SPECIFICATION
MODEL
DCVOLTAGE
RATEDCURRENT
CURRENTRANGE
RATEDPOWER
PEAKCURRENT
PEAKPOWER Note.6
OUTPUT
VOLTAGE ADJ.RANGE
LINEREGULATION
LOADREGULATION
SETUP,RISETIME
HOLDUP TIME (Typ.)
VOLTAGERANGE Note.7
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSHCURRENT (Typ.)
LEAKAGECURRENT
OVERTEMPERATURE
SAFETY STANDARDS
WORKINGTEMP.
DCOKREALY CONTACTRATINGS(max.)
WORKINGHUMIDITY
STORAGETEMP.,HUMIDITY
TEMP.COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVERVOLTAGE
ACCURRENT (Typ.)
1500ms,60ms/230VAC30 atfullload00ms,60ms/115VAC
20ms/230VAC20ms/115VACatfullload
88~264VAC124~370VDC
47~63Hz
89%
0.93/230VAC0.96/115VACatfullload
1.4A/115VAC0.7A/230VAC
29~33V
91%
56~65V
90.5%
35A/115VAC70A/230VAC
<1mA /240VAC
Normallyw morethan3 andthenshutdowno/pvoltageorkswithin110~150%ratedoutputpowerfor seconds
14~17V
>150%ratedpower,constantcurrentlimitingwithauto-recoverywithin3secondsandshutdowno/pvoltageafter3seconds
Protectiontype:Shutdowno/pvoltage,re-powerontorecover
95 5 (TSW:detectonheatsinkofpowerswitch)
Protectiontype:Shutdowno/pvoltage,recoversautomaticallyaftertemperaturegoesdown
UL508 TUVEN60950-1approved,
CompliancetoEN55022(CISPR22)ClassB, EN61000-3-2,-3
CompliancetoEN61000-4-2,3,4,5,6,8,11,EN55024,EN61000-6-2(EN50082-2),EN61204-3,heavyindustrylevel,criteria A,
SEMIF47,GL approved
-25~+70 (Referto"DeratingCurve")
60Vdc/0.3A,30Vdc/1A,30Vac/0.5A resistiveload
20~95%RHnon-condensing
-40~+85 ,10~95%RH
0.03%/ (0~50
Component:10~500Hz,2G10min./1cycle,60min.eachalongX, Y,Zaxes;Mounting:CompliancetoIEC60068-2-6
289.9Khrsmin.MIL-HDBK-217F(25 )
40*125.2*113.5mm(W*H*D)
0.67Kg;20pcs/14.4Kg/1.16CUFT
POWERFACTOR (Typ.)
SDR-120-24 SDR-120-48
24V 48V
5A 2.5A
0~5A 0~2.5A
120W 120W
7.5A 3.75A
100mVp-p 120mVp-p
24~28V 48~55V
1.0% 1.0%
0.5% 0.5%
1.0% 1.0%
SDR-120-12
12V
10A
0~10A
120W
15A
180W(3sec.)
100mVp-p
12~14V
1.0%
0.5%
1.0%
Features :
SDR-120 series
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
I/P-O/P:3KVACI/P-FG:1.5KVACO/P-FG:0.5KVAC O/P-DCOK:0.5KVAC
I/P-O/P,I/P-FG,O/P-FG:>100MOhms/500VDC/25 /70%RH
ENVIRONMENT
SAFETY &
FUNCTION
EMC
(Note4)
PROTECTION
RIPPLE&NOISE(max.) Note.2
VOLTAGETOLERANCE Note.3
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. 3 seconds max., please refer to peak loading curves.
7. Derating may be needed under low input voltage. Please check the derating curve for more details.
120WSingleOutputIndustrialDINRAIL withPFCFunction
High efficiency 91% and low power dissipation
Built-in active PFC function, PF>0.93
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508 (industrial control equipment) approved
EN61000-6-2(EN50082-2) industrial immunity level
100% full load burn-in test
3 years warranty
150% peak load capability
Built-in DC OK relay contact
FileName:SDR-120-SPEC2011-08-23
GL
PQ
SEMIF47
EMCIMMUNITY
EMCEMISSION