1
POWER ENTRY MODULES WITH LINE FILTER
5
52
20
00
0
www.schurter.com
5200
Inlet filter, front side mounting, fuseholder 5x20 mm
Type 5200, Fuseholder 1-pole with spare compart-
ment
Type 5200, Fuseholder 1-pole with spare compart-
ment
Plug removal necessary for fuse
replacement
C14
70° C
D
De
es
sc
cr
ri
ip
pt
ti
io
on
n
- Panel Mount:
Snap-in or screw-on mounting from front side
- 3 Functions:
Inlet Protection class I, Fuseholder for fuse-links 5 x 20 mm 1-pole,
Line filter in standard and medical version
- Quick connect terminals 6.3 x 0.8 mm
- Alternative: version without line filter 6200
A
Ap
pp
pr
ro
ov
va
al
ls
s
- VDE License Number: 101307
- UL License Number: E72928
C
Ch
ha
ar
ra
ac
ct
te
er
ri
is
st
ti
ic
cs
s
- All single elements are already wired
- Plug removal necessary for fuse-link replacement
Fuse drawer meets requirements of medical standard IEC/EN 60601-1
The fuseholder is accessible from the equipment front
- Qualified for use in equipment according IEC/EN 60950
W
We
eb
bl
li
in
nk
ks
s
Approvals: http://www.schurter.com/approvals
RoHS: http://www.schurter.com/rohs
T
Te
ec
ch
hn
ni
ic
ca
al
l D
Da
at
ta
a
Ratings IEC 1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
Ratings UL/CSA 1 - 10 A @ Ta 40 °C / 125 VAC; 60 Hz
Leakage Current standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
Dielectric Strength > 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
Allowable Operation Temp. -25 °C to 85 °C
Climatic Category 25/085/21acc. to, IEC 60068-1
Degree of Protection from front side IP 40 acc. to IEC 60529
Protection Class Suitable for appliances with protection
class I acc. to IEC 61140
Terminal Quick connect terminals 6.3 x 0.8 mm
Panel Thickness s Screw-on: max 8 mm
Mounting screw torque max 0.5 Nm
Snap-in: 0.8 mm to 3 mm
Material: Housing Thermoplastic, black, UL 94V-0
Appliance-Inlet /-Outlet C14 acc. to IEC/EN 60320-1,
UL 498, CSA C22.2 no. 42 (for cold con-
dition) pin-temperature 70 °C, 10 A, Pro-
tection class I
Fuseholder 1 pole, Shocksafe category PC2 acc. to
IEC 60127-6,
for fuse-links 5 x 20 mm
Rated Power Acceptance @ Ta
23 °C
5 x 20: 2 W (1 pole)
Power Acceptance @ Ta > 23°C Admissible power acceptance at higher
ambient temperature see derating curves
Line Filter Standard and Medical Version, IEC
60939, IEC 60601-1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8
Technical details
MTBF > 2'300'000 h acc. to MIL-HB-217 F