Ambient conditions
Altitude max. 3000 m
Permissible humidity (operation) 5 % ... 95 %
Permissible humidity (storage/transport) 5 % ... 95 %
Shock (operation) 10g
Vibration (operation) 2g (0... 200Hz)
General
Housing material PA
Flammability rating according to UL 94 V0
Color black
Total surge current (8/20) µs 50 kA
Total surge current (10/350) µs 15 kA
Mounting type DIN rail mounting with additional retaining screw
Type DIN rail module, two-section, divisible
Surge protection fault message Optical, remote indicator contact
Optical, remote indicator contact
Direction of action L-L / L-PE
Protective circuit
IEC test classification I / II
I / II
T1 / T2
T1 / T2
EN type T1 / T2
T1 / T2
Maximum continuous operating voltage UC75 V DC
Maximum continuous operating voltage UC (L-N) 75 V DC
Rated load current IL55 A (with 6 AWG)
Max. discharge current Imax (8/20) µs 50 kA
Nominal discharge current In (8/20) µs 12.5 kA
Voltage protection level Up≤ 0.7 kV
Residual voltage ≤ 0.6 kV (at 5 kA)
≤ 0.65 kV (at 10 kA)
≤ 0.7 kV
≤ 0.55 kV (at 3 kA)
Max. backup fuse with branch wiring 160 A
160 A