Protistor DCProtistor fuses DC fuses DC Square-body Fuses Sizes 600 - 602 - 2x602 gR Brackets size 600 - 3500 to 4000 V DC gRB-gRD from 6 to 125 A Dimensions 129 63 47.5 3 48 58 365 394 416 38 9 Weight: 1920 g 13 Main Characteristics Size Current rating IN( A ) 600 6 8 10 12 16 20 25 32 40 50 63 80 80 100 125 Breaking Capacity @ 3500 V DC 30 kA L/R = 30 ms @ 4000 V DC 30 kA L/R = 30 ms @ 4000 V DC 30 kA L/R = 15 ms Watts loss 0.8 IN IN (W) (W) 5.3 7 10.2 11 13.1 14 18 25.5 35 29 42 51 39 50.5 63 9.5 12.7 18.5 20 24 25.4 32.5 46 63 52 76.5 92 67 88 110 Designation Ref. Number Catalog Number CC 35 gRB 600 QF 0006 CC 35 gRB 600 QF 0008 CC 35 gRB 600 QF 0010 CC 35 gRB 600 QF 0012 CC 35 gRB 600 QF 0016 CC 35 gRB 600 QF 0020 CC 35 gRB 600 QF 0025 CC 40 gRB 600 QF 0032 CC 40 gRB 600 QF 0040 CC 40 gRB 600 QF 0050 CC 40 gRB 600 QF 0063 CC 40 gRB 600 QF 0080 CC 40 gRD 600 QF 0080 CC 40 gRD 600 QF 0100 CC 40 gRD 600 QF 0125 S083736 R083735 N089390 V082220 P089391 Q089392 R089393 A086963 B086964 C086965 D086966 E086967 B075763 C075764 D075765 D600GB35C6QF D600GB35C8QF D600GB35C10QF D600GB35C12QF D600GB35C16QF D600GB35C20QF D600GB35C25QF D600GB40C32QF D600GB40C40QF D600GB40C50QF D600GB40C63QF D600GB40C80QF D600GD40C80QF D600GD40C100QF D600GD40C125QF Pack: 1 piece Microswitch MC 2R 3E 1-5NBS Ref. Number: J310025 SCDC58 12/04 Protistor DC fuses Protistor DC fuses DC Square-body Fuses Sizes 600 - 602 - 2x602 gR Brackets size 600 - 3500 to 4000 V DC gRB-gRD from 6 to 125 A Electrical characteristics DC applications data Peak arc voltage vs. working voltage L/R (ms) Um(V) 3 : 3500 V gRB 4 : 4000 V gRB 5 : 4000 V gRD 100 90 80 70 60 50 40 30 20 10 0 10000 1 8000 2 6000 4000 4 5 3 2000 5000 4000 3000 2000 U (V) 1000 0 4800 4400 4000 3600 3200 2800 2400 0 1: L/R = 30 ms-3500-4000 V gRB 2: L/R = 15 ms 4000 V gRD Above: Curves indicate maximum permissible value of time constant L/R as a function of DC working voltage Above: Curves indicate for various time constants L/R the peak arc voltage which may appear across fuse terminals, vs. DC working voltage Max. AC voltage (50/60 Hz): 3600 V with breaking capacity of 30 kA t (s) gRB 10 12 16 20 25 32 40 50 63 80 gRB 8 6 10 4 a= 130 A2=0.6 B1= 1.25 B2= 0.6 Cf3= 0.8 10 3 80 100 125 Time vs. current characteristics gRD a= 130 A2=0.6 B1= 1.25 B2= 0.6 Cf3= 0.8 a= 130 A2=0.6 B1= 1.25 B2= 0.6 Cf3= 0.8 10 2 10 1 10 -1 10 -2 10 -3 10 -4 10 10 2 10 3 10 4 10 10 2 10 3 Above: Curves indicate, for each rated current, the pre-arcing time vs. the R.M.S. pre-arcing current. 12/04 SCDC59 10 4 10 2 10 3 10% tolerance for mean pre-arcing current 10 4 10 5 I (A)