Specifications are subject to change without notice (09.12.05) 3
Select the desired function
setting the DIP-switches 1
to 4 as shown on the right.
Toaccess the DIP-switches
open the plastic cover using
ascrewdriver as shown on
the right.
If DIP switch 3 is set to ON
(start/stop) the position of
DIP-switch 4 does not affect
the products working mode.
Centre knobs:
Setting of upper and lower
level of cos ϕ0.1 to 0.99.
Lower left knob:
Setting of delay on absolute
scale: 0.1 to 30 s.
Lower right knob:
Setting of power ON delay
on absolute scale: 1 to 30 s.
DWB01, PWB01
Function/Range/Level/Time Setting
Working mode
ON: Contact input for start/stop functions
OFF: Contact input for latch/inhibit functions
Relay status
ON: Relay de-energized in normal condition
OFF: Relay energized in normal condition
Input current range (terminals I1, I2 or 10, 11)
ON: 10A
OFF: 5A/MI input
Contact input (SW4 does not affect the
working mode if SW3 is ON)
ON: Latch function enable
OFF: Inhibit function enable
Mode of Operation (cont.)
well as to a 3-phase asyn-
chronous motor. The relay
energizes as soon as the
power supply is applied.
After the power ON delay,
the unit starts measuring cos
ϕ.If cos ϕis within the set-
points the relay is energized.
As soon as the power factor
drops below the lower set-
point or exceeds the upper
setpoint the output relay
releases and the red LED
turns on after the set time
has expired. To restart the
cos ϕmeasurement, connect
Z1 and U1 (2 and 9) or inter-
rupt the power supply for at
least 1 s.
Example 2
Non-latching mode, relay NE
DWB01 and PWB01 react as
described in the previous
example 1 except for the
automatic reactivation of the
relay as soon as cos ϕis
back within the two set-
points. When the measured
cos ϕexceeds the set upper
level, the red LED starts
flashing. The output relay
releases after the set time
period. When the measured
cos ϕdrops below the set
lower level, the red LED
starts flashing, and the out-
put relay releases after the
set time period. When the
output relay releases there
will be no LED indication.
Example 3
1-Phase load monitoring
DWB01CM2310A and
PWB01CM2310A can be
used for monitoring the pow-
er factor of a 1-Phase load
with 208 to 240 V AC mains
voltage. In this case the pow-
ersupply has to be connect-
edbetween L1, L2 (or 5, 6),
L2and L3 (or 6 and 7) have
to be connected.
Example 4
Start/stop mode, relay NE
In this application DWB01 or
PWB01 are directly connect-
edto a 3-phase asyn-
chronous motor. The relay
energizes as soon as the
power supply is applied and
the start/stop contact is
closed. After the power ON
delay, the unit starts measur-
ing cos ϕ.If cos ϕis within
the setpoints the relay ener-
gizes. As soon as the power
factor drops below the lower
setpoint or exceeds the
upper setpoint the output
relay releases and the red
LED turns ON after the set
time has expired. When the
start/stop contact is opened
the relay de-energizes imme-
diately. To restart the system
just connect the start/stop
contact.
Note 1: to use the start/stop
function the output relay has
tocommand a contactor
connected in series to the
load (see last two wiring dia-
grams).
Note 2: in case of current
below the minimum level the
alarm is conventionally ON.
Note 3: (3-phase voltage):
connect the 3-phase power
supply to the terminals L1,
L2 and L3 (DWB01) - 5, 6
and 7 (PWB01) taking care of
the sequence.
Contact input working mode
CLOSED OPEN
LATCH NOT ACTIVE ACTIVE
INHIBIT ACTIVE NOT ACTIVE
START/STOP START STOP
L2 L3L1
15
16 18
cos j
cos j
U1
U2
Z1
I2I1
Contact input
DWB01
Contact input
PWB01
Notes
1.DIP-switch 3 set ON enables the start/stop
function that is managed by the closing-
opening of the contact input.
2.DIP-switch 3 set OFF enables the input
contact for the latch/inhibit functions: the
selection between these is allows by the DIP
switch 4.
The following table shows how the input con-
tact manages the mode of operation: