
Settings for Timer Operation *
Use the following settings.
Settings for Twin Timer Operation *
Refer to page 25.
*It is not necessary to mount the Waterproof Packing if waterproof construction is not required.
Operating Procedures for Timer Function
After making DIP switch settings for basic operation, advanced functions can be added using the operation keys on the front panel. Refer to
on page 16 for details.
Key-protect Switch
12345678
OFF
ON
Disabled Enabled ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
OFF
OFF
ON
ON
ON
Refer to the table on
the right.
Refer to the table on
the right.
DIP switch settings
Time range
Output modes
Timer mode
Input signal width
UP DOWN
20 ms 1 ms
0.001 s to 9.999 s
0.01 s to 99.99 s
0.1 s to 999.9 s
1 s to 9999 s
0 min 01 s to 99 min 59 s
0.1 min to 999.9 min
0 h 01 min to 99 h 59 min
0.1 h to 999.9 h
OFF
ON
OFF
ON
OFF
OFF
ON
ON
Mode A: Signal ON delay 1
(Timer resets when power comes ON.)
Mode A-2: Power ON delay 1
(Timer resets when power comes ON.)
Mode E: Interval
(Timer resets when power comes ON.)
Mode F: Cumulative
(Timer does not reset when power
comes ON.)
Note: All the pins are factory-set to OFF.
Be sure to turn ON pin 1 of the DIP switch.
Changes to DIP switch settings are enabled when the
power is turned ON.
(Set the DIP switch while the power is OFF.)
Step1
Step2
Settings for basic functions can be performed with just the DIP switch.
Note: There is no DIP switch on the H5CX-L8@. Go to .
Be sure to set pin 1 to ON when using the DIP switch.
Item OFF ON Time rangePin 4Pin 3Pin 2
1
2
3
4
5
6
7
8
Pin 6 Output modePin 5
Step2
H5CX-A@-N/-L@-N
16
Timer
Run mode
Power ON
Function setting mode
Set the time range using the keys.
Set the timer mode using the keys.
Set the output mode using the keys.
Set the input signal width using the keys.
Set the NPN/PNP mode using the keys.
Set the display color using the keys.
Set the function (instantaneous or time-limit operation) for the instantaneous output (output 1)
using the Keys.
Set each digit for the output time using the corresponding keys.
For details, refer to the Time Range List.
(If the output time is set to 0.00, is displayed.)
*1. If the mode is switched to the function setting mode during operation, operation will continue.
*2. Changes made to settings in function setting mode are enabled for the first time when the mode is changed to run mode.
Also, when settings are changed, the timer is reset (time initialized and output turned OFF).
Display Set Value
Time Range List
0.01 s to 99.99 s
(default setting)
0.1 s to 999.9 s
1 s to 9999 s
0 min 01 s to
99 min 59 s
0.1 min to
999.9 min
1 min to
9999 min
0 h 01 min to
99 h 59 min
0.1 h to 999.9 h
1 h to 9999 h
0.001 s to
9.999 s
~
Time range
Timer mode
Output modes
Output time
Input signal
NPN/PNP
input
Display color
Instantaneous/
time-limit
To next pageFrom next page
ss hs
(DOWN)(UP)
(1ms)(20ms)
(A-1) (A-2) (A-3) (b-1)(b) (d) (E) (F) (S)(Z)(A)
(0.01s) (99.99s)(Output hold)
Note:
Displayed for modes A, A-1, A-2, A-3, b, b-1 and S only.
Note:
Only modes A-2, b, E, and Z can be selected for models with instantaneous
contact outputs.
(PNP input)(NPN input)
Note:
Only displayed for the H5CX-A@ and H5CX-A11@.
(Red) (Green) (Orange) (Red-green) (Green-red) (Red-orange) (Orange-red) (Green-orange)(Orange-green)
Note:
Displayed only for models with terminal screws (H5CX-A@).
Note:
Displayed only for models with instantaneous contact outputs.
3 s min. *
2
3 s min. *
1
The characters displayed in reverse video are the default settings.
When performing settings with operation keys only, set pin1 of the DIP switch to OFF (factory setting).
If pin 1 of the DIP switch is set to ON, the setting items indicated in will not be displayed.
(Instantaneous) (Time-limit)
Step2
Settings that cannot be performed with the DIP switch are performed with the operation keys.
• Change to Function Setting Mode.
Note:
Not displayed for models with instantaneous contact outputs.
Function setting mode
……
s
20ms 1ms
pnp
grn
2c1c1c
red org r-g g-r r-o o-r g-o o-g
npn
downup
za-1aa-2
99.990.01hold
hold
a-3 b b-1 d e f s
For details on operations in run mode, refer to page 19.
H5CX-A@-N/-L@-N
17
Timer
*1
To previous
page
From previous
page
Output ON
count alarm
set value/
monitor value
Key protect
level
Set value
upper limit
(KP-1) (KP-2) (KP-3) (KP-4) (KP-5) (KP-6) (KP-7)
Instantaneous
output 1
(OUT1) ON
count alarm
set value
Instantaneous
output 2
(OUT2) ON
count alarm
set value
(9999 x 1000 times)
(0 x 1000 times)
(9999 x 1000 times)
(0 x 1000 times)
Note: The monitor value is only displayed.
It cannot be set.
Output ON
count alarm
set value
Output ON
count monitor
value
(9999 x 1000 times)
(0 x 1000 times)
Note: The monitor value is only displayed.
It cannot be set.
Note: The monitor value is only displayed.
It cannot be set.
Instantaneous
output 1
(OUT1) ON
count monitor
value
Instantaneous
output 2
(OUT2) ON
count monitor
value
(9999)(1)
99990
99990
99990
9999
kp-2
kp-1 kp-3 kp-4 kp-5 kp-6 kp-7
1
• Models without Instantaneous Contact Outputs
• Models with Instantaneous Contact Outputs
Function setting mode
Set the digits for the set value limit using the corresponding keys.
Set the key protect level using the keys.
*1. Set each digit for the output time using the corresponding keys.
~
~
~
H5CX-A@-N/-L@-N
18
Timer
Explanation of Functions
Operating Procedures for Timer Function
Items marked with stars () can be set using the DIP switch.
Time Range (timr)
Set the range to be timed in the range 0.001 s to 9,999 h.
Settings of type ---- h (9,999 h) and ---- min (9,999 min) cannot be
made with the DIP switch. Use the operation keys if these settings are
required.
Timer Mode (timm)
Set either the elapsed time (UP) or remaining time (DOWN) mode.
In UP mode, the elapsed time is displayed, and in DOWN mode, the
remaining time is displayed.
Output Mode (outm)
Set the output mode.
The possible settings are A, A-1, A-2, A-3, b, b-1, d, E, F, Z and S.
Only output modes A, A-2, E, and F can be set using the DIP switch.
Use the operation keys if a different setting is required.
(For details on output mode operation, refer to "Timing Charts" on
page 20.)
Output Time (otim)
When using one-shot output, set the output time for one-shot output
(0.01 to 99.99 s).
One-shot output can be used only if the selected output mode is A,
A-1, A-2, A-3, b, b-1 or S.
If the output time is set to 0.00, hold is displayed, and the output is
held.
Input Signal Width (iflt)
Set the minimum signal input width (20 ms or 1 ms) for signal, reset,
and gate inputs.
The same setting is used for all external inputs (signal, reset, and gate
inputs).
If contacts are used for the input signal, set the input signal width to
20 ms.
Processing to eliminate chattering is performed for this setting.
NPN/PNP Input Mode (imod)
Select either NPN input (no-voltage input) or PNP input (voltage
input) as the input format.
Set an NPN input when using a 2-wire sensor.
For details on input connections, refer to "Input Connections" on
page 9.
Display Color (colr)
(Terminal block model: H5CX-A@ only)
Set the color used for the present value.
Key Protect Level (kypt)
Set the key protect level.
Refer to “Key Protect Level” on page 32.
Instantaneous/Time-limit (otmd)
Set the contact output to time-limit SPDT + instantaneous SPDT or
time-limit SPDT operation.
Set Value Upper Limit (sl-h)
Set the upper limit for the set value when it is set in Run Mode.
The limit can be set to between 1 and 9999.
This setting does not apply to the ON duty in Z mode.
Output ON Count Alarm Set Value (on-a)
Set the alarm value for the output ON count.
The limit can be set to between 0 x 1000 (0 times) and 9999 x 1000
(9,999,000 times). Only the underlined values are set. The alarm will
be disabled if 0 is set.
If the total ON count of the output exceeds the alarm set value, e3 will
be displayed on the Timer to indicate that the output ON count alarm
value was exceeded. Refer to “Self-diagnostic Function” on page
32 for information on the e3 display.
ON Count Alarm Set Values for Outputs 1 and 2 (OUT1
and OUT2) (on1a and on2a)
Set the ON count alarm values for the outputs 1 and 2.
The limit can be set to between 0 x 1000 (0 times) and 9999 x 1000
(9,999,000 times). Only the underlined values are set. The alarm will
be disabled if 0 is set.
If the total ON count of instantaneous output 1 or 2 exceeds the alarm
set value, e3 will be displayed on the Timer to indicate that the output
ON count alarm value was exceeded. Refer to “Self-diagnostic
Function” on page 32 for information on the e3 display.
Output ON Count Monitor Value (on-c)
The monitor value is only displayed. It cannot be set.
The output ON count will be 1,000 times the displayed value.
ON Count Monitor Values for Outputs 1 and 2 (OUT1 and
OUT2) (on1c and on2c)
The monitor value for output 1 or 2 is only displayed. It cannot be set.
The output ON count will be 1,000 times the displayed value.
Output OFF Output ON
red Red (fixed)
grn Green (fixed)
org Orange (fixed)
r-g Red Green
g-r Green Red
r-o Red Orange
o-r Orange Red
g-o Green Orange
o-g Orange Green
H5CX-A@-N/-L@-N
19
Timer
Operation in Run Mode
Operating Procedures for Timer Function
Present Value and Set Value
These items are displayed when the power is turned ON. The present
value is displayed in the main display and the set value is displayed
in the sub-display.
The values displayed will be determined by the settings made for the
time range and the timer mode in function setting mode.
Present Value and ON Duty Ratio (Output Mode = Z)
The present value is displayed in the main display and the ON duty
ratio is displayed in the sub-display. Set the ON duty ratio used in ON/
OFF-duty-adjustable flicker mode (Z) as a percentage.
The output accuracy will vary with the time range, even if the ON duty
ratio setting is the same. Therefore, if fine output time adjustment is
required, it is recommended that the time range for the cycle time is
set as small as possible.
Examples: 1. When Time Range = - - - - s (9999 s)
Rounded off to the nearest integer (because of the
time range setting) ON time = 6 s
2. When Time Range = - -. - - s (99.99 s)
Rounded off to 2 decimal places (because of the time
range setting) ON time = 6.20 s
If a cycle time is set, cyclic control can be performed in ON/OFF-duty-
adjustable flicker mode simply by changing the ON duty ratio.
Present Value and Cycle Time (Output Mode = Z)
The present value is displayed in the main display and the cycle time
is displayed in the sub-display. Set the cycle time.
Present value
Set value
Present value
ON duty ratio
Present value
Cycle time
Set each digit for the output time using the corresponding keys.
Note: H5CX-L8E@-N Precautions
Set the Timer’s set value before using the Timer in a self-holding circuit.
Set each digit for the output time using the corresponding keys.
(The keys for the 4th digit cannot be used.)
Set each digit for the output time using the corresponding keys.
When Output Mode Z Is Selected
ON time = Cycle time x ON duty ratio (%)
100
20(s) x 31(%) = 6.2(s)
100
20.00(s) x 31(%) = 6.200(s)
100
Elapsed cycle time
ON duty set as a percentage
Up/Down keys used for analog
adjustment of the ON duty
ON duty (%)
Cycle time
Control output
OpenClose
Opening/
closing valve
ON duty
Fully closed
Fully open
0%100%
H5CX-A@-N/-L@-N
20
Timer
Timing Charts
Operating Procedures for Timer Function
Models without Instantaneous Contact Outputs
The gate input is not included in the H5CX-L8@ models. Either one-shot output or sustained output can be selected.
Mode A: Signal ON delay 1 (Timer resets when power comes ON.)
Basic operation Detailed operation
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
The control output is controlled using a sustained or
one-shot time period.
Note: Output is instantaneous when setting is 0.
Mode A-1: Signal ON delay 2 (Timer resets when power comes ON.)
Basic operation Detailed operation
Timing starts when the start signal goes ON, and
resets when the start signal goes OFF.
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
The control output is controlled using a sustained or
one-shot time period.
Note: Output is instantaneous when setting is 0.
Mode A-2: Power ON delay 1 (Timer resets when power comes ON.)
Basic operation Detailed operation
Timing starts when the reset input goes OFF.
The start signal disables the timing function (i.e.,
same function as the gate input).
The control output is controlled using a sustained or
one-shot time period.
Note: Output is instantaneous when setting is 0.
Mode A-3: Power ON delay 2 (Timer does not reset when power comes ON.)
Basic operation Detailed operation
Timing starts when the reset input goes OFF.
The start signal disables the timing function (i.e.,
same function as the gate input).
The control output is controlled using a sustained or
one-shot time period.
Note: Output is instantaneous when setting is 0.
Power
Output
*
Start signal
inputTiming
Power
Start signal
Gate
tt
Reset
Control output
Set value
0
Set value
UP
DOWN
0
Timing diagram
Power
Output
Start signal
input Timing
t
0
0
Power
Start signal
Gate
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
Timing
t
0
0
Power
Start signal
Gate
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
Timing
Sustained
ttt
0
0
Power
Start signal
Gate
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
H5CX-A@-N/-L@-N
21
Timer
Mode b: Repeat cycle 1 (Timer resets when power comes ON.)
Basic operation Detailed operation
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time
is up (OFF at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact
output type).
Sustained Output
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The control output is turned ON when time is up.
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact
output type).
One-shot Output
Mode b-1: Repeat cycle 2 (Timer does not reset when power comes ON.)
Basic operation Detailed operation
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time
is up (OFF at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact
output type).
Sustained Output
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The control output is turned ON when time is up.
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact
output type).
One-shot Output
Power
Output
*
Start signal
inputTiming Timing Timing Timing
0
0
Power
Start signal
Gate
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
*
Start signal
inputTiming Timing Timing Timing
tt
0
0
Power
Start signal
Gate
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
*
Start signal
inputTiming Timing Timing
Timing Sustained Timing
0
0
Power
Start signal
Gate
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
*
Start signal
inputTiming Timing Timing
Timing Sustained Timing
tt t tt
0
0
Power
Start signal
Gate
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
H5CX-A@-N/-L@-N
22
Timer
Mode d: Signal OFF delay (Timer resets when power comes ON.)
Basic operation Detailed operation
*Start signal input is enabled during timing.
The control output is ON when the start signal is ON
(except when the power is OFF or the reset is ON).
The timer resets when the time is up.
Note: Output functions only during start signal input
when setting is 0.
Mode E: Interval (Timer resets when power comes ON.)
Basic operation Detailed operation
*Start signal input is enabled during timing.
Timing starts when the start signal comes ON.
The timer resets when the time is up.
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Output is disabled when the setting is 0.
Mode F: Cumulative (Timer does not reset when power comes ON.)
Basic operation Detailed operation
Start signal enables timing (timing is stopped when the
start signal is OFF or when the power is OFF).
A sustained control output is used.
Note: Output is instantaneous when setting is 0.
When the H5CX is used with power start in mode F
mode or F-1 (i.e., cumulative operation with output on
hold), there will be a timer error (approximately 100 ms
each time the H5CX is turned ON) due to the
characteristics of the internal circuitry. Use the H5CX
with signal start if timer accuracy is required.
Mode Z: ON/OFF-duty-adjustable flicker (Timer resets when power comes ON.)
Basic operation Detailed operation
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time is
up (ON at start).
While the start signal is ON, the timer starts when power
comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact output
type).
Output
*
Start signal
inputTiming
Power
0
0
Power
Start signal
Gate
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
*
Start signal
inputTiming
0
0
Power
Start signal
Gate
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
Start signal
inputTiming Sustained Timing
0
0
Power
Start signal
Gate
Reset
Control output
Set value
Set value
UP
DOWN
Timing diagram
Power
Output
*
Start signal
inputTiming
(cycle time)
Timing
ON duty
(%)
Timing
(cycle time)
Timing
ON duty
(%)
Power
Start signal
Gate
Reset
Control output
Cycle time
ON duty setting
(%) ON time
0
Cycle time
ON duty setting
(%) ON time
UP
DOWN
0
Timing diagram
H5CX-A@-N/-L@-N
23
Timer
Models with Instantaneous Contact Outputs Either one-shot output or sustained output can be selected.
Note: H5CX-L8E@-N Precautions
Set the Timer’s set value before using the Timer in a self-holding circuit.
Mode S: Stopwatch (Timer resets when power comes ON.)
Basic operation Detailed operation
The signal starts and stops timing.
The display is held and timing is continued if the reset
or gate input is received during timing operation.
The timer resets if the reset or gate input is received
when the timing operation is stopped.
Note: Output is instantaneous when setting is 0.
Mode A-2: Power ON delay (Timer resets when power comes ON.)
Basic operation Detailed operation
The Timer starts when the power comes ON or when
the reset input goes OFF.
Note: Output is instantaneous when setting is 0.
Mode b: Repeat cycle 1 (Timer resets when power comes ON.)
Basic operation Detailed operation
The Timer starts when the power comes ON or when
the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms.
Power
Start signal
input
Gate/Reset
Display
(for elapsed
time) * flashes
*
Timing
RST
9999
Set time
0
Set time
0
UP
DOWN
Power
Start signal
Gate/Reset
Timing diagram
Output
Time-limit
output
Power
Timing
Instantaneous
output
t-a
Reset Key
Time-limit
contacts, NC
Time-limit
contacts, NO
Instantaneous
contacts, NC
Instantaneous
contacts, NO
t t-a t-aRt Rtt
t = Set time, Rt = Reset time (0.5 s min.), t – a < t (Indicates the time is less than the set time.)
Power
Instantaneous
output
Time-limit
output
Power
t (time) t (time) t (time) t (time)
t-a t-a t-aRt Rtttt t-at-attt
Reset Key
Time-limit
contacts, NC
One-shot Output
Time-limit
contacts, NO
Time-limit
contacts, NC
Instantaneous
contacts, NC
Time-limit
contacts, NO
Instantaneous
contacts, NO
t = Set time, Rt = Reset time (0.5 s min.), t – a < t (Indicates the time is less than the set time.)
Power
Sustained Output
H5CX-A@-N/-L@-N
24
Timer
Note: H5CX-L8E@-N Precautions
Set the Timer’s set value before using the Timer in a self-holding circuit.
Mode E: Interval (Timer resets when power comes ON.)
Basic operation Detailed operation
The Timer starts when the power comes ON or when
the reset input goes OFF.
Note: Output is not instantaneous when setting is 0.
Mode Z: ON/OFF-duty adjustable flicker (Timer resets when power comes ON.)
Basic operation Detailed operation
The Timer starts when the power comes ON or when
the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms.
Instantaneous
output
Time-limit
output
Power
Timing
t-a
Reset Key
Time-limit
contacts, NC
Time-limit
contacts, NO
Instantaneous
contacts, NC
Instantaneous
contacts, NO
t t-a t-aRt Rtt
t = Set time, Rt = Reset time (0.5 s min.), t – a < t (Indicates the time is less than the set time.)
Power
Timing (cycle time) Timing (cycle time)
Timing
(ON duty) (ON duty)
Timing
Instantaneous
output
Time-limit
output
Power
t-a t-aRt Rt
ttt-a t-a
dty dty dty dty
t-a
t = Set time, dty = ON duty time, Rt = Reset time (0.5 s min.), t – a < t (Indicates the time is less than the set time.)
Reset Key
Time-limit
contacts, NC
Time-limit
contacts, NO
Instantaneous
contacts, NC
Instantaneous
contacts, NO
Power
H5CX-A@-N/-L@-N
25
Twin Timer
Setting Procedure Guide
Operating Procedures for Twin Timer Function
After making DIP switch settings for basic operation, advanced functions can be added using the operation keys on the front panel. Refer to
on page 26 for details.
Hold down for 1 s min.
Hold down for 1 s min.
Timer
Press the or Key to
switch to a Twin Timer.
Twin timer
Key-protect Switch
Run mode
Power ON Timer/twin timer
selection mode
1
+
1
+
tim
12345678
OFF
ON
Step2 Settings for basic functions can be performed with just the DIP switch.
Note: There is no DIP switch on the H5CX-L8@. Go to .
Step1 Switching to a Twin Timer
Disabled Enabled OFF
ON
OFF
ON
OFF
OFF
ON
ON
Refer to the table on the right.
Refer to the table on the right.
DIP switch settings
OFF time range
ON time range
Output mode
Timer mode
Input signal width
UP DOWN
Flicker OFF start Flicker ON start
20 ms 1 ms
0.01 s to 99.99 s
0.1 s to 999.9 s
1 s to 9999 s
0 min 01 s to 99 min 59 s
OFF
ON
OFF
ON
OFF
OFF
ON
ON
0.01 s to 99.99 s
0.1 s to 999.9 s
1 s to 9999 s
0 min 01 s to 99 min 59 s
Note: All the pins are factory-set to OFF.
Step3
Be sure to turn ON pin 1 on the DIP switch.
Changes to DIP switch settings are enabled when the power is turned ON.
(Perform DIP switch settings while the power is OFF.)
Item OFF ON OFF time rangePin 3Pin 2
ON time rangePin 5Pin 4
1
2
3
4
5
6
7
8
Be sure to set pin 1 to ON when using the DIP switch.
twn
Step3
H5CX-A@-N/-L@-N
26
Twin Timer
To switch to twin timer operation, use the procedure given below. For details, refer to page 31.
Run mode
Power ON
Function setting mode
From next pageTo next page
(1 ms)(20 ms)
(PNP input)(NPN input)
Note: Displayed only for the H5CX-A
@ and H5CX-A11@.
(Red) (Green) (Orange) (Red-green) (Green-red) (Red-orange) (Orange-red) (Green-orange) (Orange-green)
Note: Displayed only for models with terminal screws (H5CX-A
@).
Note: Displayed only for models with instantaneous contact outputs.
(Instantaneous) (Time-limit)
3 s min. *2
3 s min. *1
Step3
ss hs
ss hs
(DOWN)(UP)
OFF time
range
ON time
range
Timer mode
ON/OFF
start mode
Input signal
width
NPN/PNP
input
Display
color
Instantaneous/
time-limit
( ) ( ) ( ) ( )
Display Set Value
Time Range List
0.01 s to 99.99 s
(default setting)
0.1 s to 999.9 s
1 s to 9999 s
0 min 01 s to
99 min 59 s
0.1 min to
999.9 min
1 min to
9999 min
0 h 01 min to
99 h 59 min
0.1 h to 999.9 h
1 h to 9999 h
0.001 s to
9.999 s
Flicker
OFF start 1
Flicker
On Start 1
Flicker
OFF start 2
Flicker
On Start 2
Note:
Not displayed for models with instantaneous contact outputs.
Note:
Only Flicker OFF Start 1 or Flicker ON Start 1 can be selected for the H5CX-L8E@.
20ms
up down
1ms
pnp
grn
2c1c1c
red org r-g g-r r-o o-r g-o o-g
npn
……
s
……
s
toff ton tof1 ton1
For details, refer to Time Range List.
For details, refer to Time Range List.
The characters displayed in reverse video are the default settings.
When performing settings with operation keys only, set pin1 of the DIP switch to OFF (factory setting).
If pin 1 of the DIP switch is set to ON, the setting items indicated in will not be displayed.
Settings that cannot be performed with the DIP switch are performed with the operation keys.
• Change to Function Setting Mode.
Function setting mode
Set the OFF time range using the keys.
Set the ON time range using the keys.
Set the timer mode using the keys.
Set the twin timer output mode using the keys.
Set the input signal width using the keys.
Set the NPN/PNP input mode using the keys.
Set the display color using the keys.
Set the function (instantaneous or time-limit operation) for the instantaneous output (output 1)
using the Keys.
*1. If the mode is switched to the function setting mode during operation, operation will continue.
*2. Changes made to settings in function setting mode are enabled for the first time when the mode is changed to run mode.
Also, when settings are changed, the timer is reset (time initialized and output turned OFF).
For details on operations in run mode, refer to page 28.
H5CX-A@-N/-L@-N
27
Twin Timer
~
~
~
(KP-1) (KP-2) (KP-3) (KP-4) (KP-5) (KP-6) (KP-7)
(9999 x 1000 times)
(0 x 1000 times)
(9999 x 1000 times)
(0 x 1000 times)
(9999 x 1000 times)
(0 x 1000 times)
Note: The monitor value is only displayed.
It cannot be set.
Note:
The monitor value is only displayed.
It cannot be set.
Note:
The monitor value is only displayed.
It cannot be set.
To previous
page
From previous
page
Function setting mode
Set the digits for the set value limit using the corresponding keys.
Set the key protect level using the keys.
Set value
upper limit 1
Set the digits for the set value limit using the corresponding keys.
Set value
upper limit 2
Key protect
level
Output ON
count alarm
set value/
monitor value
Output ON
count alarm
set value
Output ON
count monitor
value
Instantaneous
output 1
(OUT1) ON
count alarm
set value
Instantaneous
output 2
(OUT2) ON
count alarm
set value
Instantaneous
output 1
(OUT1) ON
count monitor
value
Instantaneous
output 2
(OUT2) ON
count monitor
value
• Models without Instantaneous Contact Outputs
• Models with Instantaneous Contact Outputs
*1. Set the digits for the output ON alarm set value using the corresponding
keys.
*1
(9999)(1)
99990
99990
99990
9999
kp-2
kp-1 kp-3 kp-4 kp-5 kp-6 kp-7
1
(9999)(1)
99991
H5CX-A@-N/-L@-N
28
Twin Timer
Explanation of Functions
Operating Procedures for Twin Timer Function
Items marked with stars () can be set using the DIP switch.
OFF Time Range (oftr)
Set the time range for the OFF time in the range 0.000 s to 9,999 h.
Only settings of type --.-- s (99.99 s), ---.- s (999.9 s), ---- s (9,999 s),
and -- min -- s (99 min 59 s) can be made with the DIP switch. Use the
operation keys if another type of setting is required.
ON Time Range (ontr)
Set the time range for the ON time in the range 0.001 s to 9,999 h.
Only settings of type --.-- s (99.99 s), ---.- s (999.9 s), ---- s (9,999 s),
and -- min -- s (99 min 59 s) can be made with the DIP switch. Use the
operation keys if another type of setting is required.
Timer Mode (timm)
Set either the elapsed time (UP) or remaining time (DOWN) mode.
In UP mode, the elapsed time is displayed, and in DOWN mode, the
remaining time is displayed.
ON/OFF Start Mode (totm)
Set the output mode.
Set either flicker OFF start or flicker ON start. (For details on output
mode operation, refer to "Timing Charts" on page 29.)
Input Signal Width (iflt)
Set the minimum signal input width (20 ms or 1 ms) for signal, reset,
and gate inputs.
The same setting is used for all external inputs (signal, reset, and gate
inputs).
If contacts are used for the input signal, set the input signal width to
20 ms.
Processing to eliminate chattering is performed for this setting.
NPN/PNP Input Mode (imod)
Select either NPN input (no-voltage input) or PNP input (voltage input)
as the input format. Set an NPN input when using a 2-wire sensor.
The same setting is used for all external inputs.
For details on input connections, refer to "Input Connections" on
page 9.
Display Color (colr)
(Terminal black model: H5CX-A@ only)
Set the color used for the present value.
Key Protect Level (kypt)
Set the key protect level.
Refer to “Key Protect Level” on page 32.
Operation in Run Mode
Operating Procedures for Twin Timer Function
Present Value and OFF Set Time
The present value is displayed in the main display and the OFF set
time is displayed in the sub-display. Set the OFF time.
Present Value and ON Set Time
The present value is displayed in the main display and the ON set
time is displayed in the sub-display. Set the ON time.
Output OFF Output ON
red Red (fixed)
grn Green (fixed)
org Orange (fixed)
r-g Red Green
g-r Green Red
r-o Red Orange
o-r Orange Red
g-o Green Orange
o-g Orange Green
Present value
OFF set time
Present value
ON set time
Note: 1. The display will automatically show the OFF set time when the OFF time is being timed and the ON set time when the ON time is being timed.
Note: 2. H5CX-L8E@-N Precautions
Set the Timer’s set value before using the Timer in a self-holding circuit.
Set the digits for the OFF set time using the corresponding keys.
Set the digits for the OFF set time using the corresponding keys.
H5CX-A@-N/-L@-N
29
Twin Timer
Timing Charts
Operating Procedures for Timer Function
Models without Instantaneous Contact Outputs
The gate input is not included in the H5CX-L8@ models.
Mode toff: Flicker OFF start 1 (Timer resets when power comes ON.)
Basic operation Detailed operation
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time is
up (OFF at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact output
type).
Mode ton: Flicker OFF start 1 (Timer resets when power comes ON.)
Basic operation Detailed operation
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time is
up (ON at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact output
type).
Mode toff-1: Flicker OFF start 2 (Timer does not reset when power comes ON.)
Basic operation Detailed operation
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time is
up (OFF at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact output
type).
Power
Output
*
Start signal
inputTiming
OFF
Timing
ON
Timing
OFF
Timing
ON
ON time
OFF time
0
OFF time
ON time
0
UP
DOWN
Power
Start signal
Gate
Reset
Control output
Timing diagram
Power
Output
*
Start signal
inputTiming
ON
Timing
OFF
Timing
ON
Timing
OFF
0
0
ON time
OFF time
OFF time
ON time
UP
DOWN
Power
Start signal
Gate
Reset
Control output
Timing diagram
Power
Output
*
Start signal
input
Timing
OFF
Timing
ON
Timing
OFF
(a + b = ON time)
ab
0
0
ON time
OFF time
OFF time
ON time
UP
DOWN
Power
Start signal
Gate
Reset
Control output
Timing diagram
H5CX-A@-N/-L@-N
30
Twin Timer
Models with Instantaneous Contact Outputs
Note: H5CX-L8E@-N Precautions
Set the Timer’s set value before using the Timer in a self-holding circuit.
Mode ton-1: Flicker ON start 2 (Timer does not reset when power comes ON.)
Basic operation Detailed operation
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time is
up (ON at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact output
type).
Mode toff: Flicker OFF start 1 (Timer resets when power comes ON.)
Basic operation Detailed operation
The Timer starts when the power comes ON or when
the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the ON time and OFF time to at least 100
ms.
Mode ton: Flicker ON start 1 (Timer resets when power comes ON.)
Basic operation Detailed operation
The Timer starts when the power comes ON or when
the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the ON time and OFF time to at least 100
ms.
Timing
ON
Timing
OFF
Timing
ON
(a + b = OFF time)
ab
Power
Output
*
Start signal
input
0
0
ON time
OFF time
OFF time
ON time
UP
DOWN
Power
Start signal
Gate
Reset
Control output
Timing diagram
Ton timeToff timeTon timeToff time
Instantaneous
output
Time-limit
output
Power
t-a t-b t-aRt Rtt-off t-on t-off t-b t-at-off t-on t-off
t-on = ON time, t-off = OFF time, Rt = Reset time (0.1 s min.), t – a < t-off and t – b < t-on
(Indicates the time is less than the set time.)
Reset Key
Time-limit
contacts, NC
Time-limit
contacts, NO
Instantaneous
contacts, NC
Instantaneous
contacts, NO
Power
Toff time
Ton time
Toff time
Ton time
Instantaneous
output
Time-limit
output
Power
t-b t-a t-bRt Rtt-on t-off t-on t-a t-bt-on t-off t-on
t-on = ON time, t-off = OFF time, Rt = Reset time (0.1 s min.), t – a < t-off and t – b < t-on
(Indicates the time is less than the set time.)
Reset Key
Time-limit
contacts, NC
Time-limit
contacts, NO
Instantaneous
contacts, NC
Instantaneous
contacts, NO
Power
H5CX-A@-N/-L@-N
31
Timer/Twin Timer Selection Mode (Function Selection)
Select whether the H5CX is used as a timer or a twin timer in timer/twin timer selection mode.
The H5CX is also equipped with a DIP switch monitor function, a convenient function that enables the settings of the DIP switch pins to be
confirmed using the front display.
1
+
1
twn
1
1
tim
KeyKey
OFF
ON
12345678
1 s min.
Indicates that DIP switch pin 8 is ON.
Indicates that DIP switch pin 7 is OFF.
Indicates that DIP switch pin 6 is ON.
Indicates that DIP switch pin 5 is OFF.
Indicates that DIP switch pin 4 is ON.
Indicates that DIP switch pin 3 is OFF.
Indicates that DIP switch pin 2 is ON.
Indicates that DIP switch pin 1 is ON.
*1. When the mode is changed to timer/twin timer selection mode, the present value is reset and output turns OFF.
Timing operation is not performed in timer/twin timer selection mode.
*2. Setting changes made in timer/twin timer selection mode are enabled when the mode is changed to run mode.
If settings are changed, the HC5X is automatically reset (present value initialized, output turned OFF).
Power ON
Example
Timer/Twin
timer selection
Caution
DIP switch
monitor
Run modeTimer/Twin Timer Selection Mode
Convenient
*2 *1
To change the mode to timer/twin timer selection mode,
hold down the key for 1 s min. with the key held
down. The key must be pressed before the key. If the
key is pressed first, the mode will not change.
Select either timer operation or twin timer operation using the
keys.
Note: The H5CX is factory-set for timer operation.
Confirm the status of DIP switch pins 1 to 8 using the keys.
Note: 1. This display is not supported with H5CX-L8@-N.
2. This display is only possible when DIP switch pin 1 (DIP switch settings
enable/disable) is set to ON (enable).
H5CX-A@-N/-L@-N
32
Key Protect Level
When the key-protect switch is set to ON, it is possible to prevent setting errors by prohibiting the use of certain operation keys by specifying the
key protect level (KP-1 to KP-7).
The key protect indicator is lit while the key-protect switch is set to ON.
*Changing mode to Timer/Twin Timer Selection Mode or Function Setting Mode.
Self-diagnostic Function
The following displays will appear if an error occurs.
*1. This includes times when the life of the EEPROM has expired.
*2. The normal display and e3 will appear alternately.
When the Reset Key is pressed, e3 will no longer be displayed even if the alarm set value is exceeded. (Monitoring is possible, however, because the Timer will
continue without clearing the output ON count.)
Level Meaning
Details
Changing mode*
Switching display
during operation
Reset Key
Up/down key
KP-1
(default setting) Invalid Valid Valid Valid
KP-2 Invalid Valid Invalid Valid
KP-3 Invalid Valid Valid Invalid
KP-4 Invalid Valid Invalid Invalid
KP-5 Invalid Invalid Invalid Invalid
KP-6 Invalid Invalid Valid Valid
KP-7 Invalid Invalid Invalid Valid
Main display Sub-display Error Output status Correction method Set value after reset
e1 Not lit CPU OFF Either press the reset key or
reset the power supply. No change
e2 Not lit Memory error (RAM) OFF Reset the power supply. No change
e2 sum Memory error EEPROM *1 OFF Reset Key Factory setting
e3 *2 No change Output ON count alarm set
value exceeded No change Reset Key No change
* Factory-set to OFF
*
OFF
(Disabled)
ON
(Enabled)
Key protect indicator
H5CX-B@-N
33
H5CX Digital Timers with 6-digit Display, 2-stage Setting,
and Forecast Output (DIN 48 x 48-mm)
Times the daily operating hours of machinery and tools,
predicting and notifying when maintenance is required.
Easy-to-read backlit negative LCD with 6 digits (displays
to 99999.9 h).
The 2-stage settings and forecast output are ideal for
maintenance applications.
Specifications
Ratings
*1. Inrush current will flow for a short time when the power supply is turned ON.
Inrush Current (Reference Values)
*2. The display is lit only when the power is ON.
Digital Timer H5CX-B@-N
Classification Digital Timer with 6-digit display, 2-stage setting, and forecast output
Ratings
Power supply voltage 12 to 24 VDC
Operating voltage
fluctuation range 90% to 110% rated supply voltage
Power consumption Approx. 2.3 W *1
Mounting method Flush mounting
External connections Screw terminals
Degree of protection IEC IP66, UL508 Type 4X (indoors) for panel front surface only and only when Y92S-29 Waterproof Packing is used
Digits 6 digits
Time range 0.01 s to 9999.99 s, 1 s to 99 h 59 min 59 s, 0.1 min to 99999.9 min, 0.1 h to 99999.9 h
Timer mode Elapsed time (Up)
Inputs
Input signals Signal, reset, gate
Input method
No-voltage Input ON impedance : 1 kΩ max. (Leakage current: 12 mA when 0 Ω)
ON residual voltage : 3 V max.
OFF impedance : 100 kΩ min.
Voltage Input High (logic) level : 4.5 to 30 VDC
Low (logic) level : 0 to 2 VDC (Input resistance: approx. 4.7 kΩ)
No-voltage (NPN) input/voltage (PNP) input (switchable)
Signal, reset, gate Minimum input signal width: 1 or 20 ms (selectable, same for all input)
Reset system Power resets (only for A mode), external and manual reset
Power reset Minimum power-opening time: 0.5 s (except for F-1 mode)
Reset voltage 10% max. of rated supply voltage
Sensor waiting time 250 ms max. (Control output is turned OFF and no input is accepted during sensor waiting time.)
Outputs
Output modes A, F-1
Output type Transistor output: NPN open collector, 100 mA at 30 VDC max. residual voltage: 1.5 VDC max. (Approx. 1 V)
Leakage current: 0.1 mA max.
Display
7-segment, negative transmissive LCD;
Present value: 10-mm-high characters, red
Set value: 6-mm-high characters, green *2
Memory backup EEPROM (overwrites: 100,000 times min.) that can store data for 10 years min.
Operating temperature range -10 to 55°C (-10 to 50°C if counters are mounted side by side) (with no icing or condensation)
Storage temperature range -25 to 70°C (with no icing or condensation)
Operating humidity range 25 to 85%
Case color Black (N1.5)
Attachments Waterproof packing, flush mounting adapter, unit label
Voltage Applied voltage Inrush current (peak value) Time
12 to 24 VDC 26.4 VDC 4.4 A 1.7 ms
H5CX-B@-N
34
Characteristics
Applicable Standards
I/O Functions
Response Delay Time When Resetting (Transistor Output)
The following table shows the delay from when the reset signal is input until the output is turned OFF.
(Reference value)
Accuracy of operating time
and setting error
(including temperature and
voltage influences)
Power-ON start: ±0.01% ±50 ms max. (See note 1.)
Signal start: ±0.005%±0.03 ms max. (See note 1.)
Signal start for transistor output model: ±0.005%±3 ms max. (See note 1 and 2.)
If the set value is within the sensor waiting time at startup the control output of the H5CX will not turn ON until the sensor waiting
time passes.
Note: 1. The values are based on the set value.
2. The value is applied for a minimum pulse width of 1 ms.
Insulation resistance 100 MΩmin. (at 500 VDC) between current-carrying terminal and exposed non-current-carrying metal parts
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min between current-carrying metal parts and non-current-carrying metal parts
1,000 VAC, 50/60 Hz for 1 min between control output, power supply, and input circuit
Impulse withstand voltage 1.0 kV (between power terminals)
1.5 kV (between current-carrying terminal and exposed non-current-carrying metal parts)
Noise immunity ±480 V (between power terminals) and ±600 V (between input terminals), square-wave noise by noise simulator
(pulse width: 100 ns/1 µs, 1-ns rise)
Static immunity Destruction: 15 kV
Malfunction: 8 kV
Vibration
resistance
Destruction 10 to 55 Hz with 0.75-mm single amplitude in three directions for 2 h each
Malfunction 10 to 55 Hz with 0.35-mm single amplitude in three directions for 10 min each
Shock
resistance
Destruction 300 m/s2 in three directions, three cycles
Malfunction 100m/s2 in three directions, three cycles
Weight Approx. 105 g (Timer only)
Approved safety standards UL508/Listing, CSA C22.2 No. 14, conforms to EN 61812-1 (pollution degree 2/overvoltage category III)
Conforms to VDE0106/P100 (finger protection).
EMC
(EMI)
Emission Enclosure:
(EMS)
Immunity ESD:
Immunity RF-interference:
Immunity Conducted Disturbance:
Immunity Burst:
Immunity Surge:
EN61812-1
EN55011 Group 1 class A
EN61812-1
EN61000-4-2: 6 kV contact discharge (level 2)
8 kV air discharge (level 3)
EN61000-4-3: 10 V/m (Amplitude-modulated, 80 MHz to 1 GHz) (level 3);
10 V/m (Pulse-modulated, 900 MHz 5 MHz) (level 3)
EN61000-4-6: 10 V (0.15 to 80 MHz) (level 3)
EN61000-4-4: 2 kV power-line (level 3);
1 kV I/O signal-line (level 4)
EN61000-4-5: 1 kV line to lines (power and output lines) (level 3);
2 kV line to ground (power and output lines) (level 3)
Inputs
Start signal Starts timing.
Reset
Resets present value. (The present value returns to 0.)
Timing stops and control output turns OFF while reset input is ON.
Reset indicator is lit while reset input is ON.
Gate Inhibits timer operation.
Outputs
Forecast value
setting
Control output (OUT2) Turns ON when the present value reaches the set value.
Forecast output (OUT1) Turns ON when the present value reaches the forecast value.
Absolute value
setting
Control output 2 (OUT2) Turns ON when the present value reaches set value 2.
Control output 1 (OUT1) Turns ON when the present value reaches set value 1.
Minimum reset signal width Output delay time
1 ms 0.8 to 1.2 ms
20 ms 15 to 25 ms
H5CX-B@-N
35
Connections
Block Diagram
Terminal Arrangement
Input Circuits
Signal, Reset, and Gate Input
Transistor Output
The transistor output of
the H5CX is insulated
from the internal circuitry
by a photocoupler, so the
transistor output can be
used as both NPN and
PNP output.
The diode connected to
the collector of the output
transistor is used to
absorb inverted voltage
that is generated when an
inductive load is
connected to the H5CX.
Input Connections
The inputs of the H5CX-B are no-voltage (short-circuit or open) inputs or voltage inputs.
No-voltage Inputs (NPN Inputs)
Voltage Inputs (PNP Inputs)
Voltage Input Signal Levels
Note: 1. The DC voltage must be 30 VDC max.
2. Input resistance: Approx. 4.7 kΩ
Output circuit
Internal control
circuit
Display circuit
Key switch
circuit
Input circuits
Power supply
circuit
(Basic insulation)
678910
12 13 OUT 1
OUT 2
(+)(–)
0 V
12345
Reset
Gate
Signal
Reset
Note: 1. The power supply and input circuit
are not isolated.
2. Terminals 1 and 6 are connected
internally.
3. Terminals 7 and 10 have the same
reset function. The same function will
be performed whichever terminal is
connected. Terminals 7 and 10 are
not connected internally, however, so
do not use them for cross-over wiring.
Internal
circuit
IN
+14 V
1 kΩ
Internal
circuit
IN
Approx. 4.7 kΩ
No-voltage Inputs (NPN Inputs) Voltage Inputs (PNP Inputs)
Power for load
+
Load
Power for load
+
Load
NPN Output PNP Output
Power for load
+
Timer
Inductive
load
Open Collector Voltage Output Contact Input DC Two-wire Sensor
PLC or
sensor
Note: Operate with transistor ON
6789
10
Reset
Gate
Signal
Reset
0 V for inputs
Sensor
Note: Operate with transistor ON
6789
10
Reset
Gate
Signal
Reset
0 V for inputs
Note: Operate with relay ON
6789
10
Reset
Gate
Signal
Reset
0 V for inputs
Note: Operate with transistor ON
6789
10
Reset
Gate
Signal
Reset
0 V for inputs
Applicable Two-wire Sensor
Leakage current: 1.5 mA max.
Switching capacity: 5 mA min.
Residual voltage: 3.0 VDC max.
Operating voltage: 10 VDC
No-voltage Input Signal Levels
No-contact
input
Short-circuit level (Transistor ON)
Residual voltage: 3 V max.
Impedance when ON: 1 kΩ max.
(The leakage current is approx. 12 mA when the impedance is 0 Ω.)
Open level (Transistor OFF)
Impedance when OFF: 100 kΩ min.
Contact input Use contacts which can adequately switch 5 mA at 10 V
No-contact Input (NPN Transistor) No-contact Input (PNP Transistor) Contact Input
High level (Input ON): 4.5 to 30 VDC
Low level (Input OFF): 0 to 2 VDC
Sensor
Note: Operate with transistor OFF
6789
10
Reset
Gate
Signal
Reset
0 V for inputs
Sensor
Note: Operate with transistor ON
6789
10
Reset
Gate
Signal
Reset
0 V for inputs
Note: Operate with relay ON
6789
10
Reset
Gate
Signal
Reset
0 V for inputs
H5CX-B@-N
36
Nomenclature
Key Protect Level
When the Key-protect Switch is ON, key operations are prohibited
according to the settings for DIP switch pins 6 to 8, thus preventing
setting errors.
The Key-protect Switch can be turned ON and OFF while the power
is ON.
The Key Protection Indicator is lit orange when the Key-protect Switch
is ON.
If the key protect switch is ON, you will not be able to switch to
Function Setting Mode.
Dimensions (unit: mm)
Digital Timers
Accessories (Order Separately)
Refer to page 12 for details.
OFF
(Disabled)
ON
(Enabled)
(Default setting)
11 12
10mm 6mm
1
2
3
8
9
4
6
7
5
10
Display Section
3. Reset Indicator
(orange)
1. Key Protection Indicator
(orange)
2. Control Output Indicator
(orange)
4. Present Value Display
(red)
Character height: 10 mm
7. Set Value 1, 2 Indicator
(green)
If the time range is 0.0 min or 0.0 h, the decimal
point flashes to indicate timing operation.
6. Set Value
(green)
Character height: 6 mm
5. Time Unit Indicators
(green)
Lit when the reset input or Reset Key is ON.
Lit when the reset input or Reset Key is ON.
Forecast value setting
Operation Key
8. Mode Key
9. Reset Key
Switches
11. Key-protect Switch
12. DIP Switch
First digitSixth digit
Absolute value setting
(Changes modes and setting items)
Resets present value and output.
Character Size
for Present
Value Display
Character Size
for Set Value
Display
Forecast output ON: OUT 1 is lit.
Control output ON: OUT 2 is lit.
Control output 1 ON: OUT 1 is lit.
Control output 2 ON: OUT 2 is lit.
10. Up Keys 1 to 6
OFF
ON
12345678
Digital Timers
H5CX-BWSD-N (Flush Mounting Models)
44.8×44.8
59
6
48×48
Note: M3.5 terminal screw (effective length: 6 mm)
Panel Cutouts
Panel cutouts areas shown below. (according
to DIN43700)
Note: 1. The mounting panel thickness should
be 1 to 5 mm.
2. To allow easier operation, it is
recommended that Adapters be
mounted so that the gap between
sides with hooks is at least 15 mm
(i.e., with the panel cutouts separated
by at least 60 mm).
3. It is possible to mount Timers side by
side, but only in the direction without
the hooks. However, if Timers are
mounted side by side, water
resistance will be lost.
60 min.
60 min.
45
+0.6
–0
45
+0.6
–0
15 min.
n side by side mounting
A
A= (48n–2.5)+1
–0
With Y92A-48F1 attached.
A={48n–2.5+(n–1)×4}+1
–0
With Y92A-48 attached.
A= (51n–5.5)+1
–0
Dimensions with Flush Mounting Adapter
H5CX-BWSD-N (Provided with Adapter and Waterproof Packing)
58
48 7.5 57.5
(51)
Y92F-30 (provided)
Flush Mounting Adapter
PanelY92S-29 (provided)
Waterproof Packing
H5CX-B@-N
37
Operating Procedures
DIP Switch Settings
All functions are set using the DIP switch.
Operation in Run Mode
Forecast Value Setting Absolute Value Setting
Note: 1. All the pins are factory-set to OFF.
2. DIP switch settings are effective when the power is
turned ON again. (Set the DIP switch before installation
and power-up.)
Item OFF ON
1Time range Refer to the table on the
right.
2
3Output modes F-1 mode
A mode
4Input signal width 20 ms 1 ms
5NPN/PNP input mode NPN
(no-voltage)
PNP
(voltage)
6Reset Key protection Disabled Enabled
7Up Key protection Disabled Enabled
8Mode Key protection Disabled Enabled
Pin 1 Pin 2 Time range
OFF OFF 0.1 h to 99999.9 h
ON OFF 0.01 s to 9999.99 s
OFF ON 0 h 00 min 01 s to
99 h 59 min 59 s
ON ON 0.1 min to 99999.9 min
OFF
ON
12345678
Set the digits for the set values using the corresponding Key.
Set value
Present value
Forecast set value
Present value
Each time the Key is pressed,
the sub-display will switch between
the set value (“SET” is lit) and the
forecast set value (“1” is lit).
Set value 1
Present value
Set value 2
Present value
Each time the Key is pressed,
the sub-display will switch between
set value 1 (“SET 1” is lit) and set
value 2 (“SET 2” is lit).
H5CX-B@-N
38
Operation in Function Setting Mode
Run mode
Power ON
Function setting mode
*1. If the mode is switched to the function setting mode during operation, operation will continue.
*2. Changes made to settings in function setting mode are enabled for the first time when the mode is changed to run mode.
Also, when settings are changed, the timer is reset (time initialized and output turned OFF).
3 s min. *2
3 s min. *1
Settings that cannot be performed with the DIP switch are performed with the operation keys.
• Change to Function Setting Mode.
(Absolute
value setting)
(Forecast
value setting)
Absolute
value setting/
forecast value
setting
Set value
upper limit
Output 1
(OUT1)
ON count
alarm set value
Output 2
(OUT2)
ON count
alarm set value
Output 1
(OUT1)
ON count
monitor value
Output 2
(OUT2)
ON count
monitor value
~
Set the digits for the set values using the
corresponding Key.
(9999 x 1000
times)
(0 x 1000
times)
~
Set the digits for the set values using the
corresponding Key.
Note: The monitor value is only displayed. It cannot be set.
Note: Displayed only in forecast setting mode.
~
Function Setting Mode
Set the digits for the set values using the
corresponding Key.
Set the digits for the set values using the
corresponding Key.
(9999 x 1000
times)
(0 x 1000
times)
Note: The monitor value is only displayed. It cannot be set.
Set the digits for the set values using the
corresponding Key.
~
Forecast
setting upper
limit (1) (999999)
~
(1) (999999)
H5CX-B@-N
39
Explanation of Functions
Absolute value setting/forecast value setting
(setm)
Set value 1 can be set as the forecast value setting (ofst) or the
absolute value setting (abs).
Forecast Value Setting
OUT1 (forecast output) turns ON when the present value reaches
the forecast value.
Forecast value = Set value - Forecast set value
Note: The forecast set value is used to set the deviation for the set value.
OUT2 (control output) turns ON when the present value reaches
the set value.
If the forecast set value set value, OUT1 (forecast output) will turn
ON as soon as timing starts.
Absolute Value Setting
OUT1 (control output 1) turns ON when the present value reaches
set value 1.
OUT2 (control output 2) turns ON when the present value reaches
set value 2.
Refer to pages 18 and 28 for information on other functions.
Self-diagnostic Function
The following displays will appear if an error occurs.
*1. This includes times when the life of the EEPROM has expired.
*2. The normal display and e3 will appear alternately.
When the Reset Key is pressed, e3 will no longer be displayed even if the alarm set value is exceeded. (Monitoring is possible, however, because the Timer will
continue without clearing the output ON count.)
Set
value
Forecast
value
Forecast
set value
0
Forecast output
(OUT1)
Control output
(OUT 2)
Present
value
Example: F-1 Mode
Set value 2
Set value 1
0
Control output 1
(OUT1)
Control output 2
(OUT2)
Present
value
Example: F-1 Mode
Main display Sub-display Error Output status Correction method Set value after reset
e1 Not lit CPU OFF Either press the Reset Key or
reset the power supply. No change
e2 Not lit Memory error (RAM) OFF Reset the power supply. No change
e2 sum Memory error EEPROM *1 OFF Reset Key. Factory setting
e3 *2 No change Output ON count alarm set
value exceeded No change Reset Key No change
H5CX-B@-N
40
Timing Charts
Note: 1. The forecast value = set value - forecast set value
2. The forecast set value is used to set the deviation for the set value.
Mode A: Signal ON delay (Timer resets when power comes ON.)
Basic operation Detailed operation
*Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
A sustained control output is used.
Timing stops when the time is up.
Note: Output is instantaneous when the set value is 0. The names in parentheses are used for the absolute value setting.
Mode F-1: Cumulative (Timer does not reset when power comes ON.)
Basic operation Detailed operation
Start signal enables timing (timing is stopped when the
start signal is OFF or when the power is OFF).
A sustained control output is used.
Timing continues even after the time is up.
Note: Output is instantaneous when the set value is
0.
When the H5CX is used with power start in mode F
mode or F-1 (i.e., cumulative operation with output on
hold), there will be a timer error (approximately 100
ms each time the H5CX is turned ON) due to the
characteristics of the internal circuitry. Use the H5CX
with signal start if timer accuracy is required.
The names in parentheses are used for the absolute value setting.
Power
( ) The names in parentheses are used for the absolute value setting.
*
Start signal input
Timing
Forecast
output
OUT1
(
)
Control
output 1
OUT1
Control
output
OUT2
(
)
Control
output 2
OUT2
Set value (SV 2)
Forecast value
(SV 1)
OUT1
999999
0
OUT2
Power
Start signal
Gate
Reset
Timing diagram
Start signal input
Timing Timing
Sustained
Power
Forecast
output
OUT1
(
)
Control
output 1
OUT1
Control
output
OUT2
(
)
Control
output 2
OUT2
( ) The names in parentheses are used for the absolute value settin
g
.
0
Set value (SV 2)
Forecast value
(SV 1)
OUT1
999999
OUT2
Power
Start signal
Gate
Reset
Timing diagram
H5CX-@-N
41
Safety Precautions for All H5CX Series (Common)
Do not allow pieces of metal, wire clippings, or fine
metallic shavings or fillings from installation to enter
the product. Doing so may occasionally result in
electric shock, fire, or malfunction.
Minor injury due to explosion may occasionally occur.
Do not use the Timer where subject to flammable or
explosive gas.
Fire may occasionally occur. Tighten the terminal
screws to the rated torque.
H5CX terminals: 6.55 to 7.97 lb-in (0.74 to 0.90 N m)
P2CF Socket terminals: 4.4 lb-in (0.5 N m)
Minor injury due to electric shock may occasionally
occur. Do not touch any of the terminals while power
is being supplied. Be sure to mount the terminal cover
after wiring.
The life expectancy of the output relay varies
considerably according to its usage. Use the output
relay within its rated load and electrical life
expectancy. If the output relay is used beyond its life
expectancy, its contacts may become fused or there may be a
risk of fire. Also, be sure that the load current does not exceed
the rated load current and when using a heater, be sure to use a
thermal switch in the load circuit.
Minor electric shock, fire, or malfunction may
occasionally occur. Do not disassemble, modify, or
repair the Timer or touch internal components.
The panel surface of the H5CX is water-resistant (conforming to
NEMA4, IP66, UL Type 4X (Indoor Use Only). To protect the
internal circuits from water penetration through the space between
the H5CX and operating panel, waterproof packing is included.
Attach the Y92F-30 Adapter with sufficient pressure with the
reinforcing screws so that water does not penetrate the panel.
When mounting the Timer to a panel, tighten the two mounting
screws alternately, a little at a time, so as to keep them at an equal
tightness. If the panel screws are tightened unequally, water may
enter the panel.
Store the Timer at the specified temperature. If the Time has been
stored at a temperature of less than -10°C, allow the Time to stand
at room temperature for at least 3 hours before use.
Mounting the Timer side-by-side may reduce the life expectancies
of internal components.
Use the Timer within the specified ranges for the ambient operating
temperature and humidity.
Do not use in the following locations:
Locations subject to sudden or extreme changes in
temperature.
Locations where high humidity may result in condensation.
Do not use the Timer outside of the rated ranges for vibration,
shock, water exposure, and oil exposure.
Do not use this Timer in dusty environments, in locations where
corrosive gasses are present, or in locations subject to direct
sunlight.
Install the Timer well away from any sources of static electricity,
such as pipes transporting molding materials, powders, or liquids.
Internal elements may be destroyed if a voltage outside the rated
voltage range is applied.
Be sure that polarity is correct when wiring the terminals.
Separate the Timer from sources of noise, such as devices with
input signals from power lines carrying noise, and wiring for I/O
signals.
Do not connect more than two crimp terminals to the same
terminal.
Up to two wires of the same size and type can be inserted into a
single terminals.
Use the specified wires for wiring. Applicable Wires: AWG 18 to
AWG 22, solid or twisted, copper.
Install a switch or circuit breaker that allows the operator to
immediately turn OFF the power, and label it to clearly indicate its
function.
When the Timer is operated with no-voltage input (NPN input),
approximately 14 V is output from the input terminals. Use a sensor
that contains a diode.
Use a switch, relay, or other contact so that the rated power supply
voltage will be reached within 0.1 seconds. If the power supply
voltage is not reached quickly enough, the Timer may malfunction
or outputs may be unstable.
Use a switch, relay, or other contact to turn the power supply OFF
instantaneously. Outputs may malfunction and memory errors may
occur if the power supply voltage is decreased gradually.
•H5CX-A@-N/-L@-N:
When changing the set value during a timing operation, the output
will turn ON if the set value is changed as follows because of the
use of a constant read-in system:
Elapsed time (UP) mode: Present value Set value
Remaining time (DOWN) mode: Elapsed time Set value (The
present value is set to 0.)
When in the remaining time mode, the amount the set value is
changed is added to or subtracted from the present value.
Operation with a set value of 0 will vary with the output mode. Refer
to the timing charts on page 20.
•H5CX-B@-N:
When changing the set value during a timing operation, the output
will turn ON if the set value is changed as follows because of the
use of a constant read-in system:
1. Forecast Value Setting
When the present value the set value, OUT2 (control output)
turns ON.
When the present value the forecast value (forecast value =
set value - forecast set value), OUT1 (forecast output) turns ON.
2. Absolute Value Setting
When the present value set value 2, OUT2 (control output 2)
turns ON.
When the present value the forecast value (forecast value =
set value - forecast set value), OUT1 (control output 1) turns
ON.
When the set value is 0, the output turns ON the moment the
signal is input. The reset operation turns OFF the output.
Do not use organic solvents (such as paint thinners or benzine),
strong alkali, or strong acids. They will damage the external finish.
Confirm that indications are working normally, including the
backlight LED, and LCD. The indicator LEDs, LCD, and resin parts
may deteriorate more quickly depending on the application
environment, preventing normal indications. Periodic inspection
and replacement are required.
The waterproof packing may deteriorate, shrink, or harden
depending on the application environment. Periodic inspection and
replacement are required.
CAUTION
Precautions for Safe Use
It is recommended that the
space between the screw
head and the Adapter be 0.5
to 1 mm.
0.5 to 1 mm
Input0V
Sensor
Diode
H5CX-@-N
42
H5CX models with a 24-VDC/12 to 24-VDC power supply use a
transformer-free power supply method in which the power supply
terminals are not isolated from the signal input terminals. If a non-
isolating DC power supply is used, unwanted current paths may
occasionally burn or destroy internal components depending on
the wiring. Always check the wiring sufficiently before use.
An inrush current of approx. 10 A will flow for a short time when the
power supply is turned ON. If the capacity of the power supply is
not sufficient, the Timer may not start. Be sure to use a power
supply with sufficient capacity.
Maintain voltage fluctuations in the power supply within the
specified operating voltage range.
When turning the power ON and OFF, input signal reception is
possible, unstable, or impossible as shown in the diagram below.
To allow for the startup time of peripheral devices (sensors, etc.),
the Timer starts timing operation between 200 to 250 ms after
power is turned ON. For this reason, in operations where timing
starts from power ON, the time display will actually start from 249
ms. If the set value is 249 ms or less, the time until output turns ON
will be a fixed value between 200 and 250. The present value
display will start from 250 ms. (Normal operation is possible for set
values of 250 ms or more.) In applications where a set value of 249
ms or less is required, use start timing with signal input.
Inrush current generated by turning ON or OFF the power supply
may deteriorate contacts on the power supply circuit. Turn ON or
OFF to a device with the rated current of more than 10 A.
Make sure that all settings are appropriate for the application.
Unexpected operation resulting in property damage or accidents
may occur if the settings are not appropriate.
Do not leave the Timer for long periods at a high temperature with
output current in the ON state. Doing so may result in the
premature deterioration of internal components (e.g., electrolytic
capacitors).
EEPROM is used as backup memory when the power is
interrupted. The write life of the EEPROM is 100,000 writes.
The EEPROM is written at the following times:
When the power supply is turned OFF
When switching from Timer/Twin Timer Selection Mode or
Function Setting Mode to Run Mode
Dispose of the product according to local ordinances as they apply.
Attach the front panel when using the Timer. The tabs in the middle
of each of four sides secure the front panel to the main body. To
remove the panel, widen the four tabs and pull the panel toward
you. To mount the panel, fit all four tabs correctly into the grooves
on the main body.
When conforming to EMC standards, refer to the information
provided in this datasheet for cable selection and other conditions.
This is a class A product. In residential areas it may cause radio
interference, in which case the user may be required to take
adequate measures to reduce interference.
•H5CX-A@-N/-L@-N:
Basic insulation is provided between the power supply and input
terminals. (No insulation is provided between the power supply and
input terminals for the H5CX-@D-N.)
Basic insulation is provided between power supply and output
terminals, and between input and output terminals.
•H5CX-B@-N:
No insulation is provided between the power supply and input
terminals.
Basic insulation is provided between the power supply and output
terminals.
When double insulation or reinforced insulation is required, apply
double insulation or reinforced insulation as defined in IEC 60664
that is suitable for the maximum operating voltage with clearances
or solid insulation.
Connect the input and output terminals to devices that do not have
any exposed charged parts.
Precautions for Correct Use
Input Impossible
200ms 5ms0 to 50 ms 0 to 500 ms
Possible
Unstable
Unstable Impossible
Power
supply
ON
OFF
Ta bs
Grooves
Conformance to EN/IEC Standards
Terms and Conditions of Sale
1. Offer; Acceptance. These terms and conditions (these "Terms") are deemed
part of all quotes, agreements, purchase orders, acknowledgments, price lists,
catalogs, manuals, brochures and other documents, whether electronic or in
writing, relating to the sale of products or services (collectively, the "Products")
by Omron Electronics LLC and its subsidiary companies (“Omron”). Omron
objects to any terms or conditions proposed in Buyers purchase order or other
documents which are inconsistent with, or in addition to, these Terms.
2. Prices; Payment Terms. All prices stated are current, subject to change with-
out notice by Omron. Omron reserves the right to increase or decrease prices
on any unshipped portions of outstanding orders. Payments for Products are
due net 30 days unless otherwise stated in the invoice.
3. Discounts. Cash discounts, if any, will apply only on the net amount of invoices
sent to Buyer after deducting transportation charges, taxes and duties, and will
be allowed only if (i) the invoice is paid according to Omron’s payment terms
and (ii) Buyer has no past due amounts.
4. Interest. Omron, at its option, may charge Buyer 1-1/2% interest per month or
the maximum legal rate, whichever is less, on any balance not paid within the
stated terms.
5. Orders. Omron will accept no order less than $200 net billing.
6. Governmental Approvals. Buyer shall be responsible for, and shall bear all
costs involved in, obtaining any government approvals required for the impor-
tation or sale of the Products.
7. Taxes. All taxes, duties and other governmental charges (other than general
real property and income taxes), including any interest or penalties thereon,
imposed directly or indirectly on Omron or required to be collected directly or
indirectly by Omron for the manufacture, production, sale, delivery, importa-
tion, consumption or use of the Products sold hereunder (including customs
duties and sales, excise, use, turnover and license taxes) shall be charged to
and remitted by Buyer to Omron.
8. Financial. If the financial position of Buyer at any time becomes unsatisfactory
to Omron, Omron reserves the right to stop shipments or require satisfactory
security or payment in advance. If Buyer fails to make payment or otherwise
comply with these Terms or any related agreement, Omron may (without liabil-
ity and in addition to other remedies) cancel any unshipped portion of Prod-
ucts sold hereunder and stop any Products in transit until Buyer pays all
amounts, including amounts payable hereunder, whether or not then due,
which are owing to it by Buyer. Buyer shall in any event remain liable for all
unpaid accounts.
9. Cancellation; Etc. Orders are not subject to rescheduling or cancellation
unless Buyer indemnifies Omron against all related costs or expenses.
10. Force Majeure. Omron shall not be liable for any delay or failure in delivery
resulting from causes beyond its control, including earthquakes, fires, floods,
strikes or other labor disputes, shortage of labor or materials, accidents to
machinery, acts of sabotage, riots, delay in or lack of transportation or the
requirements of any government authority.
11. Shipping; Delivery. Unless otherwise expressly agreed in writing by Omron:
a. Shipments shall be by a carrier selected by Omron; Omron will not drop ship
except in “break down” situations.
b. Such carrier shall act as the agent of Buyer and delivery to such carrier shall
constitute delivery to Buyer;
c. All sales and shipments of Products shall be FOB shipping point (unless oth-
erwise stated in writing by Omron), at which point title and risk of loss shall
pass from Omron to Buyer; provided that Omron shall retain a security inter-
est in the Products until the full purchase price is paid;
d. Delivery and shipping dates are estimates only; and
e. Omron will package Products as it deems proper for protection against nor-
mal handling and extra charges apply to special conditions.
12. Claims. Any claim by Buyer against Omron for shortage or damage to the
Products occurring before delivery to the carrier must be presented in writing
to Omron within 30 days of receipt of shipment and include the original trans-
portation bill signed by the carrier noting that the carrier received the Products
from Omron in the condition claimed.
13. Warranties. (a) Exclusive Warranty. Omron’s exclusive warranty is that the
Products will be free from defects in materials and workmanship for a period of
twelve months from the date of sale by Omron (or such other period expressed
in writing by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION,
EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL-
ITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS.
BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. Omron further disclaims all warranties and responsibility of
any type for claims or expenses based on infringement by the Products or oth-
erwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obli-
gation hereunder shall be, at Omron’s election, to (i) replace (in the form
originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying
Product, or (iii) repay or credit Buyer an amount equal to the purchase price of
the non-complying Product; provided that in no event shall Omron be responsi-
ble for warranty, repair, indemnity or any other claims or expenses regarding
the Products unless Omron’s analysis confirms that the Products were prop-
erly handled, stored, installed and maintained and not subject to contamina-
tion, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Compa-
nies shall not be liable for the suitability or unsuitability or the results from the
use of Products in combination with any electrical or electronic components,
circuits, system assemblies or any other materials or substances or environ-
ments. Any advice, recommendations or information given orally or in writing,
are not to be construed as an amendment or addition to the above warranty.
See http://www.omron247.com or contact your Omron representative for pub-
lished information.
14. Limitation on Liability; Etc. OMRON COMPANIES SHALL NOT BE LIABLE
FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY
WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS
BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual
price of the Product on which liability is asserted.
15. Indemnities. Buyer shall indemnify and hold harmless Omron Companies and
their employees from and against all liabilities, losses, claims, costs and
expenses (including attorney's fees and expenses) related to any claim, inves-
tigation, litigation or proceeding (whether or not Omron is a party) which arises
or is alleged to arise from Buyer's acts or omissions under these Terms or in
any way with respect to the Products. Without limiting the foregoing, Buyer (at
its own expense) shall indemnify and hold harmless Omron and defend or set-
tle any action brought against such Companies to the extent based on a claim
that any Product made to Buyer specifications infringed intellectual property
rights of another party.
16. Property; Confidentiality. Any intellectual property in the Products is the exclu-
sive property of Omron Companies and Buyer shall not attempt to duplicate it
in any way without the written permission of Omron. Notwithstanding any
charges to Buyer for engineering or tooling, all engineering and tooling shall
remain the exclusive property of Omron. All information and materials supplied
by Omron to Buyer relating to the Products are confidential and proprietary,
and Buyer shall limit distribution thereof to its trusted employees and strictly
prevent disclosure to any third party.
17. Export Controls. Buyer shall comply with all applicable laws, regulations and
licenses regarding (i) export of products or information; (iii) sale of products to
“forbidden” or other proscribed persons; and (ii) disclosure to non-citizens of
regulated technology or information.
18. Miscellaneous. (a) Waiver. No failure or delay by Omron in exercising any right
and no course of dealing between Buyer and Omron shall operate as a waiver
of rights by Omron. (b) Assignment. Buyer may not assign its rights hereunder
without Omron's written consent. (c) Law. These Terms are governed by the
law of the jurisdiction of the home office of the Omron company from which
Buyer is purchasing the Products (without regard to conflict of law princi-
ples). (d) Amendment. These Terms constitute the entire agreement between
Buyer and Omron relating to the Products, and no provision may be changed
or waived unless in writing signed by the parties. (e) Severability
. If any provi-
sion hereof is rendered ineffective or invalid, such provision shall not invalidate
any other provision. (f) Setoff. Buyer shall have no right to set off any amounts
against the amount owing in respect of this invoice. (g) Definitions. As used
herein, “includingmeans “including without limitation”; and “Omron Compa-
nies” (or similar words) mean Omron Corporation and any direct or indirect
subsidiary or affiliate thereof.
Certain Precautions on Specifications and Use
1. Suitability of Use. Omron Companies shall not be responsible for conformity
with any standards, codes or regulations which apply to the combination of the
Product in the Buyers application or use of the Product. At Buyer’s request,
Omron will provide applicable third party certification documents identifying
ratings and limitations of use which apply to the Product. This information by
itself is not sufficient for a complete determination of the suitability of the Prod-
uct in combination with the end product, machine, system, or other application
or use. Buyer shall be solely responsible for determining appropriateness of
the particular Product with respect to Buyer’s application, product or system.
Buyer shall take application responsibility in all cases but the following is a
non-exhaustive list of applications for which particular attention must be given:
(i) Outdoor use, uses involving potential chemical contamination or electrical
interference, or conditions or uses not described in this document.
(ii) Use in consumer products or any use in significant quantities.
(iii) Energy control systems, combustion systems, railroad systems, aviation
systems, medical equipment, amusement machines, vehicles, safety equip-
ment, and installations subject to separate industry or government regulations.
(iv) Systems, machines and equipment that could present a risk to life or prop-
erty. Please know and observe all prohibitions of use applicable to this Prod-
uct.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS
RISK TO LIFE OR PROPERTY OR IN LARGE QUANTITIES WITHOUT
ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO
ADDRESS THE RISKS, AND THAT THE OMRON’S PRODUCT IS PROP-
ERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
2. Programmable Products. Omron Companies shall not be responsible for the
user’s programming of a programmable Product, or any consequence thereof.
3. Performance Data. Data presented in Omron Company websites, catalogs
and other materials is provided as a guide for the user in determining suitabil-
ity and does not constitute a warranty. It may represent the result of Omron’s
test conditions, and the user must correlate it to actual application require-
ments. Actual performance is subject to the Omron’s Warranty and Limitations
of Liability.
4. Change in Specifications. Product specifications and accessories may be
changed at any time based on improvements and other reasons. It is our prac-
tice to change part numbers when published ratings or features are changed,
or when significant construction changes are made. However, some specifica-
tions of the Product may be changed without any notice. When in doubt, spe-
cial part numbers may be assigned to fix or establish key specifications for
your application. Please consult with your Omron’s representative at any time
to confirm actual specifications of purchased Product.
5. Errors and Omissions. Information presented by Omron Companies has been
checked and is believed to be accurate; however, no responsibility is assumed
for clerical, typographical or proofreading errors or omissions.
Note: Specifications are subject to change. © 2008 Omron Electronics LLC Printed in U.S.A.
OMRON ELECTRONICS LLC
THE AMERICAS HEADQUARTERS
Schaumburg, IL USA • 847.843.7900 • 800.556.6766 • www.omron247.com
OMRON CANADA, INC. • HEAD OFFICE
Toronto, ON, Canada • 416.286.6465 • 866.986.6766 • www.omron.ca
OMRON ELETRÔNICA DO BRASIL LTDA • HEAD OFFICE
São Paulo, SP, Brasil 55.11.2101.6300 • www.omron.com.br
OMRON ELECTRONICS MEXICO SA DE CV • HEAD OFFICE
Apodaca, N.L. • 52.811.156.99.10 • mela@omron.com
OMRON ARGENTINA • SALES OFFICE
Cono Sur • 54.11.4787.1129
OMRON CHILE • SALES OFFICE
Santiago 56.2206.4592
OTHER OMRON LATIN AMERICA SALES
56.2206.4592
L111-E1-01 7/09
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron:
H5CX-A-N AC100-240 H5CX-A11-N AC100-240 H5CX-ASD-N-DC12-24/AC24 H5CX-L8D-N DC12-24/AC24 H5CX-
AD-N AC24/DC12-24 H5CX-L8-N AC100-240 H5CX-A11SD-N DC12-24/AC24 H5CX-L8ED-N DC12-24/AC24 H5CX-
L8S-N AC100-240 H5CX-A11D-N DC12-24/AC24 H5CX-AS-N AC100-240 H5CX-L8SD-N DC12-24/AC24 H5CX-L8D-
N AC12-24/AC24 H5CX-BWSD-N DC12-24 H5CX-L8E-N AC100-240 H5CX-A11S-N AC100-240 H5CX-A-AC100-240
H5CX-A AC100-240 CALIBRATED H5CX-AD-AC24/DC12-24 H5CX-L8-AC100-240 H5CX-A11-AC100-240 H5CX-
A11D-AC24/DC12-24