ACDC
Specification
240 Watts
•Ultra Slim Design
•150% Peak Load for 3 seconds
•Full Power from 40 °C to +60°C
•High Efficiency – Up to 93%
•Hazardous Locations Approval
•Parallel Capability
•3 Year Warranty
DSL240 Series
Input
Input Voltage • 88-264 VAC (120-375 VDC)
Input Frequency • 47-63 Hz
Input Current • 2.3 A at 115 VAC, 1.15 A at 230 VAC
Inrush Current • 24/48 A max at 115/230 VAC
Power Factor • 0.97 typical at 230 VAC
Conforms to EN61000-3-2 Class A.
Earth Leakage Current • 3.5 mA maximum
Input Protection • Internal fuse in line, T5.0 A/250 VAC
Output
Output Voltage • See table
Output Voltage Trim • See table
Initial Set Accuracy • +1% at 100% load
Minimum Load • No minimum load required
Start Up Delay • 1.0 s max
Start Up Rise Time • 150 ms max
Hold Up Time • 25 ms minimum at full load and 115 VAC
Line Regulation • ±1%
Load Regulation • ±1% (±5% in parallel mode)
Transient Response • 10% maximum deviation, recovering to
less than 1% within 2 ms for 50% step
load change at 0.2 A/µs
Ripple & Noise • 100 mV pk-pk maximum, measured with
20 MHz bandwidth
Overvoltage Protection • 12 V output: 15-16.5 V,
24 V output: 30-33 V
Overload Protection • 120-150% of rated current
(see application note)
Short Circuit Protection • Trip and restart (hiccup mode)
auto recovery within 7 s
Temperature • ±0.03%/°C
Coefficient
Thermal Protection • 110°C max, measured on internal heatsink
auto recovery
Parallel Operation • A maximum of 3 units can be paralleled.
Max power available is 90% of total rated
power. Minimum load of 10% required per
unit
Maximum Capacitive • 7000 µF (start up delay increases to 1.5s
Load and rise time to 500 ms)
xppower.com
General
Efficiency • See table
Isolation • 3000 VAC Input to Output
1500 VAC Input to Ground
500 VAC Output to Ground
Switching Frequency • 100 kHz typical PFC & main converter at
230 VAC and full load
DC OK Signal • Volt free contacts rated at 60 VDC/ 0.3 A
on 24 V versions only
Output LED • Green LED to indicate output on. Red LED
to indicate low output voltage. See
mechanical details for operating range.
MTBF • >370 kHrs to BELLCORE Issue 6 at 40 °C,
GB
Environmental
Operating Temperature • -40 °C to +70 °C (see derating curves)
Cooling • Natural convection
Operating Humidity • 20-95% RH, non-condensing
Protection • IP20
Storage Temperature • -40 °C to +85 °C
Operating Altitude • 4850 m
Shock • IEC68-2-27, 4 g, 22 ms half sine, 3 times
in each of 6 axes
Vibration • IEC68-2-6, 10-500 Hz, 2 g 10 mins/sweep.
60 mins for each of 3 axes
EMC & Safety
Emissions • EN55022, class B conducted & radiated
Harmonic Currents • EN61000-3-2, class A
Voltage Flicker • EN61000-3-3
ESD Immunity • EN61000-4-2, 8 KV Contact,
15 KV Air Discharge, Perf Criteria A
Radiated Immunity • EN61000-4-3, 10 V/m Perf Criteria A
EFT/Burst • EN61000-4-4, level 4 Perf Criteria A
Surge • EN61000-4-5, Installation Class 4
Perf Criteria A
Conducted Immunity • EN61000-4-6, 10 V Perf Criteria A
Magnetic Field • EN61000-4-8, level 4, Perf Criteria A
Dips & Interruptions • EN55024, 30% 10 ms, 60% 100 ms,
100% 5000 ms Perf Criteria A, B, B
Safety Approvals • UL508, UL60950-1, EN60950-1, ANSI/ISA
12.12.01 (Class I, Division 2, Groups A, B,
C and D)