C-UFB- 5DC/E-LAN Order No.: 2809487
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2809487
PHOENIX CONTACT Deutschland GmbH Page 2 / 5
http://www.phoenixcontact.de Feb 2, 2011
Ambient temperature (operation) -40 °C ... 80 °C
Mounting type Connection-specific intermediate plugging
Design Attachment plug
Number of positions 1
Degree of protection IP20
Direction of action Line-Signal Ground/Shield & Signal Ground/Shield-Earth Ground
Width 25.40 mm
Height 93.00 mm
Length 25.40 mm
Protective circuit
IEC category C2
C3
D1
VDE requirement class C2
C3
D1
Maximum continuous voltage UC (wire-wire) - 7.5 V DC (core-shield)
Maximum continuous voltage UC (wire-shield) 0.5 V DC (- 7.5 V DC)
Nominal current IN500 mA (25°C)
Operating effective current IC at UC≤ 100 µA
Ground conductor current IPE ≤ 1 µA
Nominal discharge surge current In (8/20) µs
(Core-Earth)
10 kA
Nominal discharge surge current In (8/20) µs
(Core-Shield)
10 kA
Nominal discharge surge current In (8/20) µs
(Shield-Earth)
10 kA
Total surge current (8/20) µs 10 kA
Output voltage limitation at 1 kV/µs (Core-Earth)
spike
≤ 600 V
Output voltage limitation at 1 kV/µs (Core-Core)
static
≤ 12 V
Output voltage limitation at 1 kV/µs (Core-Earth)
static
≤ 600 V
Residual voltage at In, (conductor-conductor) ≤ 25 V
Residual voltage at In, (conductor-ground) ≤ 400 V
Protection level UP (Core-Core) ≤ 25 V (core-shield)