Compact and complete
JX INVERTER
» Cost and eco-friendly
» Communications built-in
» Quality & reliability you can depend on
The smallest gets integrated...
Omron fully understands your needs, which
is why we put quality and reliability first.
And we keep listening, so our products come
with new features and functionality that save
you time and money.
With the RFI filter built-in, and the
communications integrated as standard, the
JX provides a compact and complete solution
to a whole range of simple applications, such
as conveyor control.
Key features include:
Ratings up to . kW
RS Modbus built-in
Side-by-side mounting
EMC filter built-in
PID function
Micro-surge voltage suppression
Automatic energy saving
Emergency shut-off
Second motor setting
Auto carrier-frequency reduction
PTC thermistor input
Cooling fan switch control
RoHS
1
2
Easy network integration
The RS485 Modbus is built into the
RJ45 port in the inverter front,
making it very easy to add inverters
into the network without any extra
option boards. Therefore, saving
money and space.
Easy communications setting
Modbus commands are implemented
even in low end CP1 PLC family by
Modbus-RTU Easy Master
functionality, making it easier than
ever to integrate the inverters into
the network.
Space and cost saving
The new JX has a built-in EMC filter
that saves on costs and space
compared with the standard
external filter solution.
1 ph : EN61800-3 cat. C1
3 ph : EN61800-3 cat. C2
120
110
100
90
80
70
60
50
40
30
20
10
0
Frequency (Hz)
Level (dBV)
Conducted emission data
Integrated EMC filter
No Filter
500k 1M 2M 5M 10M 20M 30M200150
OMRON Function Block for Pulse Output Positioning.
OMRON Function Block for Communications.
Sensor?
3 54
5
3
6
No additional devices required
Even advanced functionality such as
PID control is standard with the JX
inverter making it a convenient
solution for applications such as
pumps & fans where pressure, flow
and other processes need
controlling.
Reliable emergency shutdown
The IGBT’s output is directly
switched off from the external input,
assuring no energy is supplied to the
motor. This hardware-based solution
is more reliable than other CPU
dependent solutions.
Convenient and efficient
The parameter settings of two
different motors can be stored,
allowing the inverter to drive
different motors with a unique
inverter. The two motors are never
working at the same time.
for your application
Everything on-board
Heating section
Motor
Sensor
Emergency stop switch
IGBT gate
Power supply
circuit
Set
Reset
24 V
Latch
Interruption 0 V
PCS
RS
EMR
M
~
3
W
A
R
R
A
N
T
Y
Y
E
E
A
A
R
R
S
S
4
6
Automatic energy saving
The Inverter always adopts the
optimum energy-saving setting for
cost savings in such applications as
fans and pumps. The inverter can
reduce energy consumption by
61% compared with standard
mechanical systems.
Reliability with environmental responsibility
Omron is renowned for the reliability of its products.
Moreover, Omron’s policy is to offer environmentally
safe products free from any banned substances.
Silent operation
Depending on the inverter
temperature, switching off the fan
creates a noise-free atmosphere and
prolongs the life time of the product.
Maximise motor life
Advanced PWM control is used to
suppress micro-surge voltages that
sometimes cause malfunction in
400 V motors. The motor is thus
protected and its life is prolonged.
90
80
70
60
50
40
30
20
10
0
Power (%)
1,250 V
76%
91%
61%
22%
Damper system
Energy-saving effect
Inverter system
Airflow (%)
10 20 30 40 50 60 70 80 90 100
Spikes in the terminal voltage are suppressed even when
the wiring distance from the inverter to the motor is long
6Frequency inverters
JX
Compact & Complete
V/f controlled inverter
Side by side mounting
Built-in EMC filter
Built-in RS-485 Modbus
Overload detection function (150% during 60s)
•PID
Micro-surge voltage suppression
Automatic energy saving
Emergency shut-off
Second motor setting
Auto carrier-frequency reduction
PTC thermistor input
Cooling fan switch control
PC configuration tool: CX-Drive
CE, UL, cUL, RoHS
Ratings
200 V Class single-phase 0.2 to 2.2 kW
200 V Class three-phase 0.2 to 7.5 kW
400 V Class three-phase 0.4 to 7.5 kW
System configuration
Choke
LCD 5 lines remote
operator
Remote operator
extension cable
* Only needed for 3 phase 200 V or to comply C1 on 3 phase 400 V models
Output reactor
RJ45 - USB cable
CX-Drive
CX-One
*
MCCB
JX
Filter
AC reactor
Motor
Ground
Power
supply
DC reactor
JX 7
Type designation
200 V class
400 V class
Specifications
Single-phase: 3G3JX@AB002 AB004 AB007 AB015 AB022 - - -
Three-phase: 3G3JX@A2002 A2004 A2007 A2015 A2022 A2037 A2055 A2075
Motor
kW*1
*1Based on a standard 3-Phase standard motor.
Applicable motor capacity 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5
Output
characteristics
Inverter capacity kVA 200 V 0.4 0.9 1.32.4 3.4 5.5 8.311.0
240 V 0.5 1.0 1.6 2.9 4.1 6.6 9.9 13.3
Rated output current (A) 1.4 2.6 4.0 7.1 10.0 15.9 24.0 32.0
Max. output voltage Proportional to input voltage: 0…240 V
Max. output frequency 400 Hz
Power
supply
Rated input voltage
and frequency
Single-phase 200…240 V 50/60 Hz
3-phase 200…240 V 50/60 Hz
Rated input current (A) Three-phase 200 V 1.8 3.4 5.2 9.313.0 20.0 30.0 40.0
Rated input current (A) Single-phase 200 V 3.1 5.8 9.0 16.0 22.5 –––
Allowable voltage
fluctuation -15%…+10%
Allowable frequency
fluctuation +5%
Built-in filter EMC filter (C1 single phase)
Braking torque
At short-time
deceleration
At capacitor
feedback
Approx. 50%
50% for
3-phase
20 to 40% for
1-phase
Approx 20% to 40% Approx 20%
Cooling method Self cooling Forced-air-cooling
Three-phase: 3G3JX@A4004 A4007 A4015 A4022 A4040 A4055 A4075
Motor
kW*1
*1Based on a standard 3-Phase standard motor.
Applicable motor capacity 0.4 0.75 1.5 2.2 4.0 5.5 7.5
Output
characteristics
Inverter capacity kVA 380 V 0.9 1.6 2.5 3.6 5.6 8.5 10.5
480 V 1.2 2.0 3.1 4.5 7.1 10.8 13.3
Rated output current (A) 1.5 2.5 3.8 5.5 8.6 13.0 16.0
Max. output voltage Proportional to input voltage: 0…480 V
Max. output frequency 400 Hz
Power
supply
Rated input voltage
and frequency 3-phase 380…480 V 50/60 Hz
Rated input current (A) 2.0 3.35.0 7.0 11.0 16.5 20.0
Allowable voltage
fluctuation -15%…+10%
Allowable frequency
fluctuation +5%
Built-in filter EMC filter C2 class
Braking torque
At short-time
deceleration
At capacitor
feedback
Approx. 50% Approx. 20% to 40% Approx. 20%
Cooling method Self cooling Forced-air-cooling
JX series
A: Standard specs
3G3JX-AB002-EF
Voltage:
B: Single-phase 200 VAC
2: Three-phase 200 VAC
4: Three-phase 400 VAC
Max. applicable motor output
002: 0,2 kW
~
075: 7,5 kW
F: Built-in EMC Filter
E: Europe standard
8Frequency inverters
Common specifications
Specifications
Model number
3G3JX@Specifications
Control functions
Control methods Phase-to-phase sinusoidal modulation PWM (V/f)
Output frequency range 0.5..400 Hz
Frequency precision Digital set value: ±0.01% of the max. frequency
Analogue set value: ±0.4% of the max. frequency (25 ±10 ºC)
Resolution of frequency set value Digital set value: 0.1 Hz
Analogue set value: 1/1000 of maximum frequency
Resolution of output frequency 0.1 Hz
Overload capability 150% rated output current for one minute
Frequency set value 0 to 10 VDC (10 k), 4 to 20 mA (250 ), frequency setting volume (selectable), RS485 Modbus
V/f Characteristics Constant/ reduced torque
Functionality
Inputs signals
FW (forward), RV (reverse), CF1 to CF4 (multi-step speed), JG (jogging), DB (external DC injection braking), SET (2nd func-
tion), 2CH (2-step acceleration/deceleration), FRS (free run), EXT (external trip), USP (USP function), SFT (soft lock), AT
(analog current input function selection), RS (reset), PTC (thermistor input), STA (3-wire startup), STP (3-wire stop), F/R (3-
wire forward/reverse), PID (PID selection), PIDC (PID integral reset), UP (UP of UP/DWN function), DWN (DWN of UP/DWN
function), UDC (data clear of UP/DWN function), OPE (forced OPE mode), ADD (frequency addition), F-TM (forced terminal
block), RDY (operation ready), SP-SET (special setting), EMR (emergency shutoff)
Output signals
RUN (signal during operation), FA1 (frequency arrival signal 1), FA2 (frequency arrival signal 2), OL (overload warning sig-
nal), OD (PID excess deviation signal), AL (alarm signal), DC (analog input disconnection detection signal), FBV (PID FB
status output), NDc (network error), LOG (logical operation result), ODc (communication option disconnected), LOC (light
load signal)
Standard functions
AVR function, V/f characteristic selection, upper/lower limit, 16-step speeds, starting frequency adjustment, jogging
operation, carrier frequency adjustment, PID control, frequency jump, analog gain/bias adjustment, S-shape acceleration/
deceleration, electronic thermal characteristics/level adjustment, retry function, simplified torque boost, trip monitor, soft lock
function, frequency conversion display, USP function, 2nd control function, motor rotation speed UP/DOWN, overcurrent
suppression function
Analogue inputs 2 analogue inputs 0 to 10 V (20 k), 4 to 20 mA (250 )
Accel/Decel times 0.01 to 3000 s (line/curve selection), 2nd accel/decel setting available
Display Status indicator LED’s Run, Program, Power, Alarm, Power, Hz, Amps, Volume Led indicator
Digital operator: Available to monitor frequency reference, output current, output frequency
Protection functions
Motor overload protection Electronic Thermal overload relay and PTC thermistor input
Instantaneous overcurrent 180% of rated current
Overload 150% for 1 minute
Overvoltage 790 V for 400 V type and 395 for 200 V type
Momentary power loss Following items are selectable: Alarm, 0 Hz start, frequency output at interruption, maximum frequency
Cooling fin overheat Temperature monitor and error detection
Stall prevention level Selectable level applicable only at constant speed or during acceleration and constant speed
Ground fault Detected at power-on
Power charge indication On when power is supplied to the control part
Ambient conditions
Degree of protection IP20
Ambient humidity 90% RH or less (without condensation)
Storage temperature -20ºC..+65 ºC (short-term temperature during transportation)
Ambient temperature 10C to 50C (Both the carrier frequency and output current need to be reduced at over 40C.)
Installation Indoor (no corrosive gas, dust, etc.)
Installation height Max. 1000 m
Vibration 5.9 m/s2 (0.6 G), 10 to 55 Hz (Complies with the test method specified in JIS C0040 (1999).)
JX 9
IP 20 type 0.2 to 7.5 kW
Rasmi footprint Filters
Filter only needed by the 1-phase 200 V or 3-phase 400 V to comply with C1 EMC class.
Dimensions
Voltage class Max. applicable
motor output kW
Inverter model
3G3JX@Figure Dimensions in mm
W1 H1 W H D t1 D1 Weight
Single-phase
200 V
0.2 AB002 1 67 14380 155 95.5
2.6
130.8
0.4 AB004 1109.5 27 0.9
0.75 AB007 2
98 176 110 189
130.5 28 1.5
1.5 AB015 2 157.5 6 55 2.3
2.2 AB022 2 2.4
Three-phase
200 V
0.2 A2002 1
67 14380 155
95.5
2.6
130.8
0.4 A2004 1 109.5 27 0.9
0.75 A2007 1 132.5 50 1.1
1.5 A2015 2
98 176 110 189 157.5 6 55
2.2
2.2 A2022 2 2.4
3.7 A20372
5.5 A2055 2 164 235 180 250 167.5 1.6 77.5 4.2
7.5 A2075 2
Three-phase
400 V
0.4 A4004 2
98 176 110 189
130.5 2.6 28 1.5
0.75 A4007 2
157.5 6 55
2.3
1.5 A4015 2
2.42.2 A4022 2
4.0 A4040 2
5.5 A4055 2 164 235 180 250 167.5 1.6 77.5 4.2
7.5 A4075 2
Figure 1 Figure 2
6
5
5
W
H1
W1
H
t1
D1
1.9 D
H1
5
H
W1
W
5
6
t1
D1
D
1.9
Rasmi model Dimensions Weight
kg
W H L X Y M
1x200 V
AX-FIJ1006-RE 81 40 19318357 M4 0.5
AX-FIJ1010-RE 112 47 226 216 88 M4 0.6
AX-FIJ1026-RE 112 47 226 216 88 M4 0.8
3x200 V
AX-FIJ2006-RE 81 50 19318357 M4 1.0
AX-FIJ2020-RE 112 50 226 216 88 M4 1.3
AX-FIJ2040-RE 182 55 289 279 150 M5 2.3
3x400 V
AX-FIJ3005-RE 112 45 226 216 88 M4 0.9
AX-FIJ3011-RE 112 45 226 216 88 M4 1.1
AX-FIJ3020-RE 182 45 289 279 150 M4 1.7
10 Frequency inverters
Input AC Reactor
DC Reactor
Output AC Reactor
Chokes
Voltage Reference Dimensions Weight
kg
AB2 C2 D E F
200 V
AX-RAI02800080-DE 120 70 120 80 52 5.5 1.78
AX-RAI00880175-DE 120 80 120 80 62 5.5 2.35
AX-RAI00350335-DE 180 85 190 140 55 6 5.5
400 V
AX-RAI07700042-DE 120 70 120 80 52 5.5 1.78
AX-RAI03500090-DE 120 80 120 80 62 5.5 2.35
AX-RAI01300170-DE 120 80 120 80 62 5.5 2.50
Voltage Reference Dimensions Weight
kg
A B C D E F G H
200 V
AX-RC21400016-DE
84 113
96
101 66 5 7.5 2
1.22
AX-RC10700032-DE
AX-RC06750061-DE 105 1.60
AX-RC03510093-DE
AX-RC02510138-DE 116 1.95
AX-RC01600223-DE 108 135 124 120 82 6.5
9.5
9.5 3.20
AX-RC01110309-DE 120 152 13613594 7 - 5.20
AX-RC00840437-DE 146 6.00
400 V
AX-RC43000020-DE
84 113
96
101 66 5 7.5 2
1.22
AX-RC27000030-DE 105 1.60
AX-RC14000047-DE
AX-RC10100069-DE 116 1.95
AX-RC06400116-DE 108 135133 120 82 6.5
9.5
9.5 3.70
AX-RC04410167-DE 120 152 13613594 7 - 5.20
AX-RC03350219-DE 146 6.00
Voltage Reference Dimensions Weight
kg
AB2 C2 D E F
200 V
AX-RAO11500026-DE 120 70 120 80 52 5.5 1.78
AX-RAO07600042-DE 120 70 120 80 52 5.5 1.78
AX-RAO04100075-DE 120 80 120 80 62 5.5 2.35
AX-RAO03000105-DE 120 80 120 80 62 5.5 2.35
AX-RAO01830180-DE 180 85 190 140 55 6 5.5
AX-RAO01150220-DE 180 85 190 140 55 6 5.5
AX-RAO00950320-DE 180 85 205 140 55 6 6.5
400 V
AX-RAO16300038-DE 120 70 120 80 52 5.5 1.78
AX-RAO11800053-DE 120 80 120 80 52 5.5 2.35
AX-RAO07300080-DE 120 80 120 80 62 5.5 2.35
AX-RAO04600110-DE 180 85 190 140 55 6 5.5
AX-RAO03600160-DE 180 85 205 140 55 6 6.5
X
H
YW
Ø
m
L
Ø
d
Reference D
diameter
Motor
KW
Dimensions Weight
kg
L W H X Y m
AX-FER2102-RE 21 < 2.2 85 22 46 70 - 5 0.1
AX-FER2515-RE 25 < 15 105 25 62 90 - 5 0.2
JX 11
Standard connections
Terminal Block Specifications
Installation
Terminal Name Function (signal level)
R/L1, S/L2, T/N/L3
Main circuit power supply input Used to connect line power to the drive.
Drives with single-phase 200 V input power use only terminals R/L1 and N (T/L3), terminal
S/L2 is not available for these units
U/T1, V/T2, W/T3 Inverter output Used to connect the motor
PD/+1, P/+ External DC reactor terminal Normally connected by the short-circuit bar. Remove the short-circuit bar between +1 and
P/+2 when a DC reactor is connected.
P/+, N/- DC bus terminal -
Grounding For grounding (grounding should conform to the local grounding code.)
Inverter
R (L1)
S (L2)
T/N (L3)
PCS
P24
U/T1
V/T2
W/T3
Motor
Note:
To connect the DC reactor,
remove the short-circuit bar.
For Source logic
5
4
4.7 k
3
2
1
L
PD/+1
DC reactor
P/+
N/-
11
24 VDC
CM2
10 k
250
10 VDC
L
OI
O
H
AM
Frequency
meter
Frequency
setting unit
1 to 2 k
Power supply input
4 to 20 mA DC
Relay output
Common
AL1
AL2
AL0
RY
3-phase 200 VAC
1-phase 200 VAC
3-phase 400 VAC
12 Frequency inverters
Control Circuit
Side by side mounting
Type No. Signal name Function Signal level
Digital
input
signals
PCS Input power supply
External power supply terminal for input signal (input)
...At sink logic
Internal power supply output terminal for input signal (output)
...At source logic
24 VDC ±10%
P24 Internal 24 VDC 24 VDC internal power supply 24 VDC±10% 100 mA
1Multi-function Input selection 1 Factory setting: Forward/ Stop
2Multi-function Input selection 2 Factory setting: Reverse/ Stop
3Multi-function Input selection 3Factory setting: Fault reset
4Multi-function Input selection 4 Factory setting: Emergency stop fault
5Multi-function Input selection 5 Factory setting: Multi-step speed reference 1
LMulti-function Input selection common -- --
Analog input
signal
HFrequency reference power supply 10 VDC 10 mA max
OVoltage frequency reference signal 0 to 10 VDC (10 K)
OI Current frequency reference signal 4 to 20 mA (250 )
LFrequency reference common --
Digital output
signals
AL2 NC output Factory default relay settings
Under normal operation: AL2-AL0 Closed
Under abnormal operation or power shutdown: AL1-AL0 Open
250 VAC 2.5 A
30VDC 3A
AL1 NO output 250 VAC 1 A
30VDC 1A
AL0 Relay Output common
11 Multi-function output terminal Factory setting: Frequency arrival signal at a constant speed 27 VDC
50 mA max
CM2 Output signal common --
Monitor
Signal
AM Analog frequency monitor/Analog output
current monitor Factory setting: Analog frequency monitor 0 to 10 VDC 1 mA
JX 13
Input AC Reactor
DC Reactor
Output AC Reactor
3 phase 200 V class 400 V class
Max. applicable
motor output kW Reference Current value
A
Inductance
mH
Max. applicable
motor output kW Reference Current value
A
Inductance
mH
0.1 to 1.5 AX-RAI02800080-DE 8.0 2.8 0.4 to 1.5 AX-RAI07700042-DE 4.2 7.7
2.2 to 3.7 AX-RAI00880175-DE 17.5 0.88 2.2 to 4.0 AX-RAI03500090-DE 9.0 3.5
5.5 to 7.5 AX-RAI00350335-DE 33.5 0.35 5.5 to 7.5 AX-RAI01300170-DE 17.0 1.3
200 V class 400 V class
Max. applicable
motor output kW Reference Current value
A
Inductance
mH
Max. applicable
motor output kW Reference Current value
A
Inductance
mH
0.2 AX-RC21400016-DE 1.6 21.4 -
0.4 AX-RC10700032-DE 3.2 10.7 0.4 AX-RC43000020-DE 2.0 43.0
0.7 AX-RC06750061-DE 6.1 6.75 0.7 AX-RC27000030-DE 3.0 27.0
1.5 AX-RC03510093-DE 9.33.51 1.5 AX-RC14000047-DE 4.7 14.0
2.2 AX-RC02510138-DE 13.8 2.51 2.2 AX-RC10100069-DE 6.9 10.1
3.7 AX-RC01600223-DE 22.31.60 4.0 AX-RC06400116-DE 11.6 6.40
5.5 AX-RC01110309-DE 30.9 1.11 5.5 AX-RC04410167-DE 16.7 4.41
7.5 AX-RC00840437-DE 43.7 0.84 7.5 AX-RC03350219-DE 21.9 3.35
200 V class 400 V class
Max. applicable
motor output kW Reference Current value
A
Inductance
mH
Max. applicable
motor output kW Reference Current value
A
Inductance
mH
0.1 to 0.4 AX-RAO11500026-DE 2.6 11.50 0.4 to 1.5 AX-RAO16300038-DE 3.8 16.30
0.75 AX-RAO07600042-DE 4.2 7.60 2.2 AX-RAO11800053-DE 5.311.80
1.5 AX-RAO04100075-DE 7.5 4.10 4.0 AX-RAO07300080-DE 8.0 7.30
2.2 AX-RAO03000105-DE 10.5 3.00 5.5 AX-RAO04600110-DE 11.0 4.60
3.7 AX-RAO01830160-DE 16.0 1.837.5 AX-RAO03600160-DE 16.0 3.60
5.5 AX-RAO01150220-DE 22.0 1.15 -
7.5 AX-RAO00950320-DE 32.0 0.95
MCCB
Power supply
AC reactor JX
R/L1U
V
W
X
Y
Z
S/L2
T/L3
Power
supply
JX
DC reactor
R/L1
+1 P/+2
MCCB
S/L2
T/L3
14 Frequency inverters
3G3JX
Ordering information
Specifications Model
Voltage class Max. applicable motor output kW Rated output current (A) Standard
Single-phase 200 V
0.2 1.4 3G3JX-AB002-EF
0.4 2.6 3G3JX-AB004-EF
0.75 4 3G3JX-AB007-EF
1.5 7.1 3G3JX-AB015-EF
2.2 10 3G3JX-AB022-EF
Three-phase 200 V
0.2 1.4 3G3JX-A2002-E
0.4 2.6 3G3JX-A2004-E
0.75 4 3G3JX-A2007-E
1.5 7.1 3G3JX-A2015-E
2.2 10 3G3JX-A2022-E
3.7 15.9 3G3JX-A2037-E
5.5 24 3G3JX-A2055-E
7.5 323G3JX-A2075-E
Three-phase
400 V
0.4 1.5 3G3JX-A4004-EF
0.75 2.5 3G3JX-A4007-EF
1.5 3.8 3G3JX-A4015-EF
2.2 5.5 3G3JX-A4022-EF
4.0 8.6 3G3JX-A4040-EF
5.5 133G3JXA4055-EF
7.5 16 3G3JXA4075-EF
Choke
A
BB
LCD 5 lines remote
operator
Remote operator
extension cable
A
A
CC C C
A
Output reactor
BD
A
USB cable CX-Drive
CX-One
MCCB
JX
Filter
AC reactor
Motor
Ground
Power
supply
DC reactor
* Only needed for 3 phase 200 V or to comply C1 on 3 phase 400 V models
*
JX 15
A Line filters
A Input AC Reactors
A DC Reactors
A Chokes
A Output AC Reactors
B Accessories
D Computer software
Inverter Line filter Rasmi
Voltage Model 3G3JX-@Reference Rated current (A) Weight (kg)
1-Phase 200 VAC
AB002 / AB004 AX-FIJ1006-RE 6 0.5
AB007 AX-FIJ1010-RE 10 0.6
AB015 / AB022 AX-FIJ1026-RE 26 0.8
3-Phase 200 VAC
A2002 / A2004 / A2007 AX-FIJ2006-RE 6 1.0
A2015 / A2022 / A2037AX-FIJ2020-RE 20 1.3
A2055 / A2075 AX-FIJ2040-RE 40 2.3
3-Phase 400 VAC
A4004 / A4007 /A4015 AX-FIJ3005-RE 5 0.9
A4022 /A4040 AX-FIJ3011-RE 11 1.1
A4055 / A4075 AX-FIJ3020-RE 20 1.7
Inverter AC Reactor
Voltage Model 3G3JX-@Reference
3-Phase 200 VAC
A2002 / A2004 / A2007 AX-RAI02800080-DE
A2015 / A2022 / A2037AX-RAI00880175-DE
A2055 / A2075 AX-RAI00350335-DE
1-Phase 200 VAC
AB002 / AB004
Under developmentAB007
AB015 / AB022
3-Phase 400 VAC
A4004 / A4007 / A4015 AX-RAI07700042-DE
A4022 / A4040 AX-RAI03500090-DE
A4055 / A4075 AX-RAI01300170-DE
200V single phase 200V 3-phase 400V 3-phase
Inverter DC Reactor Inverter DC Reactor Inverter DC Reactor
3G3JX-AB002 AX-RC10700032-DE 3G3JX-A2002 AX-RC21400016-DE -
3G3JX-AB004 AX-RC06750061-DE 3G3JX-A2004 AX-RC10700032-DE 3G3JX-A4004 AX-RC43000020-DE
3G3JX-AB007 AX-RC03510093-DE 3G3JX-A2007 AX-RC06750061-DE 3G3JX-A4007 AX-RC27000030-DE
3G3JX-AB015 AX-RC02510138-DE 3G3JX-A2015 AX-RC03510093-DE 3G3JX-A4015 AX-RC14000047-DE
3G3JX-AB022 AX-RC01600223-DE 3G3JX-A2022 AX-RC02510138-DE 3G3JX-A4022 AX-RC10100069-DE
-
3G3JX-A2037 AX-RC01600223-DE 3G3JX-A4040 AX-RC06400116-DE
3G3JX-A2055 AX-RC01110309-DE 3G3JX-A4055 AX-RC04410167-DE
3G3JX-A2075 AX-RC00840437-DE 3G3JX-A4075 AX-RC03350219-DE
Model Diameter Description
AX-FER2102-RE 21 For 2.2 KW motors or below
AX-FER2515-RE 25 For 7.5 KW motors or below
Inverter AC Reactor
Voltage Model 3G3JX-@Reference
200 VAC
A2001 / A2002 / A2004
AB001 / AB002 / AB004 AX-RAO11500026-DE
A2007/AB007 AX-RAO07600042-DE
A2015 / AB015 AX-RAO04100075-DE
A2022 / AB022 AX-RAO03000105-DE
A2037AX-RAO01830160-DE
A2055 AX-RAO01150220-DE
A2075 AX-RAO00950320-DE
400 VAC
A4004 / A4007 / A4015 AX-RAO16300038-DE
A4022 AX-RAO11800053-DE
A4040 AX-RAO07300080-DE
A4055 AX-RAO04600110-DE
A4075 AX-RAO03600160-DE
Types Model Description Functions
Digital
operator
AX-OP05-E LCD remote
operator
5 Line LCD remote operator
with copy function,
cable length max. 3m.*1
*1Please note, for 3G3JX inverters models, the operator will only display 2 lines
of text.
3G3AX-CAJOP300-EE Remote operator
cable
3 meters cable for connecting
remote operator
3G3AX-OP01 LED remote
operator
LED remote operator, cable
length max. 3m
4X-KITMINI Mounting kit for
LED operator
Mounting kit for LED operator
on panel
Accessories
3G3AX-PCACN2 USB converter /
USB cable
RJ45 to USB connection
cable
USB-convertercable
3G3AX-CTB020-EE RJ45 T-Branch
cable
T cable for RS-422
connection
3G3AX-CTR150-EE RJ45 Terminator
resistor
Terminator resistor for
RS-422 connection
Types Model Description Installation
Software
CX-Drive Computer
software
Configuration and monitoring
software tool
CX-One Computer
software
Configuration and monitoring
software tool
€Saver Computer
software
Software tool for Energy Sav-
ing calculation
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Cat. No. I110E-EN-02
Austria
Tel: +43 (0) 2236 377 800
industrial.omron.at
Belgium
Tel: +32 (0) 2 466 24 80
industrial.omron.be
Czech Republic
Tel: +420 234 602 602
industrial.omron.cz
Denmark
Tel: +45 43 44 00 11
industrial.omron.dk
Finland
Tel: +358 (0) 207 464 200
industrial.omron.fi
France
Tel: +33 (0) 1 56 63 70 00
industrial.omron.fr
Germany
Tel: +49 (0) 2173 680 00
industrial.omron.de
Hungary
Tel: +36 1 399 30 50
industrial.omron.hu
Italy
Tel: +39 02 326 81
industrial.omron.it
Netherlands
Tel: +31 (0) 23 568 11 00
industrial.omron.nl
Norway
Tel: +47 (0) 22 65 75 00
industrial.omron.no
Poland
Tel: +48 22 458 66 66
industrial.omron.pl
Portugal
Tel: +351 21 942 94 00
industrial.omron.pt
Russia
Tel: +7 495 648 94 50
industrial.omron.ru
South Africa
Tel: +27 (0)11 579 2600
industrial.omron.co.za
Spain
Tel: +34 913 777 900
industrial.omron.es
Sweden
Tel: +46 (0) 8 632 35 00
industrial.omron.se
Switzerland
Tel: +41 (0) 41 748 13 13
industrial.omron.ch
Turkey
Tel: +90 212 467 30 00
industrial.omron.com.tr
United Kingdom
Tel: +44 (0) 870 752 08 61
industrial.omron.co.uk
More Omron representatives
industrial.omron.eu
Automation Systems
• Programmable logic controllers (PLC) • Human machine interfaces (HMI) • Remote I/O
• Industrial PC’s • Software
Motion & Drives
• Motion controllers • Servo systems • Inverters • Robots
Control Components
• Temperature controllers • Power supplies • Timers • Counters • Programmable relays
• Digital panel indicators • Electromechanical relays • Monitoring products • Solid-state relays
• Limit switches • Pushbutton switches • Low voltage switch gear
Sensing & Safety
• Photoelectric sensors • Inductive sensors • Capacitive & pressure sensors
• Cable connectors • Displacement & width-measuring sensors • Vision systems
• Safety networks • Safety sensors • Safety units/relay units • Safety door/guard lock switches
Although we strive for perfection, Omron Europe BV and/or its subsidiary and affiliated companies do not warrant
or make any representations regarding the correctness or completeness of the information described in this document.
We reserve the right to make any changes at any time without prior notice.
OMRON EUROPE B.V.
Wegalaan -, NL- JD, Hoofddorp, The Netherlands. Tel: + ()     Fax: + ()     industrial.omron.eu
KPP_JX_EN_INT03
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron: