LEM reserves the right to carry out modications on its transducers, in order to improve them, without prior notice. www.lem.com
Page 1/3
100121/18
IPN = 200 .. 1500 A
VOUT = ± 4 V
Features
Hall effect measuring principle ●
Galvanic isolation between ●
primary and secondary circuit
Isolation voltage 3000 V ●
Low power consumption ●
Extended measuring range ●
(3 x IPN)
Isolated plastic case recognized ●
according to UL 94-V0.
Advantages
Easy installation ●
Small size and space saving ●
Only one design for wide current ●
ratings range
High immunity to external ●
interference.
Applications
DC motor drives ●
Switched Mode Power Supplies ●
(SMPS)
AC variable speed drives ●
Uninterruptible Power Supplies ●
(UPS)
Battery supplied applications ●
Power supplies for welding ●
applications.
Application domain
Industrial ●
Current Transducer HAT 200 .. 1500-S
For the electronic measurement of currents: DC, AC, pulsed,...,
with galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
Electrical data
Type Primary nominal Primary current, RoHS since
current rms measuring range1) date code
IPN (A) IPM (A)
HAT 200-S 200 ± 600 47143
HAT 400-S 400 ± 1200 46115
HAT 500-S 500 ± 1500 46129
HAT 600-S 600 ± 1800 46115
HAT 800-S 800 ± 2400 46115
HAT 1000-S 1000 ± 2500 46097
HAT 1200-S 1200 ± 2500 77271
HAT 1500-S 1500 ± 2500 46158
VC Supply voltage (± 5 %) 1) ± 15 V
IC Current consumption ± 15 mA
RIS Isolation resistance @ 500 VDC > 1000 MΩ
VOUT Output voltage (Analog) @ ± IPN, RL =10 kΩ, TA = 25°C ± 4 V
ROUT Output internal resistance 100 Ω
RL Load resistance > 10 kΩ
X Accuracy @ IPN , TA = 25°C (excluding offset) ≤ ± 1 % of IPN
Accuracy - Dynamic performance data
εL Linearity error 2) (0 .. ± IPN) ≤ ± 1 % of IPN
VOE Electrical offset voltage @ TA = 25°C < ± 20 mV
VOH Hysteresis offset voltage @ IP = 0,
after an excursion of 1 x IPN < ± 10 mV
TCVOE Temperature coefcient of VOE < ± 1 mV/K
TCVOUT Temperature coefcient of VOUT (% of reading) < ± 0.1 %/K
tr Response time to 90 % of IPN step < 5 µs
BW Frequency bandwidth 3) (- 3 dB) DC .. 25 kHz
TA Ambient operating temperature - 10 .. + 80 °C
General data
TS Ambient storage temperature - 25 .. + 85 °C
m Mass 300 g
Notes: 1) Operating at ± 12V ≤ VC < ± 15V will reduce the measuring range
2) Linearity data exclude the electrical offset
3) Please refer to derating curves in the technical le to avoid excessive core
heating at high frequency.