Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
36
1Power Protection and Conditioning
The MCR Hardwired Series provides excellent noise
ltering and surge protection to safeguard connected
equipment from damage, degradation or misoperation.
Combined with the excellent voltage regulation inherent to
SolaHD’s ferroresonant design, the MCR can increase the
actual Mean Time Between Failure (MTBF) of protected
equipment. The MCR is a perfect choice where dirty power,
caused by impulses, swell, sags, brownouts and waveform
distortion can lead to costly downtime because of damaged
equipment.
Features
±3% output voltage regulation
Noise attenuation
- 120 dB common mode
- 60 dB transverse mode
Surge protection tested to ANSI/IEEE
C62.41 Class A & B Waveform:
- <10 V let through typical
Acts as a step-up or step-down transformer
Harmonic ltering
Hardwired
Galvanic isolation provides exceptional
circuit protection.
25 year typical MTBF
No maintenance required
Applications
• Industrial automation and control equipment PLCs
• Machine tools
• Computer loads and electronic equipment
• Robotics
• Semiconductor fabrication equipment
MCR Hardwired Series – Power Line Conditioning with Voltage Regulation
Selection Tables: Single Phase
Group 2 – MCR Series, 60 Hz Only
* Canadian option: cULus certied units must be ordered by changing “-8” (UL only) to “-C8”.
** UL Listed Only. Use Group 3 for CSA only models.
VA Catalog Number Voltage Input Voltage Output Height
(inch)
Width
(inch)
Depth
(inch)
Ship Weight
(lbs)
Design
Style
Elec
Conn
120 63-23-112-4 120, 208, 240, 480 120 9 4 5 15 1 D
250 63-23-125-4 120, 208, 240, 480 120 10 6 827 1 D
500 63-23-150-8 120, 208, 240, 480 120, 208, 240 13 9 7 37 1E
750 63-23-175-8 120, 208, 240, 480 120, 208, 240 14 9 7 52 1E
1000* 63-23-210-8 120, 208, 240, 480 120, 208, 240 17 9 7 62 1 E
1500* 63-23-215-8 120, 208, 240, 480 120, 208, 240 17 13 995 1E
2000* 63-23-220-8 120, 208, 240, 480 120, 208, 240 18 13 9 109 1 E
3000* 63-23-230-8 120, 208, 240, 480 120, 208, 240 19 13 9142 1E
5000* 63-23-250-8 120, 208, 240, 480 120, 208, 240 28 13 9 222 1 E
7500** 63-28-275-8 208, 240, 480 120, 208, 240 27 26 9 362 2F
10000** 63-28-310-8 208, 240, 480 120, 208, 240 28 26 9 446 2F
15000** 63-28-315-8 208, 240, 480 120, 208, 240 28 38 10 710 3 F
Related Products
On-line UPS (S4K Industrial)
Surge Protection
Three Phase Power Conditioners
Active Tracking® Filters
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 37
1
Power Protection and Conditioning
Group 4 – MCR Series, 50 Hz Only (±5% output voltage regulation)
Selection Tables: Single Phase
Group 3 – MCR Series, 60 Hz Only
Specifications
VA Catalog Number Voltage Input Voltage Output Height
(inch)
Width
(inch)
Depth
(inch)
Ship weight
(lbs)
Design
Style
Elec
Conn
500 63-31-150-8 600 120, 208, 240 13 9 7 38 1B
1000 63-32-210-8 600 120, 208, 240 17 9 7 62 1 B
2000 63-32-220-8 600 120, 208, 240 18 13 10 109 1 B
3000 63-32-230-8 600 120, 208, 240 19 13 10 142 1B
5000 63-29-250-8 * 208, 240, 480, 600 120, 208, 240 28 13 10 221 1 A
7500 63-29-275-8 * 208, 240, 480, 600 120, 208, 240 27 25 10 360 2A
10000 63-29-310-8 * 208, 240, 480, 600 120, 208, 240 28 25 10 441 2A
15000 63-29-315-8 * 208, 240, 480, 600 120, 208, 240 28 38 10 706 3 A
VA Catalog Number Voltage Input Voltage Output Height
(inch)
Width
(inch)
Depth
(inch)
Ship weight
(lbs)
Design
Style
Elec
Conn
120 63-23-612-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 9 6 8 24 1 C
250 63-23-625-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 11 6 827 1 C
500 63-23-650-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 13 9 7 40 1 C
1000 63-23-710-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 18 9 7 64 1 C
2000 63-23-720-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 18 13 10 113 1 C
3000 63-23-730-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 27 13 10 162 1 C
5000 63-23-750-8 110, 120, 220, 240, 380, 415 110, 120, 220, 240 30 13 10 266 1 C
7500 63-28-775-8 220, 240, 380, 415 110, 120, 220, 240 28 26 10 393 2 C1
10000 63-28-810-8 220, 240, 380, 415 110, 120, 220, 240 30 26 10 490 2 C2
15000 63-28-815-8 220, 240, 380, 415 110, 120, 220, 240 30 38 10 776 3C2
Parameter Condition Value
Input
Voltage
Continuous at full load (lower input voltage possible at lighter load) +10% to -20% of nominal
For temporary surge or sags +20% to -35% of nominal
Current1at Full Load & 80% of nominal input voltage Iin (VA/.89)/(Vin x 80%)
Frequency See Operating Characteristics section for details. 50 Hz or 60 Hz depending on model
Output
Line Regulation Vin >80% and <110% of nominal ± 5% for 50 Hz units, ± 3% for 60 Hz units
Overload Protection At Nominal Input Voltage Current limited at 1.65 times rated current
Output Harmonic Distortion At full load within input range 3% total RMS content
Noise Attenuation Common Mode
Transverse Mode
120 dB
60 dB
General
Efficiency At Full Load Up to 92%
Storage Temperature Humidity <95% non-condensing -20° to +85°C
Operating Temperature Humidity <95% non-condensing -20° to 50°C
Audible Noise Full Resistive Noise 35 dBA to 65 dBA
Approvals
60 Hz Models UL1012, CSA evaluated by UL
50 Hz Models CE (EMC & LVD)
Warranty See General Information section for details 10 + 2 Years
Notes: 1 - Consult user manual for fuse sizing.
2 - It is recommended that the unit run at a minimum of 40-50% load.
* CSA only models.
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
38
1Power Protection and Conditioning
Primary Voltage Interconnect Connect Lines To
208 H1 to H4
H2 to H5 H1 & H5
240 H1 to H4
H3 to H6 H1 & H6
480 H3 to H4 H1 & H6
600 H3 to H4 H1 & H7
Secondary Voltage Interconnect Connect Lines To
120 X1 & X2 or X3 & X2
208 X4 & X5
240 X1 & X3
Primary
Voltage Interconnect Connect Lines To
600 H1 & H2
Secondary
Voltage Interconnect Connect Lines To
120 X1 & X2 or X3 & X2
208 X4 & X5
240 X1 & X3
Primary Voltage Interconnect Connect Lines To
110-120 H1 to H3
H2 to H4 H1 & H4
220-240 H2 to H3 H1 & H4
380-415 H2 to H3 H1 & H5
Secondary Voltage Interconnect Connect Lines To
110 X1 & X2 or X3 & X2
120 X4 & X2 or X5 & X2
220 X1 & X3
240 X4 & X5
Primary Voltage Interconnect Connect Lines To
220-240 H1 to H3
H2 to H5 H1 & H5
380-415 H2 to H3 H1 & H4
Secondary Voltage Interconnect Connect Lines To
110 X1 & X2 or X2 & X3
120 X4 & X2 or X5 & X2
220 X1 & X3
240 X4 & X5
Primary Voltage Interconnect Connect Lines To
220-240 H2 to H3 H1 & H4
380-415 H2 to H3 H1 & H5
Secondary Voltage Interconnect Connect Lines To
110 X1 & X2 or X3 & X2
120 X4 & X2 or X5 & X2
220 X1 & X3
240 X4 & X5
Primary Voltage Interconnect Connect Lines To
120 H1 & H2
208 H1 & H3
240 H1 & H4
480 H1 & H5
Secondary Voltage Interconnect Connect Lines To
120 X1 & X2
Electrical Connections
MCR 60 Hz 5000–15000 VA MCR 60 Hz 500–3000 VA MCR 50 Hz 120–5000 VA
MCR 50 Hz 7500 VA MCR 50 Hz 10000–15000 VA
MCR 60 Hz 120–250 VA
BC
C1 C2 D
A
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com. 39
1
Power Protection and Conditioning
Primary Voltage Interconnect Connect Lines To
120 H1 to H3 to H6 to H8
H2 to H5 to H7 to H10 H1 & H2
208 H2 to H3 H7 to H8
H1 to H6 H4 to H9 H1 & H4
240 H2 to H3 H7 to H8
H1 to H6 H5 to H10 H1 & H5
480 H2 to H3 H5 to H6
H7 to H8 H1 & H10
Secondary Voltage Interconnect Connect Lines To
120 X1 & X2 or X3 & X2
240 X1 & X3
30 & 60 VA
Primary Voltage
120 VA
Primary Voltage
7500 VA
Primary Voltage Interconnect Connect
Lines To
120 N/A N/A Note: H3 & H4
are not used H1 & H2
N/A 120 240 H1 to H3
H2 to H4 H1 & H4
N/A 240 480 H2 to H3 H1 & H4
30 & 60 VA
Secondary Voltage
120 VA
Secondary Voltage
7500 VA
Secondary Voltage Interconnect Connect
Lines To
120 120 N/A X1 & X2
N/A N/A 120 X1 & X2 or
X3 & X2
N/A N/A 240 X1 & X3
Primary Voltage Interconnect Connect Lines To
120 H1 to H3 to H5 to H7
H2 to H4 to H6 to H8 H1 & H2
240 H2 to H3 H6 to H7
H1 to H5 H4 to H8 H1 & H4
480 H2 to H3 H4 to H5
H6 to H7 H1 & H8
Secondary Voltage Interconnect Connect Lines To
120 X1 & X2
Primary Voltage Interconnect Connect Lines To
120 H1 & H2
208 H1 & H3
240 H1 & H4
480 H1 & H5
Secondary Voltage Interconnect Connect Lines To
120 X1 & X2 or X3 & X2
208 X4 & X5
240 X1 & X3
MCR 60 Hz 500–5000 VA MCR 60 Hz 7500, 10000 and 15000 VA CVS 60 Hz 250 VA only
CVS 60 Hz 500–5000 VA
EFG
HJ
Series-Multiple Primary
with Tap for two input voltages
Electrical Connections
CVS 60 Hz 30–120 VA & 7500 VA
Note:
Secondaries are
not grounded.
Ground X2 per
Code.
Open MCR/CVS terminal
Primary Voltage Interconnect Connect Lines To
208 H2 & H3
240 H2 & H4
480 H1 & H4
Secondary Voltage Interconnect Connect Lines To
120 X1 & X2 or X3 & X2
208 X4 & X5
240 X1 & X3