1
POWER ENTRY MODULES WITH LINE FILTER
5
52
20
00
0
www.schurter.com
5200
Inlet filter, front side mounting, fuseholder 5x20 mm
Type 5200, Fuseholder 1-pole with spare compart-
ment
Type 5200, Fuseholder 1-pole with spare compart-
ment
Plug removal necessary for fuse
replacement
C14
70° C
D
De
es
sc
cr
ri
ip
pt
ti
io
on
n
- Panel Mount:
Snap-in or screw-on mounting from front side
- 3 Functions:
Inlet Protection class I, Fuseholder for fuse-links 5 x 20 mm 1-pole,
Line filter in standard and medical version
- Quick connect terminals 6.3 x 0.8 mm
- Alternative: version without line filter 6200
A
Ap
pp
pr
ro
ov
va
al
ls
s
- VDE License Number: 101307
- UL License Number: E72928
C
Ch
ha
ar
ra
ac
ct
te
er
ri
is
st
ti
ic
cs
s
- All single elements are already wired
- Plug removal necessary for fuse-link replacement
Fuse drawer meets requirements of medical standard IEC/EN 60601-1
The fuseholder is accessible from the equipment front
- Qualified for use in equipment according IEC/EN 60950
W
We
eb
bl
li
in
nk
ks
s
Approvals: http://www.schurter.com/approvals
RoHS: http://www.schurter.com/rohs
T
Te
ec
ch
hn
ni
ic
ca
al
l D
Da
at
ta
a
Ratings IEC 1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz
Ratings UL/CSA 1 - 10 A @ Ta 40 °C / 125 VAC; 60 Hz
Leakage Current standard < 0.5 mA (250 V / 60 Hz)
medical < 5 µA (250 V / 60 Hz)
Dielectric Strength > 1.7 kVDC between L-N
> 2.7 kVDC between L/N-PE
Test voltage (2 sec)
Allowable Operation Temp. -25 °C to 85 °C
Climatic Category 25/085/21acc. to, IEC 60068-1
Degree of Protection from front side IP 40 acc. to IEC 60529
Protection Class Suitable for appliances with protection
class I acc. to IEC 61140
Terminal Quick connect terminals 6.3 x 0.8 mm
Panel Thickness s Screw-on: max 8 mm
Mounting screw torque max 0.5 Nm
Snap-in: 0.8 mm to 3 mm
Material: Housing Thermoplastic, black, UL 94V-0
Appliance-Inlet /-Outlet C14 acc. to IEC/EN 60320-1,
UL 498, CSA C22.2 no. 42 (for cold con-
dition) pin-temperature 70 °C, 10 A, Pro-
tection class I
Fuseholder 1 pole, Shocksafe category PC2 acc. to
IEC 60127-6,
for fuse-links 5 x 20 mm
Rated Power Acceptance @ Ta
23 °C
5 x 20: 2 W (1 pole)
Power Acceptance @ Ta > 23°C Admissible power acceptance at higher
ambient temperature see derating curves
Line Filter Standard and Medical Version, IEC
60939, IEC 60601-1, UL 1283, UL 544,
EN 133 200, CSA C22.2 no. 8
Technical details
MTBF > 2'300'000 h acc. to MIL-HB-217 F
2
POWER ENTRY MODULES WITH LINE FILTER
5
52
20
00
0
www.schurter.com
D
Di
im
me
en
ns
si
io
on
ns
s
Length 48.7 mm
Screw-on mounting type 5200
ø 6.3x90˚
29
34
36
36
44
ø 3.5
M3
+0.50
0
max.R3
32+0.2
0
43.7 5
2.5
Snap-in mounting type 5200
29
34
36
+0.20
0
max.R3
32+0.20
0
43.7 5
3.5
T
Te
ec
ch
hn
ni
ic
ca
al
l D
Da
at
ta
a o
of
f F
Fi
il
lt
te
er
r-
-C
Co
om
mp
po
on
ne
en
nt
ts
s
RRaatteedd CCuurrrreenntt
[[AA]]
FFiilltteerr--TTyyppeeIInndduuccttaanncceess
LL [[mmHH]]
CCaappaacciittaannccee
CCXX [[nnFF]]
CCaappaacciittaannccee
CCYY [[nnFF]]
RR [[MM]]
1 Standard Version 2 x 11 47 2.2 -
2 Standard Version 2 x 4 47 2.2 -
4Standard Version 2 x 1.6 47 2.2 -
6Standard Version 2 x 0.7 47 2.2 -
8Standard Version 2 x 0.6 47 2.2 -
10 Standard Version 2 x 0.4 47 2.2 -
1Medical Version (M5) 2 x 11 47 - 1
2Medical Version (M5) 2 x 4 47 - 1
4Medical Version (M5) 2 x 1.6 47 - 1
6Medical Version (M5) 2 x 0.7 47 - 1
8Medical Version (M5) 2 x 0.6 47 - 1
10 Medical Version (M5) 2 x 0.4 47 - 1
3
POWER ENTRY MODULES WITH LINE FILTER
5
52
20
00
0
www.schurter.com
D
Di
ia
ag
gr
ra
am
ms
s
5200 Standard version
1) Line
2) Load
5200 Medical version
1) Line
2) Load
D
De
er
ra
at
ti
in
ng
g c
cu
ur
rv
ve
es
s
1-pole
Admissible power accep-
tance in Watt
0 20 40 60 80 100
I = << In
I = 0.7 In
I = 1.0 In
2.0
1.5
1.0
0.5
0.0
Ambient air temperature Ta °C
A
At
tt
te
en
nu
ua
at
ti
io
on
n l
lo
os
ss
s- - - - differential mode _____ common mode
Standard version
1 A 2 A 4 A 6 A
8 A 10 A
Medical version (M5)
1 A 2 A 4 A 6 A
8 A10 A
4
POWER ENTRY MODULES WITH LINE FILTER
5
52
20
00
0
www.schurter.com
V
Va
ar
ri
ia
an
nt
ts
s
Socket and fuse-carrier included
RRaatteedd CCuurrrreenntt
[[AA]]
FFiilltteerr--TTyyppeePPaanneell mmoouunnttiinnggFFuusseehhoollddeerrOOrrddeerr NNuummbbeerr
1Standard Version Snap-in 1 pole 5200.0143.1
2Standard Version Snap-in 1 pole 5200.0243.1
4Standard Version Snap-in 1 pole 5200.0443.1
6Standard Version Snap-in 1 pole 5200.0643.1
8Standard Version Snap-in 1 pole 5200.0843.1
10 Standard Version Snap-in 1 pole 5200.1043.1
1Standard Version Screw-on 1 pole 5200.0123.1
2Standard Version Screw-on 1 pole 5200.0223.1
4Standard Version Screw-on 1 pole 5200.0423.1
6Standard Version Screw-on 1 pole 5200.0623.1
8Standard Version Screw-on 1 pole 5200.0823.1
10 Standard Version Screw-on 1 pole 5200.1023.1
1Medical Version (M5) Snap-in 1 pole 5200.0143.3
2Medical Version (M5) Snap-in 1 pole 5200.0243.3
4Medical Version (M5) Snap-in 1 pole 5200.0443.3
6Medical Version (M5) Snap-in 1 pole 5200.0643.3
8Medical Version (M5) Snap-in 1 pole 5200.0843.3
10 Medical Version (M5) Snap-in 1 pole 5200.1043.3
1Medical Version (M5) Screw-on 1 pole 5200.0123.3
2Medical Version (M5) Screw-on 1 pole 5200.0223.3
4Medical Version (M5) Screw-on 1 pole 5200.0423.3
6Medical Version (M5) Screw-on 1 pole 5200.0623.3
8 Medical Version (M5) Screw-on 1 pole 5200.0823.3
10 Medical Version (M5) Screw-on 1 pole 5200.1023.3
P
Pa
ac
ck
ka
ag
gi
in
ng
g u
un
ni
it
t
10 Pcs
A
Ac
cc
ce
es
ss
so
or
ry
y
DDeessccrriippttiioonn
Assorted Covers
Cord retaining kits