AC hot-air circulation blower
for solid fuel heating systems
R2E225-AG01-21
ebm-papst Mulfingen GmbH & Co. KG
Bachmühle 2 · D-74673 Mulfingen
Phone +49 7938 81-0
Fax +49 7938 81-110
info1@de.ebmpapst.com
www.ebmpapst.com
Limited partnership · Headquarters Mulfingen
County court Stuttgart · HRA 590344
General partner Elektrobau Mulfingen GmbH · Headquarters Mulfingen
County court Stuttgart · HRB 590142
Nominal data
Type R2E225-AG01-21
Motor M2E068-EC
Phase 1~ 1~
Nominal voltage VAC 230 230
Frequency Hz 50 60
Type of data definition fa fa
Valid for approval / standard CE CE
Speed min-1 2600 2800
Power input W 200 285
Current draw A 0.88 1.25
Motor capacitor µF 6 6
Capacitor voltage VDB 400 400
Capacitor standard P2 (CE) P2 (CE)
Min. back pressure Pa 0 0
Min. ambient temperature °C -25 -25
Max. ambient temperature °C 70 50
ml = max. load · me = max. efficiency · fa = running at free air · cs = customer specs · cu = customer unit
Subject to alterations
Item no. 11835-5-9980 · Revision 75033 · Release 2012-02-22 · Page 1 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
AC hot-air circulation blower
for solid fuel heating systems
R2E225-AG01-21
Technical features
Mass 3.9 kg
Size 225 mm
Surface of rotor Uncoated
Material of impeller Sheet steel, rust-resistant
Number of blades 16
Motor suspension Motor mounted via brackets on one side
Direction of rotation Clockwise, seen on rotor
Type of protection IP 20
Insulation class "F"
Humidity class F0
Max. permissible ambient motor
temp. (transp./ storage)
+ 80 °C
Min. permissible ambient motor
temp. (transp./storage)
- 40 °C
Mounting position Any
Condensate discharge holes None
Operation mode S1
Motor bearing Ball bearing
Touch current acc. IEC 60990
(measuring network Fig. 4, TN
system)
< 0.75 mA
Motor protection Thermal overload protector (TOP) wired internally
Cable exit Axial
Protection class I (if protective earth is connected by customer)
Product conforming to standard EN 60335-1; CE
Approval CSA C22.2 Nr.100; UL 1004-1
Item no. 11835-5-9980 · Revision 75033 · Release 2012-02-22 · Page 2 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
AC hot-air circulation blower
for solid fuel heating systems
R2E225-AG01-21
Product drawing
1 Connection line PFA AWG20, 3 x brass lead tips crimped
Connection screen
U1 Blue Z brown U2 black
Item no. 11835-5-9980 · Revision 75033 · Release 2012-02-22 · Page 3 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
AC hot-air circulation blower
for solid fuel heating systems
R2E225-AG01-21
Charts: Air flow 50 Hz
Druck p f s[Pa]für Rho=1,2kg/m^3
qv [m³/h]
1.4001.3001.2001.1001.0009008007006005004003002001000
qv [cfm]
800750700650600550500450400350300250200150100500
p fs[Pa]
400
380
360
340
320
300
280
260
240
220
200
180
160
140
120
100
80
60
40
20
0
pfs_E[IN H2O]
1,6
1,55
1,5
1,45
1,4
1,35
1,3
1,25
1,2
1,15
1,1
1,05
1
0,95
0,9
0,85
0,8
0,75
0,7
0,65
0,6
0,55
0,5
0,45
0,4
0,35
0,3
0,25
0,2
0,15
0,1
0,05
0
p fs[Pa]
1
2
3
4
Measurement: LU-20206
Air performance measured as per ISO 5801
Installation category A. For detailed
information on the measuring set-up, please
contact ebm-papst. Suction-side noise
levels: LwA measured as per ISO 13347 /
LpA measured with 1m distance to fan axis.
The values given are valid under the
measuring conditions mentioned above and
may vary according to the actual installation
situation. With any deviation from the
standard set-up, the specific values have to
be checked and reviewed with the unit
installed.
Measured values
1
2
3
4
U
V
230
230
230
230
f
Hz
50
50
50
50
n
min-1
2600
2550
2525
2605
Pe
W
200
214
220
200
I
A
0.88
0.93
0.96
0.87
qv
m3/h
1195
975
750
490
pfs
Pa
0
140
260
320
U = Supply voltage · f = Frequency · n = Speed · Pe= Power input · I = Current draw · qv = Air flow · pfs = Pressure increase
Item no. 11835-5-9980 · Revision 75033 · Release 2012-02-22 · Page 4 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
AC hot-air circulation blower
for solid fuel heating systems
R2E225-AG01-21
Charts: Air flow 60 Hz
Druck p f s[Pa]für Rho=1,2kg/m^3
qv [m³/h]
1.6001.5001.4001.3001.2001.1001.0009008007006005004003002001000
qv [cfm]
9008007006005004003002001000
p fs[Pa]
520
500
480
460
440
420
400
380
360
340
320
300
280
260
240
220
200
180
160
140
120
100
80
60
40
20
0
pfs_E[IN H2O]
2,1
2
1,9
1,8
1,7
1,6
1,5
1,4
1,3
1,2
1,1
1
0,9
0,8
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0
p fs[Pa]
1
2
3
4
Measurement: LU-20207
Air performance measured as per ISO 5801
Installation category A. For detailed
information on the measuring set-up, please
contact ebm-papst. Suction-side noise
levels: LwA measured as per ISO 13347 /
LpA measured with 1m distance to fan axis.
The values given are valid under the
measuring conditions mentioned above and
may vary according to the actual installation
situation. With any deviation from the
standard set-up, the specific values have to
be checked and reviewed with the unit
installed.
Measured values
1
2
3
4
U
V
230
230
230
230
f
Hz
60
60
60
60
n
min-1
2800
2670
2590
2800
Pe
W
285
298
304
281
I
A
1.25
1.30
1.32
1.23
qv
m3/h
1285
1035
800
510
pfs
Pa
0
140
260
360
U = Supply voltage · f = Frequency · n = Speed · Pe= Power input · I = Current draw · qv = Air flow · pfs = Pressure increase
Item no. 11835-5-9980 · Revision 75033 · Release 2012-02-22 · Page 5 / 5
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com