2
www.power-one.com
Edition 2/01.03
DIN Rail Mountable
LOS, LOR, LOK 4000 Series
Protection
Input fuse not user accessible 1.6 A, slow blow
Input transient protection voltage depending resistor (VDR)
Output no-load, overload and short circuit proof
Control
Status indication LED output O.K.
Output voltage adjustment R input - recitfier version 90...110% Uo nom
Output undervoltage monitoring D battery charger typ. 80% Uoset
Safety
Approvals EN 60950, UL 1950, CSA22.2 No. 950, UL 508 listed in progress
Class of equipment I
Electr ic strength test voltage input/ protective ear th, input/output 1.5 kV AC
output/protective earth 1 kV AC
Pollution degree 2
Degree of protection IP 20
EMC
Electrostatic discharge IEC/EN 61000-4-2, level 2 (8 kV) cr iterion B
Electromagnetic field IEC/EN 61000-4-3, level 2 (3 V/m) cr iterion B
Electr. fast transients/bursts IEC/EN 61000-4-4, level 3 (2 kV) cr iterion B
Surge IEC/EN 61000-4-5, level 3, line to prot. earth (2 kV) cr iterion B
IEC/EN 61000-4-5, level 2, line to line (1 kV) cr iterion B
Conducted disturbances IEC/EN 61000-4-6, level 2 (3 V) cr iterion A
Electromagnetic emissions CISPR 22/EN 55022, conducted class B
Environmental
Operating ambient temperature Ui nom, Io nom, convection cooled –10...50°C
Operating case temperature TCUi nom, Io nom –10...80°C
Storage temperature non operational –40...85°C
Damp heat IEC/EN 60068-2-3, 93%, 40°C 21 days
Vibration, sinusoidal IEC/EN 60068-2-6, 10...60/60...2000 Hz 0.15 m m/ 2 gn
Shock IEC/EN 60068-2-27 11 ms / 15 gn
Bump IEC/EN 60068-2-29 11 ms / 10 gn
MTBF MIL-HDBK-217F, 6B, 40° 1'600'000 h
Options and Accessories
Built-in second fuse in the neutral F
No fuse (operation from DC input voltage) F1
System connectors with screw ter minals K
Batter y temperature sensor