49
KLK Fuses
FAST-ACTING ■600 V A C
Fast-acting, high-interrupting capacity,
current-limiting type fuse. Especially suited
for control circuits, street lighting, H.I.D.
lighting, computers, and other applications
without high inrush currents.
Voltage Rating: 600 Volts AC
500 Volts DC
Interrupting Rating: UL Listed 100,000
amperes rms symmetr ical
(Capable of 200,000 amperes)
Ampere Ratings:
KLKD Fuses
FAST-ACTING ■600 V A C/DC
Fast-acting, high-interrupting capacity,
current-limiting type fuse. Especially suited
for DC control circuits, street lighting, H.I.D.
lighting, computers, and other applications.
Voltage Rating: 600 Volts AC/DC
Interrupting Rating: AC:100,000 amperes
rms symmetr ical; DC: 10,000 amperes
Ampere Ratings:
FLM Fuses
TIME-DELAY ■250 V A C
Use FLM 250 volt time-delay fuses to
protect control circuit transfor mers,
solenoids, and other circuits with high
inrush currents. Excellent for supplemental
protection of small motors. For motor
branch-circuit protection, See Class
CC fuses.
Voltage Rating: 250 Volts AC
Interrupting Rating: AC: 10,000 amperes
rms symmetr ical.
Ampere Ratings:
FLQ Fuses
TIME-DELAY ■500 V A C
These 500 volt time-delay fuses provide
excellent supplemental protection of control
power transformers, solenoids, and circuits
with high inrush currents. UL and CSA 500
volt ratings permit use on 480 volt circuits.
FLQ fuses also provide supplemental
protection to small motors. For motor
branch-circuit protection, see Class
CC fuses.
Voltage Rating: 500 Volts AC
Interrupting Rating: 10,000 amperes
rms symmetr ical
Ampere Ratings:
Approvals: Standard 248-14
UL Listed 3/10-30A
(File No: E10480)
CSA Cer tified 3/10-30A
(File No: LR29862)
Versions available to meet
MIL-F-5160/60, QPL F60C:
Contact Factory.
Dimensions: 13/32" x 1-1/2"
Example part number (series & amperage): KLK 1-1/2
Approvals: Standard 248-14
UL Listed 3/10-30A
(File No: E10480)
CSA Cer tified 3/10-30A
(File No: LR29862)
Dimensions: 13/32" x 1-1/2"
Example par t number (series & amperage): KLKD 30
Approvals: Standard 248-14
UL Listed (File No: E10480)
CSA Cer tified
(File No: LR29862)
Dimensions: 13/32" x 1-1/2"
Example par t number (series & amperage): FLM 15
1⁄10 1410
1⁄811⁄2512
2⁄10 2615
1⁄421⁄2720
3⁄10 3825
1⁄231⁄2930
3⁄4
1⁄10 1410
1⁄811⁄2512
2⁄10 2615
1⁄421⁄2720
3⁄10 3825
1⁄231⁄2930
3⁄4
1⁄10 11⁄837
15⁄100 11⁄432⁄10 8
2⁄10 14⁄10 31⁄29
1⁄411⁄2410
3⁄10 16⁄10 41⁄212
4⁄10 18⁄10 515
1⁄225
6⁄10 20
6⁄10 21⁄4625
8⁄10 21⁄261⁄430
12
8⁄10
1⁄10 8⁄10 32⁄10 8
1⁄813
1⁄29
15⁄100 11⁄8410
3⁄16 11⁄441⁄212
2⁄10 11⁄2514
1⁄416⁄10 56⁄10 15
3⁄10 2620
4⁄10 21⁄461⁄425
1⁄221⁄2730
6⁄10 3
RECOMMENDED FUSE BLOCKS
L60030M series. Refer to Fuse Block section of this catalog for additional information.
Midget Fuses
Supplementar y Overcurrent Protection
Approvals: Standard 248-14
UL Listed (File No: E10480)
CSA Cer tified
(File No: LR29862)
Dimensions: 13/32" x 1-1/2"
Example par t number (series & amperage): FLQ 1/2