258 Slim Relay G2RV
Specifications
■Coil Ratings @ 23°C
■Contact Ratings
■Characteristics
Note: Data shown are of initial values.
Rated voltage Rated current Operate
voltage
Release
voltage
Power consumption Input voltage
AC DC % of rated voltage AC (VA)
Approx.
DC (mW)
Approx.
% of rated
voltage
50 Hz 60 Hz
12 VDC --- --- 27.2 80% max. 10% min. --- 300 mW ±10%
24 VDC --- --- 13.3 --- 300 mW
24 VAC/DC 21.1 22.5 13.0 0.5 VA 300 mW
48 VAC/DC 8.5 9.0 5.2 0.4 VA 250 mW
110 VAC 7.1 7.5 --- 0.8 VA ---
230 VAC 7.3 7.9 --- 1.7 VA ---
Number of poles 1 pole
Load Resistive load
(cos φ = 1)
Inductive load
(cos φ = 0.4, L/R = 7 ms)
Rated load 6 A at 250 VAC;
6 A at 30 VDC
2.5 A at 250 VAC;
2 A at 30 VDC
Rated carry current 6 A
Max. switching voltage 400 VAC, 125 VDC
Max. switching current 6 A
Max. switching power 1,500 VA
180 W
500 VA
60 W
Minimum permissible load 10 mA at 5 VDC : P level: λ60 = 0.1 x 10-6/operation
Item 1 pole
Contact resistance 100 mΩ max.
Operate (set) time 20 ms max.
Release time 40 ms max.
Max. operating frequency Mechanical: 18,000 operations/hr
Electrical: 1,800 operations/hr (under rated load)
Insulation resistance 1,000 MΩ min. (at 500 VDC)
Dielectric strength 4,000 VAC, 50/60 Hz for 1 min between coil and contacts
1,000 VAC, 50/60 Hz for 1 min between contacts of same polarity
Vibration resistance Destruction: 10 to 55 Hz, 1.0 mm double amplitude
Malfunction: 10 to 55 Hz, 1.0 mm double amplitude
Shock resistance Destruction: 1,000 m/s2 (approx. 100G)
Malfunction: 200 m/s2 (approx. 20G)when energized; 100 m/s2 (approx. 10G) when not energized
Life expectancy Mechanical: 5,000,000 operations min.
Electrical: 100,000 typical;
NO 70,000 operations min.;
NC 50,000 operations min.
Ambient temperature Operating: –40°C to 55°C (with no icing or condensation)
Ambient humidity Operating: 5% to 85%
Weight Approx. 35 g
Overvoltage category III
Pollution degree 2
Contact Material AgSnIn
Creepage distance 7.0 mm
Clearance distance 5.5 mm